HomeMy WebLinkAbout24 Metheny Wy - 210935401009Work Classification: NewPermit
12770 MERIT DR
DALLAS TX 75251-
Address Owner Information
Permit Status: Active
Project Address
210935401009
Permit Type: OWTS Permit
Permit NO. OWTS-8-16-15181
Expires: 12/16/2016 Issue Date: 8/18/2016
Parcel No.
1840 FROST CREEK DR
Private Wastewater
System
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970)328-8755
Fax: (970)328-8788
Phone:
Cell:
Inspection
For Inspections call: (970) 328-8755
Inspections:
IVR
OWTS Final Inspection 095
PhoneEngineer(s)
(970)926-9088LKP Engineering, Inc
Contractor(s)Phone Primary ContractorLicense Number
BEAUMONT EXCAVATING Yes44-16
NORMAN AND ANNE MILLER
Permitted Construction / Details:
Install the OWTS exactly as designed by LKP Engineering in accordance with the deign drawing signed
and dated by Luiza Petrovska July 14, 2016 with the last revision date of August 4, 2016. System is
designed to serve a six bedroom home and incorporates denitrification as required by the PUD.
System consists of a 2,000 gallon Front Range Precast "FLXX" septic tank followed by a 2,000 gallon
Front Range Precast "FLXX" septic tank that contains the pumps and 3B mode plumbing configuration
necessary to deliver wastewater to two Orenco Advantex AX 20 filter pods to nitrify the effluent to be
delivered to the first compartment of the septic tank for denitrification. The denitrified effluent will be
pressure dosed to 1,500 square feet of soil treatment area (prior to the adjustments for pressure dosing
and using chambers) consisting of 3 shallow trenches with 24 Quick 4 Plus Standard Infiltrator chambers
in each trench for a total of 72 chambers.
Four feet of vertical separation between the infiltrative surface and any confining layer must be
maintained and verified by the engineer by observing another 8 foot profile pit prior to construction; or by
varying the infiltrative surface depths of each trench at two feet below grade.
The Orenco Advantex system must be installed in accordance with the March 26, 2015 acceptance letter
of the treatment technology from Chuck Cousino of CDPHE to Joseph Soulia of Orenco.
LKP engineering will perform all inspections necessary to certify the installation of the OWTS as
designed and to prepare the as-built drawings, which in turn, will be provided to Simon Farrell with JVA
for final certification and transmittal to Eagle County Environmental Health for review and approval. Final
approval by Eagle County Environmental Health is required prior to the use of the system or occupancy of
the residence.
Issued by: Environmental Health Department, Eagle County, CO
August 19, 2016
Date
Customer Copy
Ray Merry
CONDITIONS:
1. THIS PERMIT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT
COMMENCED WITHIN 120 DAYS OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
2. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN C.R.S. 25-10-101, et seq., AS AMENDED
3. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND
BUILDING DEPARTMENTS SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN
BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL
SYSTEM TO BE LICENSED
Work Classification: NewPermit
12770 MERIT DR
DALLAS TX 75251-
Address Owner Information
Permit Status: Active
Project Address
210935401009
Permit Type: OWTS Permit
Permit NO. OWTS-8-16-15181
Expires: 12/16/2016 Issue Date: 8/18/2016
Parcel No.
1840 FROST CREEK DR
Private Wastewater
System
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970)328-8755
Fax: (970)328-8788
Phone:
Cell:
Inspection
For Inspections call: (970) 328-8755
Inspections:
IVR
OWTS Final Inspection 095
PhoneEngineer(s)
(970)926-9088LKP Engineering, Inc
Contractor(s)Phone Primary ContractorLicense Number
BEAUMONT EXCAVATING Yes44-16
NORMAN AND ANNE MILLER
Permitted Construction / Details:
Install the OWTS exactly as designed by LKP Engineering in accordance with the deign drawing signed
and dated by Luiza Petrovska July 14, 2016 with the last revision date of August 4, 2016. System is
designed to serve a six bedroom home and incorporates denitrification as required by the PUD.
