Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout30 Alkali Creek Rd - 185521400081Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970) 328-8730
Fax: (970) 328-7185
Permit
Permit No. OWTS-018860-2020
Permit Type: OWTS Permit
Work Classification: New
Permit Status: Active
Issue Date: 8/29/2020 Expires: 12/28/2020
On-Site Wastewater
Treatement System
Project Address Parcel Number
30 ALKALI CREEK RD, WOLCOTT AREA,185521400081
Owner Information Address
Andrew Isaacson PO Box1803
Gypsum, CO 81637
Phone: (970) 471-1740
Cell: (970) 471-1740
Email: aisaacson1@gmail.com
Inspections:
For Inspections Call: (970) 328-8755
and call the Design Engineer
Engineer Phone Email
KUMAR & ASSOCIATES, Dave Young (970) 945-7988 dyoung@kumarusa.com
Contractor License Number Phone Email
Andrew Isaacson aisaacson1@gmail.com(970) 471-1740OWTSPL-000060-20
20
Permitted Construction / Details:
Instal the OWTS exactly as depicted in the Kumar & Associates, Inc design dated August 5, 2020, stamped, signed,
and dated August 6, 2020 by David A. Young. The OWTS is designed to serve a three-bedroom single family
residence.
The OWTS will consist of a 1,000 gallon two-compartment Valley Precast Septic tank with an effluent filter in the
outlet tee, followed by a distribution box, set level on compacted screened gravel and made accessible at grade,
with speed levelers set to equally distribute effluent to 900 square feet of soil treatment area via three shallow
trenches not more than one foot deep to allow for four feet of separation distance from the infiltrative surface to
bedrock. Install 25 Infiltrator Quick4 Plus Standard chambers in each trench for a total of 75 chambers. Scarify the
trench sidewalls and bottoms prior to placement of chambers.
Contact Eagle County Environmental Health and the design engineer well in advance of requesting inspections prior
to backfilling any component of the OWTS. The design engineer is responsible for conducting all inspections
necessary to certify the installation and assure the functionality of the system. System certification, along with
photos and a record drawing is required to be submitted to and approved by Eagle County Environmental Health
prior to the use of the system or occupancy of the dwelling.
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS OF
ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Claire Lewandowski
Date
August 29, 2020
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Saturday, August 29, 2020 1
INSPECTION WORKSHEET (WOLCOTT AREA - 30 ALKALI CREEK - 508172)
FOR EAGLE COUNTY GOVERNMENT
OWTS-018860-2020Case Number:Case Module:Permit Management
06/25/2021 ApprovedInspection Status:Inspection Date:
OWTS Final InspectionInspection Type:Inspector:
Job Address:Parcel Number:30 Alkali Creek Rd
Wolcott Area, CO
185521400081
Company Name NameContact Type
Contractor Andrew Isaacson Andrew Isaacson
Engineer KUMAR & ASSOCIATES Dave Young
Owner Andrew Isaacson Andrew Isaacson
CommentsPassedChecklist Item
True A Valley Precast 1,000 gallon two chamber septic tank was used.Septic Tank - Septic Tank
True Received 3/29/2022 from K&A.Record Drawing - Record Drawing
True Received 3/29/2022 from K&A.Record Photos - Record Photos
True Received 8/29/2020 from K&A.Site and Soil - Site & Soil
True Received 3/29/2022 from K&A.Final Certification Letter - Final Certification Letter
True Received 8/29/2020 from K&A.General Plan - General Plan
True 3 rows of 25 Infiltrator Quick4 Plus Standard chambers for a total
of 75.