System consists of a 2,000 gallon Front Range Precast "FLXX" septic tank followed by a 2,000 gallon
Front Range Precast "FLXX" septic tank that contains the pumps and 3B mode plumbing configuration
necessary to deliver wastewater to two Orenco Advantex AX 20 filter pods to nitrify the effluent to be
delivered to the first compartment of the septic tank for denitrification. The denitrified effluent will be
pressure dosed to 1,500 square feet of soil treatment area (prior to the adjustments for pressure dosing
and using chambers) consisting of 3 shallow trenches with 24 Quick 4 Plus Standard Infiltrator chambers
in each trench for a total of 72 chambers.
Four feet of vertical separation between the infiltrative surface and any confining layer must be
maintained and verified by the engineer by observing another 8 foot profile pit prior to construction; or by
varying the infiltrative surface depths of each trench at two feet below grade.
The Orenco Advantex system must be installed in accordance with the March 26, 2015 acceptance letter
of the treatment technology from Chuck Cousino of CDPHE to Joseph Soulia of Orenco.
LKP engineering will perform all inspections necessary to certify the installation of the OWTS as
designed and to prepare the as-built drawings, which in turn, will be provided to Simon Farrell with JVA
for final certification and transmittal to Eagle County Environmental Health for review and approval. Final
approval by Eagle County Environmental Health is required prior to the use of the system or occupancy of
the residence.
Work Classification: NewPermit
12770 MERIT DR
DALLAS TX 75251-
Address Owner Information
Permit Status: Active
Project Address
210935401009
Permit Type: OWTS Permit
Permit NO. OWTS-8-16-15181
Expires: 12/16/2016 Issue Date: 8/18/2016
Parcel No.
1840 FROST CREEK DR
Private Wastewater
System
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970)328-8755
Fax: (970)328-8788
Phone:
Cell:
Inspection
For Inspections call: (970) 328-8755
Inspections:
IVR
OWTS Final Inspection 095
PhoneEngineer(s)
(970)926-9088LKP Engineering, Inc
Contractor(s)Phone Primary ContractorLicense Number
BEAUMONT EXCAVATING Yes44-16
NORMAN AND ANNE MILLER
Permitted Construction / Details:
Install the OWTS exactly as designed by LKP Engineering in accordance with the deign drawing signed
and dated by Luiza Petrovska July 14, 2016 with the last revision date of August 4, 2016. System is
designed to serve a six bedroom home and incorporates denitrification as required by the PUD.
System consists of a 2,000 gallon Front Range Precast "FLXX" septic tank followed by a 2,000 gallon
Front Range Precast "FLXX" septic tank that contains the pumps and 3B mode plumbing configuration
necessary to deliver wastewater to two Orenco Advantex AX 20 filter pods to nitrify the effluent to be
delivered to the first compartment of the septic tank for denitrification. The denitrified effluent will be
pressure dosed to 1,500 square feet of soil treatment area (prior to the adjustments for pressure dosing
and using chambers) consisting of 3 shallow trenches with 24 Quick 4 Plus Standard Infiltrator chambers
in each trench for a total of 72 chambers.
Four feet of vertical separation between the infiltrative surface and any confining layer must be
maintained and verified by the engineer by observing another 8 foot profile pit prior to construction; or by
varying the infiltrative surface depths of each trench at two feet below grade.
The Orenco Advantex system must be installed in accordance with the March 26, 2015 acceptance letter
of the treatment technology from Chuck Cousino of CDPHE to Joseph Soulia of Orenco.
LKP engineering will perform all inspections necessary to certify the installation of the OWTS as
designed and to prepare the as-built drawings, which in turn, will be provided to Simon Farrell with JVA
for final certification and transmittal to Eagle County Environmental Health for review and approval. Final
approval by Eagle County Environmental Health is required prior to the use of the system or occupancy of
the residence.
Office Copy
August 19, 2016
Issued by: Environmental Health Department, Eagle County, CO Date
Ray Merry
CONDITIONS:
1. THIS PERMIT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT
COMMENCED WITHIN 120 DAYS OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
2. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN C.R.S. 25-10-101, et seq., AS AMENDED
3. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND
BUILDING DEPARTMENTS SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN
BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL
SYSTEM TO BE LICENSED
Work Classification: NewPermit
12770 MERIT DR
DALLAS TX 75251-
Address Owner Information
Permit Status: Active
Project Address
210935401009
Permit Type: OWTS Permit
Permit NO. OWTS-8-16-15181
Expires: 12/16/2016 Issue Date: 8/18/2016
Parcel No.
1840 FROST CREEK DR
Private Wastewater
System
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970)328-8755
Fax: (970)328-8788
Phone:
Cell:
Inspection
For Inspections call: (970) 328-8755
Inspections:
IVR
OWTS Final Inspection 095
PhoneEngineer(s)
(970)926-9088LKP Engineering, Inc
Contractor(s)Phone Primary ContractorLicense Number
BEAUMONT EXCAVATING Yes44-16
NORMAN AND ANNE MILLER
Permitted Construction / Details:
Install the OWTS exactly as designed by LKP Engineering in accordance with the deign drawing signed
and dated by Luiza Petrovska July 14, 2016 with the last revision date of August 4, 2016. System is
designed to serve a six bedroom home and incorporates denitrification as required by the PUD.
System consists of a 2,000 gallon Front Range Precast "FLXX" septic tank followed by a 2,000 gallon
Front Range Precast "FLXX" septic tank that contains the pumps and 3B mode plumbing configuration
necessary to deliver wastewater to two Orenco Advantex AX 20 filter pods to nitrify the effluent to be
delivered to the first compartment of the septic tank for denitrification. The denitrified effluent will be
pressure dosed to 1,500 square feet of soil treatment area (prior to the adjustments for pressure dosing
and using chambers) consisting of 3 shallow trenches with 24 Quick 4 Plus Standard Infiltrator chambers
in each trench for a total of 72 chambers.
Four feet of vertical separation between the infiltrative surface and any confining layer must be
maintained and verified by the engineer by observing another 8 foot profile pit prior to construction; or by
varying the infiltrative surface depths of each trench at two feet below grade.
The Orenco Advantex system must be installed in accordance with the March 26, 2015 acceptance letter
of the treatment technology from Chuck Cousino of CDPHE to Joseph Soulia of Orenco.
LKP engineering will perform all inspections necessary to certify the installation of the OWTS as
designed and to prepare the as-built drawings, which in turn, will be provided to Simon Farrell with JVA
for final certification and transmittal to Eagle County Environmental Health for review and approval. Final
approval by Eagle County Environmental Health is required prior to the use of the system or occupancy of
the residence.
December, 14th 2017
Mr. Norman Miller
12770 Merit Dr.
Dallas, TX..
RE: Final approval of the: Septic System Tank Installation, OWTS-8-16-15181 Property
location: 1840 Frost Creek Drive at Eagle County, Colorado.
Mr. Miller:
This letter is to inform you that the above-referenced, OWTS-8-16-15181 permit, has been
inspected and finalized. This permit was approved and sized for a total capacity of six (6)
bedrooms. Additional information about the maintenance your septic system needs can be
accessed through our website links, provided on the Environmental Health Department’s septic
system resource page.
Be aware that changes in the use of your property or alterations of your building may require
commensurate changes to, or relocation of, your septic system. Landscape features, trees with tap
roots, irrigation systems and parking areas above the soil treatment area can cause premature
system failure. It is equally important that you notice and immediately repair dripping faucets
and hissing toilets as this will certainly cause the system to fail.
If you have any questions regarding this information, please contact us at (970) 328-8755 and
reference the OWTS septic permit number.
Best Regards,
Giovanna Harkay.