Soil Treatment Area (STA) - Soil Treatment Area (STA)
True Drew Issacson is the licensed installer.Identification of Systems Contractor - Identification of
Systems Contractor
March 31, 2022 Page 1 of 1P.O. Box 179, 500 Broadway, Eagle, CO 81631-0179
5020 County Road 154
Glenwood Springs, CO 81601
phone: (970) 945-7988
fax: (970) 945-8454
email: kaglenwood@kumarusa.com
www.kumarusa.com
Office Locations: Denver (HQ), Parker, Colorado Springs, Fort Collins, Glenwood Springs, and Summit County, Colorado
March 25, 2022
Drew and Kate Isaacson
P. O. Box 1803
Gypsum, Colorado 81637
(aisaacson1@gmail.com)
Project No. 19-7-719.02
Permit No. OWTS-018860-2020
Subject: Certification of Onsite Wastewater Treatment System, Proposed Residence,
Parcel HM33, Horse Mountain Ranch, 30 Alkali Creek Road, Eagle County,
Colorado
Dear Drew and Kate:
A representative of Kumar & Associates observed the installation of the Onsite Wastewater
Treatment System (OWTS) for the residence at the subject site as required by the Eagle County
Environmental Health Department. Our observations and recommendations are presented in this
report. The services are supplemental to Kumar & Associates agreement for professional
services to you dated December 6, 2019.
We previously designed the OWTS for the residence as submitted in our report dated August 5,
2020, Project No. 19-7-719.02. The system was designed for a total of three bedrooms and six
persons. The system was installed by Drew Isaacson.
We performed our evaluation on June 29 and September 30, 2021. The OWTS components
observed included: cleanout, septic tank, effluent line, distribution box and soil treatment area
(STA) and the locations of these components. The installation and locations of the system
components were verified as shown on Figure 1. Pictures of the OWTS components made
during the site visit are included with this report. Trench cuts for the STA were a maximum of
foot deep. The distance locations to the septic tank shown on Figure 1 were made by taping.
The installation of the water line crossing the sewer line and the installation of the septic tank
was not observed. No photographs of the water line crossing were able to be obtained from the
installer. Per the installer, the water line was encased for five feet on both sides of the sewer line
crossing.
It is our opinion that the OWTS was installed in general conformance with the above referenced
design.
The observations and recommendations presented above are based on our site observations and
our experience in the area. We make no warranty either express or implied. Alterations to the
Kumar & Associates
OWTS PHOTOGRAPH LOG
PROPOSED RESIDENCE
PARCEL HM33, HORSE MOUNTAIN RANCH
30 ALKALI CREEK ROAD
EAGLE COUNTY, COLORADO
Project No. 19-7-719.02
Photograph 1: Cleanout and
sewer line exiting residence.
Photograph 2: Sewer line and
water line crossing. Water line
not yet encased.
OWTS PHOTOGRAPH LOG
PROPOSED RESIDENCE
PARCEL HM33, HORSE MOUNTAIN RANCH
30 ALKALI CREEK ROAD
EAGLE COUNTY, COLORADO
Project No. 19-7-719.02
Photograph 3: Valley Precast
1,000 gallom, two-compartment
septic tank with effluent filter on
outlet.
Photograph 4: Effluent and
sewer lines. Septic tank yet to
be set near middle of picture.
OWTS PHOTOGRAPH LOG
PROPOSED RESIDENCE
PARCEL HM33, HORSE MOUNTAIN RANCH
30 ALKALI CREEK ROAD
EAGLE COUNTY, COLORADO
Project No. 19-7-719.02
Photograph 5: Effluent line to
distribution box and to trenches.
Photograph 6: Tuf-Tite 4-Hole
Distibrution Box with Speed
Levels installed.
OWTS PHOTOGRAPH LOG
PROPOSED RESIDENCE
PARCEL HM33, HORSE MOUNTAIN RANCH
30 ALKALI CREEK ROAD
EAGLE COUNTY, COLORADO
Project No. 19-7-719.02
Photograph 7: Chambers
installed in STA trenches with
observation ports. Note cuts less
than 1 foot.
Photograph 8: Graded STA.