Administrative Technician IV
Attachments: Certification Letter and Design – Septic System Flyer – Final Letter
DEPARTMENT OF
ENVIRONMENTAL HEALTH
(970) 328-8755
FAX: (970) 328-8788
TOLL FREE: 800-225-6136
www.eaglecounty.us
RAYMOND P. MERRY, REHS
Director
August 8th, 2016
Mr. Ray Merry, REHS
Director of Environmental Health
PO Box 179
Eagle, CO 81631
RE: Frost Creek - Onsite Wastewater Treatment System Design – 1840 Frost Creek Drive,
Eagle County, CO – Miller Residence
Dear Ray:
LKP Engineering Inc. has prepared a design of an onsite wastewater treatment system (OWTS)
to serve 1840 Frost Creek Drive located within the Frost Creek PUD. JVA Inc. (JVA) is the
designated engineer to process all OWTS permit applications within Frost Creek. JVA has
reviewed the OWTS design and has determined that it is in general conformance with OWTS
requirements of the PUD.
The most recently reported sampling results from the Water Quality Monitoring and Mitigation
Plan (dated July 13th, 2016) did not result in any exceedances of the water quality trigger limits.
Please proceed with the permit review of this OWTS design.
Sincerely,
JVA, INCORPORATED
By: _________________________________
Simon Farrell, P.E.
Project Engineer
Attachment A - LKP OWTS design with revisions dated August 4th, 2016
Attachment B – LKP site and soil evaluation
Attachment C – LKP discharge pump calculations
1840 Frost Creek Drive, south from the Town of Eagle, Eagle
County, Colorado
Lots 39, Frost Creek & Salt Creek PUD, Filing No. 1,
Eagle County, Colorado
There weren’t any existing structures on the lot.
Water is provided by
the Town of Eagle Water Department.
There are no existing septic systems on Lot 39.
The topography of the property is moderate. Within the
proposed leachfield area the topography was moderate, about 10 percent,
sloping west to east. The leachfield will be located south from the proposed
building site, in the back yard of the proposed residence.
One profile hole and three percolation holes were excavated and
observed. The Profile Hole had about 8 inches of topsoil over 8 inches of
dark brown, blocky clay over reddish brown, sandy gravel with subangular
to flat sandstone and shale rocks to about 2.5 feet. From 2.5 to 6.5 feet was
reddish-brown, silty, gravelly sand with cobbles and boulder. Some of the
boulders had about 2 feet diameter and the mini excavator had difficult time
digging them out. There was no ground water or bedrock observed at the
time of the excavation.
The proposed septic tanks and
the treatment components are at least 45 feet away from the house, and at
least 35 feet away from the leachfield. The leachfield is at least 83 feet away
from the house, and about 67 feet away from the closest property lines.
The proposed leachfield site will be located in the
back/side slope, on a linear slope, along the contours.
The topography of the proposed leachfield site is moderate
(about 10 percent slopes) and the trenches will run along the contours.
The vegetation of the proposed leachfield site consisted of wild
grass and some sage brush.
: The natural topography of the site is
moderate, sloping west to east. At about the middle of the lot there is an old,
abandoned irrigation ditch. Above (west) the old ditch the vegetation is all
sage brush, while to the east of it is mostly grass with some sage.
Based on the records available, the property
seems to have been used as a ranch by an early settler, W.E. Frost from the
early 1880's. From 1973 the land had been developed into the residential
subdivision Adam’s Rib Ranch with a golf course. Most recently, in March of
2015 the property had been repurchased and renamed to Frost Creek
Ranch. The use remains as a residential subdivision with a golf course.
One profile hole and three percolation holes were
excavated. Percolation test was run in the three percolation holes the
following day.
This site
evaluation was completed by Luiza Petrovska, PE, of LKP Engineering, Inc.
LKP Engineering, Inc., is located at 67 Robins Egg Lane, Eagle, Colorado.
The phone number is 970-926-9088 and Luiza’s email address is
luiza@lkpeng.com
Attached
The proposed septic tanks and treatment
components of the system are about 45 feet away from the house and about
35 feet away from the leachfield. The leachfield is at least 83 feet away from
the house and about 67 feet away from the property lines.
: No well. No cut bank. The trenches for
proposed infiltrator chambers will be cut to the same bottom elevation and
the depth will vary from about one foot to three feet below the existing grade,
with at least four feet of suitable soil below the trenches.
Some large boulders can be
encountered and will need to be removed from the trenches. The voids can be
filled with the onsite gravelly soil.
None known
Large boulders (about 2-foot diameter) were encountered at about 6.5 feet
in the profile hole that were difficult to remove. Larger excavator will not
have an issue with those boulders.
L K P E N G I N E E R I N G , I N C .
P .O . B o x 7 2 4
E a g le , C O 8 1 6 3 1
(9 7 0 ) 9 2 6 -9 0 8 8
PERCOLATION TEST RESULTS
C lie n t :Brannen Fitzgerald, AIA
Scott S. Turnipseed AIA
P.O. Box 3388
Eagle, CO 81631
L o ca t io n : Miller Residence
Lot 39, Frost Creek & Salt Creek
PUD Filing No. 1
1840 Frost Creek Drive
E a g le C o u n ty , C o lo rad o
P r o je c t N o . : 1 5 -3 0 7 1
P -1 P -2 P -3
T IM E /D E P T H 2 0 "1 9 "2 2 "
1 :0 0 p m 6 -1 3 /1 6 "5 -1 2 /1 6 "6 -1 /1 6 "
1 :1 0 p m 8 -1 3 /1 6 "2 "7 -1 0 /1 6 "1 -1 4 /1 6 "7 -9 /1 6 "1 -8 /1 6 "
1 :2 0 p m 9 -1 5 /1 6 "1 -2 /1 6 "8 -1 1 /1 6 "1 -1 /1 6 "8 /1 2 /1 6 "1 -3 /1 6 "
1 :3 0 p m 1 0 -1 3 /1 6 "1 4/1 6 "9 -1 4 /1 6 "1 -3 /1 6 "9 -1 1 /1 6 "1 5 /1 6 "
1 :4 0 p m 1 1 -1 0 /1 6 "1 3/1 6 "1 0 -1 1 /1 6 "1 3 /1 6 "1 0 -7 /1 6 "1 2 /1 6 "
1 :5 0 p m 1 2 -3 /1 6 "9 /1 6 "1 1 -6 /1 6 "1 1 /1 6 "1 1 -3 /1 6 "1 2 /1 6 "
2 :0 0 p m 1 2 -1 3 /1 6 "1 0/1 6 "1 2 -1 /1 6 "1 1 /1 6 "1 2 -1 /1 6 "1 4 /1 6 "
2 :1 0 p m 1 3 -6 /1 6 "9 /1 6 "1 2 -9 /1 6 "8 /1 6 "1 2 -9 /1 6 "8 /1 6 "
2 :2 0 p m 1 3 -1 3 /1 6 "7 /1 6 "1 3 -2 /1 6 "9 /1 6 "1 3 -5 /1 6 "1 2 /1 6 "
2 :3 0 p m 1 4 -6 /1 6 "9 /1 6 "1 3 -1 1 /1 6 "9 /1 6 "1 4 "1 1 /1 6 "
2 :4 0 p m 1 4 -1 3 /1 6 "7 /1 6 "1 4 -4 /1 6 "9 /1 6 "1 4-1 0 /1 6 "1 0 /1 6 "
2 :5 0 p m 1 5 -2 /1 6 "5 /1 6 "1 4 -1 1 /1 6 "7 /1 6 "1 5 -3 /1 6 "9 /1 6 "
3 :0 0 p m 1 5 -7 /1 6 "5 /1 6 "1 5 -1 /1 6 "6 /1 6 "1 5-1 1 /1 6 "8 /1 6 "
P E R C R A T E 3 2 M IN /IN C H 2 2 M I N /IN C H 2 0 M IN /IN C H
A V G P E R C 2 3 M I N /IN C H
A v e ra g e P e rc o la tio n H o le D ia m e te r: ~8 .5 "
H o le s D u g an d P re s o a k ed : N o v em b e r2 , 2 0 1 5
T es t R u n : N o v e m b e r 3 , 2 0 1 5
Run by Kiril Petrovski
S o il
P ro f ile :
0 to 8 " T o p so il
8 " to 1 6 " D ark b ro w n , b lo c k y c la y
1 6 " to 2 .5 '' R e d d ish b ro w n , sa n d y g ra v e l w ith