5020 County Road 154
Glenwood Springs, CO 81601
phone: (970) 945-7988
fax: (970) 945-8454
email: kaglenwood@kumarusa.com
www.kumarusa.com Office Locations: Denver (HQ), Parker, Colorado Springs, Fort Collins, Glenwood Springs, and Summit County, Colorado
ONSITE WASTEWATER TREATMENT SYSTEM DESIGN
PROPOSED RESIDENCE
PARCEL HM33, HORSE MOUNTAIN RANCH
30 ALKALI CREEK ROAD
EAGLE COUNTY, COLORADO
PROJECT NO. 19-7-719.02
AUGUST 05, 2020
PREPARED FOR:
DREW AND KATE ISAACSON
P. O. BOX 1803
GYPSUM, COLORADO 81637
(aisaacson1@gmail.com)
Kumar & Associates, Inc. Project No. 19-7-719.02
TABLE OF CONTENTS
INTRODUCTION ...................................................................................................................... - 1 -
PROPOSED CONSTRUCTION ................................................................................................ - 1 -
SITE CONDITIONS ................................................................................................................... - 1 -
SUBSURFACE CONDITIONS ................................................................................................. - 1 -
OWTS ANALYSIS .................................................................................................................... - 3 -
DESIGN RECOMMENDATIONS ............................................................................................ - 3 -
SOIL TREATMENT AREA................................................................................................... - 3 -
OWTS COMPONENTS ......................................................................................................... - 4 -
OWTS OPERATION AND MAINTENANCE.......................................................................... - 7 -
OWTS HOUSEHOLD OPERATION .................................................................................... - 7 -
OWTS MAINTENANCE ....................................................................................................... - 8 -
OWTS CONSTRUCTION OBSERVATION ............................................................................ - 8 -
LIMITATIONS ........................................................................................................................... - 8 -
FIGURES
FIGURE 1 – OWTS SITE PLAN
FIGURE 2 – USDA GRADATION TEST RESULTS
FIGURE 3 – SOIL TREATMENT AREA CALCULATIONS
FIGURE 4 – SOIL TREATMENT AREA PLAN VIEW
FIGURE 5 – SOIL TREATMENT AREA CROSS SECTION
ATTACHMENTS
VALLEY PRECAST 1,000 GALLON, TWO-CHAMBER SEPTIC TANK DETAIL
TUF-TITE 4-HOLE DISTRIBUTION BOX
Kumar & Associates, Inc. Project No. 19-7-719.02
INTRODUCTION
This report provides the results of an onsite wastewater treatment system (OWTS) design for the
proposed residence to be located on Parcel HM33, Horse Mountain Ranch, 30 Alkali Creek
Road, near Wolcott, Eagle County, Colorado. The purpose of the report is to provide design
details for the OWTS in accordance with the 2018 Eagle County Environmental Health
Department Onsite Wastewater Treatment System Regulations and the Colorado Department of
Public Health and Environmental Regulation #43. The services were performed as part of our
agreement for professional services to Drew and Kate Isaacson dated December 6, 2019. We
previously conducted a subsoil study for foundation design of the proposed residence at the site
and presented our findings in a report dated January 6, 2020, Project No. 19-7-719.
PROPOSED CONSTRUCTION
The proposed construction will consist of a single-family residence located on the site as shown
on Figure 1. The residence will be a three-bedroom structure and include a walkout basement
level and an attached garage. The OWTS will be designed for a total of three bedrooms. The
proposed soil treatment area (STA) for the OWTS will be located to the northeast of the
residence as shown on Figure 1. Water service will be provided by an existing on-site well
located near the east edge of the property as shown in the inset on Figure 1. The route of the
water supply line from the well to the residence has been roughly designed.
If proposed construction is different than that described, we should be contacted to re-evaluate
our design recommendations.
SITE CONDITIONS
The parcel was vacant with a rough-cut driveway to the proposed residence location at the time
of our field exploration. There are two apparently abandoned water wells on the lot, one to the
northwest of the proposed residence and the other near the southeast corner of the lot. Water will
be supplied to the residence by a new well on the eastern edge of the lot, approximately 800 feet
east of the proposed STA, see Figure 1. The terrain in the area of the proposed residence and
proposed OWTS is moderately sloping down to the east at grades from about 8 to 12%.
Vegetation consists of grass and weeds with sage brush and juniper trees.
SUBSURFACE CONDITIONS
The field exploration for the OWTS was conducted on July 9, 2020. Two profile pits (Profile
Pits 1 and 2) were excavated with a mini-excavator at the approximate locations shown on
- 2 -
Kumar & Associates, Inc. Project No. 19-7-719.02
Figure 1 to evaluate the subsurface conditions at the planned soil treatment area for the OWTS.
The pits were logged by a representative of Kumar & Associates. Logs of the profile pits are
provided below.
Log of Profile Pit 1
Depth USDA Classification
0-1’ TOPSOIL; organic Loam, firm, slightly moist, dark brown.
1’-4’ SILTY CLAY LOAM; strong blocky structure, very stiff, slightly moist, brown.
4’-5’ GRAVELLY SANDY LOAM; massive structure, medium dense, slightly moist,
brown.
5’-6’ WEATHERED CLAYSTONE BEDROCK; hard, slightly moist, gray.
• Disturbed bulk sample obtained from 2 to 3 feet.
• Bottom of pit @ 6 feet where digging refusal with the mini-excavator occurred.
• No groundwater or redoximorphic features observed at time of pit excavation.
Log of Profile Pit 2
Depth USDA Classification
0-1’ TOPSOIL; organic Loam, firm, slightly moist, dark brown.
1’-3½’ SILTY CLAY LOAM; strong blocky structure, very stiff, slightly moist, brown.
3½’-5’ GRAVELLY SANDY LOAM; massive structure, medium dense, slightly moist,
brown.
5’-6’ WEATHERED CLAYSTONE BEDROCK; hard, slightly moist, gray.
• Bottom of pit @ 6 feet where digging refusal with the min-excavator occurred.
• No groundwater or redoximorphic features observed at time of pit excavation.
The soils encountered in profile pits, below about 1 foot of organic topsoil, consisted of about
2½ to 3 feet of Silty Clay Loam overlying 1 to 1½ feet of gravelly Sandy Loam. Weathered
claystone bedrock was encountered in both profile pits at 5 feet depth. Practical digging refusal
was encountered with the mini-excavator in the bedrock due to hardness at depths of 6 feet in
both pits. Hydrometer and gradation analyses were performed on a disturbed bulk sample of the
Silty Clay Loam soils from Profile Pit 1 from 2 to 3 feet depth with the results provided on
Figure 2. The tested sample (minus No. 10 size sieve fraction) classified as Silty Clay Loam per
the USDA system. No free water was encountered in the pits nor indications of seasonal high
groundwater were observed at the time of excavation. We did not encounter groundwater in our
borings drilled for the subsoil study at the residence site in December 2019.
Based on the subsurface conditions and laboratory testing, the soils at the STA have been
classified as Type 3 per State regulations, which equates to a long-term acceptance rate (LTAR)
of 0.35 gallons per square foot per day.
- 3 -
Kumar & Associates, Inc. Project No. 19-7-719.02
OWTS ANALYSIS
Based on the site conditions and profile pit evaluations, the evaluated area should be suitable for
a conventional infiltration disposal system. The system will consist of chambers in a trench
configuration based in the Silty Clay Loam soils. The STA will be sized for three bedrooms (six
persons) and an average daily flow of 75 gallons per person and an LTAR of 0.35 gallons per
square foot per day for the natural Silty Clay Loam soils.
The effluent will gravity flow from the residence to the septic tank for primary treatment and
then gravity flow to the STA for dispersal and final treatment. The STA will consist of three
trenches with Infiltrator Quick 4 Plus Standard chambers. Equal distribution will be provided to
the chambers and trenches by a distribution box.
A 100 feet minimum setback is required from the STA to the onsite wells. Based on site plan
measurements, the STA appears to be far outside any setbacks to the wells. The route of the
planned water supply line to the residence is roughly planned as shown on Figure 1. The
required setback of the water line to the septic tank is 10 feet, 5 feet for sewer and effluent lines,
and 25 to the STA. The setback from the proposed water supply cistern is 50 feet to the sewer
and effluent lines and septic tanks, and 100 feet to the STA. The sewer line as designed will
encroach on the setback to the cistern and will cross the water line. The sewer line should be
encased in larger diameter Schedule 40 pipe with both ends of the encasement capped and sealed
watertight throughout the length of the encroachment. This needs to be verified in the field as
part of our certification of the OWTS.
DESIGN RECOMMENDATIONS
The design recommendations presented below are based on the proposed construction, the site
and subsurface conditions encountered and our experience in the area. A layout of the proposed
OWTS components is provided on Figure 1. If conditions encountered during construction are
different than those that are described in this report, please contact us to re-evaluate our design
recommendations.
SOIL TREATMENT AREA
• The STA will consist of three trenches with 25 Infiltrator Quick 4 Plus Standard
chambers placed in each trench (75 chambers total) in the native soils. Equal distribution
will be provided to the trenches by a distribution box.