f lat, sa n d sto n e a n d sh ale ro ck s
2 .5 to 6 .5 ' R e d d is h b ro w n silty , g ra v e lly s a n d
w ith co b b les an d b o u ld e r s , ~ 2 ft d ia m eter
N o g ro u n d w a te r e n c o u n tere d
N o B e d r o c k
Pump Selection for a Pressurized System - Single Family Residence Project
15-3071 Miller Res / 1840 Frost Creek Drive
Parameters
Discharge Assembly Size
Transport Length
Transport Pipe Class
Transport Line Size
Distributing Valve Model
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
2.00
38
40
2.00
None
5
18
40
2.00
3
96
40
1.50
5/32
4
2
None
2
inches
feet
inches
feet
feet
inches
feet
inches
inches
feet
feet
inches
feet
Calculations
Minimum Flow Rate per Orifice
Number of Orifices per Zone
Total Flow Rate per Zone
Number of Laterals per Zone
% Flow Differential 1st/Last Orifice
Transport Velocity
0.43
75
32.6
3
6.3
3.1
gpm
gpm
%
fps
Frictional Head Losses
Loss through Discharge
Loss in Transport
Loss through Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
'Add-on' Friction Losses
2.1
0.7
0.0
0.1
0.3
0.0
2.0
feet
feet
feet
feet
feet
feet
feet
Pipe Volumes
Vol of Transport Line
Vol of Manifold
Vol of Laterals per Zone
To ta l V ol um e
6.6
3.1
30.5
40.2
gals
gals
gals
gals
Minimum Pump Requirements
Design Flow Rate
Total Dynamic Head
32.6
12.2
gpm
feet
0 1020304050607080
0
20
40
60
80
100
120
140
160
Net Discharge (gpm)
PumpData
PF5005 High Head Effluent Pump
50 GPM, 1/2HP
115/230V 1Ø 60Hz, 200/230V 3Ø 60Hz
Legend
System Curve:
Pump Curve:
Pump Optimal Range:
Operating Point:
Design Point:
December 13, 2017
Mr. Ray Merry, Director of Environmental Health
Eagle County Environmental Health
500 Broadway Street
Eagle, CO 81631
RE: OWTS Final Certification – 1840 Frost Creek Drive, Lot 39
Dear Ray:
The Onsite Wastewater Treatment System (OWTS) serving 1840 Frost Creek Drive is ready for
final certification from Eagle County Environmental Health. The engineer of record for this
system is Luiza Petrovska with LKP Engineering Inc. The final approval letter and record
drawings from Luiza are provided as an attachment.
As part of the final approval process JVA ensured that start-up was completed by the
manufacturer’s representative (Jerry at Valley Precast) and that a communication line was
connected to the control panel. The system is connected and can be monitored remotely as
required in the PUD. Moving forward, JVA will be working with Frost Creek on the
management of this more advanced remote monitoring technology.
Please proceed with the closeout process for this OWTS permit.
Sincerely,
JVA, INCORPORATED
By: ________________________
Kevin Tone, P.E., LEED AP
Vice President
Enclosure:
Attachment A – LKP Inc. Inspection Letter
Attachment B – LKP Inc. As-built Drawing
CC: Simon Farrell, JVA
There is no other warranty either expressed or implied.