• The STA was sized based on an LTAR of 0.35 gallons per square feet per day.
• Each chamber was allowed 12 square feet of area. A 30% reduction of the STA size was
applied for use of Infiltrator chambers in a trench configuration. The total STA design
size is 900 square feet. Soil treatment area calculations are shown on Figure 3.
- 4 -
Kumar & Associates, Inc. Project No. 19-7-719.02
• A minimum of four feet of undisturbed soil between trenches is required.
• Trench cut depths for the Infiltrators should be a maximum of 1 foot deep to provide a
minimum 4 feet of separation to the weathered bedrock.
• The trenches should be oriented along ground contours to minimize soil cut and cover.
• The base and sidewalls of the trench excavations should be scarified prior to the chamber
placement.
• A minimum of 12 inches and a maximum of 24 inches of cover soil should be placed
over the chambers. Additional cover soil should be placed between trenches as needed to
provide a uniform ground surface.
• Backfill should be graded to deflect surface water away from the STA and should be
sloped at 3 horizontal to 1 vertical or flatter. A swale to divert surface water flow away
from the STA will likely be needed along the upslope side of the STA.
• Disturbed soil should be re-vegetated as soon as possible with a native grass mix. No
trees, shrubs or other plants with deep roots should be planted on or near the STA as this
may damage the system piping.
• Four-inch diameter inspection ports should be installed vertically into the knockouts
provided in the chamber end caps. Install ports at each end of the trench. The inspection
port piping should be screwed into the top to the chambers and should not extend down to
the ground surface inside the chambers. The inspection ports should extend at least 8
inches above the finished ground surface or be protected in a valve box at finished grade.
• The STA must be a minimum of 25 feet from the potable water supply line.
• A plan view of the STA is presented on Figure 4 and a cross section of the STA is
presented on Figure 5.
OWTS COMPONENTS
Recommended OWTS components provided below are based on our design details and our
experience with the specific component manufacturers. Equivalent components may be feasible
but need to be approved by us prior to construction.
Septic Tank
• A Valley Precast 1,000 gallon, two-chamber septic tank should be used for primary
treatment and dosing to the STA. A detail of the tank is provided as an attachment to this
report.
• An effluent filter should be installed in the tank outlet tee.
• The tank must be a minimum of five feet from the residence. The tank must be a
minimum of 10 feet from any potable water supply lines. The tank must be a minimum
of 50 feet from any well or potable water supply cistern.
- 5 -
Kumar & Associates, Inc. Project No. 19-7-719.02
• The tank must be set level. The excavation bottom must be free of large rocks or other
objects that could damage the tank during placement. A road base or gravel bedding
material may be needed to prevent tank damage during placement and act as a leveling
course.
• The tank lids must extend to final surface grade and made to be easily located.
• Install the tank with 2 feet minimum cover soil for frost protection. Maximum tank soil
cover is 4 feet.
Sewer Pipe
• The sewer line to the septic tank should not be less than the diameter of the building
drains and not less than 4 inches in diameter.
• The sewer pipe should have a rating of SDR35 or stronger. Schedule 40 PVC pipe is
required beneath any driveway surfaces.
• The sewer pipe should be sloped between 2% to 4% to help limit disturbance of solids in
the tank and potential sewage bypass of the first chamber of the tank. Due to the
basement sewerline invert elevation, care will be needed to maintain a minimum 2%
grade.
• A minimum 24 inches of cover soil should be provided over the sewer pipe. Paved areas,
patios or other areas without vegetative cover may be more susceptible to frost and we
recommend 48 inches of soil cover over the sewer pipe in these areas, and the pipe be
insulated on top and sides with 2-inch-thick blue foam insulation board. If adequate soil
cover is not possible, we should be contacted for re-evaluation prior to installation.
• The sewer pipes should be bedded in compacted ¾-inch road base or native soils
provided that the native soils contain no angular rocks or rocks larger than 2½ inches in
diameter to help prevent settlement of the pipe. Sags in the pipe could cause standing
effluent to freeze and damage the piping.
• Install cleanout pipes within 5 feet of the building foundation, where the sewer pipes
bend 90 degrees or more and every 100 feet of sewer pipe.
• All 90-degree bends should be installed using a 90-degree long-sweep or by using two
45-degree elbows.
• The sewer pipe should be encased in larger diameter Schedule 40 PVC pipe anywhere
that it encroaches on the setbacks to the potable water supply line and/or potable water
supply cistern. The setbacks are 5 feet to potable water supply line and 50 feet to the
potable water supply cistern. Encasement will be needed for the sewerline at the cistern
setback and the waterline crossing. The encasement should be capped and sealed
watertight at both ends.
- 6 -
Kumar & Associates, Inc. Project No. 19-7-719.02
• The sewer line location shown on Figure 1 is considered conceptual. We assume that
there will be only one sewer line exiting the residence. It is the responsibility of the
owner/contractors to locate all sewer line exit locations and connections to the septic
tank. We should be notified if there are other sewer lines exiting the building.
Effluent Transport Piping
• The effluent transport pipe should be 4-inch diameter SDR35 piping sloped at a 2%
minimum to flow from the septic tank to the distribution box and from the distribution
box to each trench. Piping should extend at least 6 inches into the top knockout provided
in the Infiltrator end caps and be screwed in place. Splash plates should be installed
beneath the inlet piping to help limit scouring of the infiltrative soil surface in the
chambers.
• The effluent transport pipe should be bedded in compacted ¾ inch road base or native
soils provided that the native soils contain no angular rocks or rocks larger than 2½
inches in diameter to help prevent settlement of the pipe. Sags could cause standing
effluent to freeze and damage to the piping.
• A minimum 18 inches of cover soil should be provided over the effluent transport pipe.
Paved areas, patios or other areas without vegetative cover may be more susceptible to
frost. We recommend 48 inches of soil cover over the effluent pipe and insulation with at
least 2 inches of rigid foam insulation in these areas. If adequate cover soil is not
possible, we should re-evaluate the condition prior to installation.
• Schedule 40 PVC pipe is required underneath any driveway and roadway surfaces and
should be provided with at least 48 inches of soil cover, and be insulated on top and sides
with 2-inch-thick rigid foam insulation board.
• All 90-degree bends should be installed using a 90 degree long-sweep or by using two
45-degree elbows.
Distribution Box
• The distribution box will be used to equally divide effluent flow between the trenches.
We recommend the Tuf-Tite 4-Hole Distribution Box since it is easily accessible from
ground surface for maintenance. A copy of the distribution box detail is provided as an
attachment to this report.
• The distribution box outlet pipes should be equipped with Tuf-Tite speed levelers for ease
of initial setup and adjustment over time.
• The distribution box should be a minimum of 18 inches below grade with risers and an
access lid at or above grade.
• The distribution box must be accessible from ground surface for inspection and
maintenance per State guidelines.
- 7 -
Kumar & Associates, Inc. Project No. 19-7-719.02
• The effluent line from the septic tank should be directed downward into the distribution
box with a 90-degree elbow inside the box.
• The distribution box must be installed level on a compacted road base subgrade to ensure
equal effluent distribution. If settlement of the distribution box occurs, unequal effluent
distribution may take place which could cause hydraulic overload of one of the trenches
and potential failure. The distribution box should be monitored periodically, and the
speed levelers should be adjusted as necessary for leveling. The ground surface above
and around the distribution box should be graded to drain away surface water to prevent
standing water near the distribution box which could freeze or cause settlement.
OWTS OPERATION AND MAINTENANCE
The OWTS will require periodic inspection and maintenance to function properly. A properly
designed, installed and maintained system can greatly increase its lifespan. The level of
maintenance will vary depending on the complexity of the system and water use habits of the
residents. We recommend that an OWTS Operation and Maintenance (O&M) Manual be
developed. Depending on the complexity of the system, a contract with an OWTS maintenance
provider may be prudent. Below are some basic recommendations for the OWTS O&M.
OWTS HOUSEHOLD OPERATION
• Use of high efficiency water fixtures is recommended to decrease the hydraulic load on
the OWTS system.
• Fix plumbing leaks immediately as this may cause a hydraulic overload of the soil
absorption system.
• Do not irrigate the area on top of or directly upgradient of the soil absorption field as this
may cause a hydraulic overload.
• Do not dispose of household waste down drains as this may clog or damage OWTS
components. Examples of household waste includes: dental floss, cotton swabs, coffee
grounds, paper towels, feminine products and many other kitchen and bath items.
• Use of kitchen garbage disposals is not recommended. If a garbage disposal is utilized,
kitchen wastewater should be screened thoroughly. Many kitchen solids are not
decomposed in the septic tank and may cause increased tank pumping frequency.
• Do not dispose of household chemicals, greases, oils, paints, hot tub water or water
softener backwash in household drains. A separate drywell, if feasible, may be necessary
for hot tub water or water softener backwash disposal.
• Limit the use of bleach as this may harm useful bacteria in the septic tank and soil
absorption system.
• Liquid dishwasher and clothes washer detergent is recommended for households served
- 8 -
Kumar & Associates, Inc. Project No. 19-7-719.02
by an OWTS. Clay substances used as fillers in powder detergents may result in
clogging of the soils absorption system.
• The effluent in septic tanks can freeze during extended periods of non-use in cold
weather. We recommend that a tank heater be installed in this system to help prevent
freezing.
OWTS MAINTENANCE
• Inspect the septic tank, distribution box and STA at least annually for problems or signs
of failure.
• The filter should be cleaned at least annually by spray washing solids into the first
chamber of the septic tank.
• The septic tank should be pumped and cleaned every 3 to 5 years depending on use.
Longer pumping intervals may increase the amount of solids that reach the STA, which
may shorten its life span.
• Pumping of the septic tank should take place when the level of the sludge and scum
layers combined take up 25 to 33% of the capacity of the first chamber of the tank.
OWTS CONSTRUCTION OBSERVATION
The Eagle County Environmental Health Department requires that the designer of the system
provide a record drawing and certification of the OWTS construction (As-Built inspection). We
should be provided with at least 48-hour notice prior to the installer needing the inspections.
Prior to issuance of our certification letter, we require observation of all system components
prior to backfill. The number of site visits required for the As-Built inspection will depend on
the installer’s construction schedule.
LIMITATIONS
We have conducted this design in accordance with generally accepted engineering principles and
practices in this area at this time. We make no warranty either expressed or implied. The
recommendations provided in this report are based on the site conditions, profile pit evaluations
and soil texture analysis, the proposed construction and our experience in the area. Variations in
the subsurface conditions may not become evident until excavation is performed. If conditions
encountered during construction appear different from those described in this report, we should
be notified so that re-evaluation of the recommendations may be made.
This report has been prepared for the exclusive use by our client for design purposes. We are not
responsible for technical interpretations by others of our information. As the project evolves, we
should provide continued consultation and field services during construction to review and
monitor the implementation of our recommendations, and to verify that the recommendations
Kumar & Associates
SILT
COBBLES
COARSE
GRAVEL
MEDIUMMEDIUMV. FINE
SAND
CLAY
FINE CO.FINEV. CO.CO.FINE
Kumar & Associates
Kumar & Associates
Kumar & Associates
Notes:
&KDPEeUssKoXOGEeLQstDOOeGOeYeOoQDsFDULILeGJUoXQGsXUIDFe&oQFUetesDQGPD\EeXseGDsDOeYeOLQJFoXUseLI
QeFessDU\
&DUesKoXOGEetDNeQE\tKeFoQtUDFtoUtoDYoLGFoPSDFtLoQoItKeQDtLYesoLOsLQtKetUeQFKDUeDs7KeEDseDQGsLGeZDOOsoI
tUeQFKe[FDYDtLoQssKoXOGEesFDULILeGSULoUtoFKDPEeULQstDOODtLoQ
$OOSLSLQJsKoXOGKDYeDUDtLQJoI6'5oUstUoQJeU
&KDQJestotKLsGesLJQsKoXOGQotEePDGeZLtKoXtFoQsXOtDtLoQDQGDSSUoYDOE\.XPDU $ssoFLDtes
5eIeUtotKe(DJOe&oXQt\2QsLte:DsteZDteU6\steP5eJXODtLoQsIoUotKeUDSSOLFDEOesSeFLILFDtLoQs
Infiltrator Quick 4 Plus
Standard Chamber
Installed Level
Scarify ground surface prior
to chamber placement.
Excavate 36"
Wide Trench
Approx. Existin
g
G
r
o
u
n
d
S
u
r
f
a
c
e
12" min. 24" max.
Cover Soil Graded
to Deflect Surface
Water
Native Soil
4' Min.
Undisturbed
Soil
Between
Trenches
1' Maximum
Cut Depth
Kumar & Associates
Notes
1.Chambers should be installed level on a scarified ground surface. Concrete
sand may be used as a leveling course if necessary.
2.Care should be taken by the contractor to avoid compaction of the native soils in
the trench areas. The base and side walls of trench excavations should be
scarified prior to chamber installation.
3.Changes to this design should not be made without consultation and approval
by Kumar & Associates.
Tough Problem
Providing a simple, reliable, and
permanent means for dividing septic
tank effluent flow.
TUF-TITE Solution
A strong, stable, permanent,
non-corrosive Tuf-Tite Distribution
Box, with a Tuf-Tite Speed Leveler
in each outlet.
Snap-in pipe seals
They’re patented. Simply insert your
PVC pipe and push it through the
flexible, polyethylene Tuf-Tite seal.
Pipes fit watertight. Installation couldn’t
be easier.
Tuf-Tite®
Distribution Box.
THE TOUGH ONE!
n Injection molded HDPE
n Non-corrosive
n Simple to install
n Easy to level
In a septic environment, no other
material can match High Density
Polyethylene in delivering a lifetime
of trouble-free service. Tuf-Tite
Distribution Boxes are injection
molded, using only premium HDPE
which contains no fillers or foam.
They’re permanent
Unlike cement-based pipe grout,
Tuf-Tite seals will not crack or corrode
in septic conditions. They stay pliable
and watertight permanently.
4-Hole Distribution Box4-Hole Dist Cat Sheet 11/8/01 8:09 AM Page 1
nInjection molded.Exceptionallystrong.nHDPE is non-corrosive
in a septic
environment.
nPatented snap-in
pipe seals
simplify
installation.
Interlocking Lid. Heavy-dutyHDPE Lid is ribbed for addedstrength and rigidity. Slottedsides interlock on theDistribution Box to assure atight fit.The 4HD2 Distribution Box
comes complete with a
Regular Lid or an Inspection
Port Lid, and 5 snap-in
fittings of your choice.
Model B1 Riser. For series
B1 Box. Stackable HDPE
Risers extend to grade in 6”
increments. Accept 11” x 11”
lids and grates.
11”
S-35 S-40
P-10
11”
11”
11”
11”
151/2”
2” Drop
INSTALLATION IS
JUST THIS SIMPLE
1.Position the Distribution Box
on level virgin soil.
Do not place box on a
concrete slab.
2.Install the inlet pipe and
outlet pipes. Be sure the
bottoms of all pipes rest on
virgin soil.
3.Level the Distribution Box
and all pipes as needed.
4.Backfill the pipes to within
two feet of the Distribution
Box. Recheck the level of the
box, then backfill up to the
top lid ridge.
5.Install and adjust Tuf-Tite
Speed Levelers.
6.Place lid on the Distribution
Box and finish backfilling.
Choice of Fittings
S-35 Pipe Seal, for:
n Sewer and Drain
n SDR 35 n ASTM 3034
n Thin Wall n 1500 Lb. Crush
S-40 Pipe Seal, for:
n Schedule 40
n 4” Corrugated
P-10 Plug, for unused holes
Choice of Lids
Regular Lid. Molded of rugged
HDPE.
Inspection Port Lid. For easy
access and inspection. Models
available to accept either 4” or
6” extension pipes.
Tuf-Tite Speed Levelers™
Control the flow of effluent from
the Distribution Box. Simply
insert a Speed Leveler into each
outlet pipe. Rotate each Speed
Leveler so the flow is distributed
as desired. Available for 3” or 4”
PVC pipe.
©1999 Tuf-Tite® Corporation
Form 4HD2-3. Printed in USA
A full line of
innovations for
better septic
systems
11”
6”
7”
14”
Drainage and Septic Products
Tuf-Tite®Corporation
1200 Flex Court
Lake Zurich, Illinois 60047
4-Hole Distribution Box 4HD24-Hole Dist Cat Sheet 11/8/01 8:09 AM Page 2