Permit
Permit No. OWTS-021890-2021
Permit Type: OWTS Permit
Work Classification: Alteration
Permit Status: Under Review
Issue Date: Not Issued Expires: N/A
On-Site Wastewater
Treatement System
Project Address Parcel Number
1633 EMMA SPUR, BASALT AREA,246512303002
Owner Information Address
Sarah Willeman Phone: (970) 945-5558
Cell: (970) 290-6426
Email: swilleman@mac.com
Inspections:
For Inspections Call: (970)
328-8755
Engineer Phone Email
Mountain Cross Engineering, Chris Hale (970) 945-5544 chris@mountaincross-eng
.com
Contractor License Number Phone Email
Permitted Construction / Details:
A licensed installer has not been identified. No person shall install, renovate, or repair an OWTS in Eagle County
(EC) without a valid EC Systems Contractor License. Any person that conducts a business as a systems contractor
without having obtained a valid license section commits a Class 1 petty offense as defined in section 18-1.3-503,
C.R.S. Please notify the department when an installer is identified, prior to installation of the OWTS.
Alteration of the existing OWTS soil treatment area (STA) exactly as depicted in the Mountain Cross Engineering,
Inc. dated January 19, 2021 design report and drawings stamped by Christopher F. Hale, PE. The OWTS is designed
to serve a two bedroom residence above a barn. The existing soil treatment area (STA), permit #2-18-18541 is to be
removed and disposed of per ECPHA Regulation 43.9.C. The STA will be replaced with a new STA NE of the current
location, as shown on design, to be outside of the area to be used for vehicle crossing.
Note: Prior to beginning installation of the new STA, two 8' test pits must be excavated for the design engineer to
confirm soil type and horizontal setback distances. Final inspection must confirm the relocation of the well outside
of the required 100ft setback.
The system proposes using the existing 1,000 gallon, two compartment septic tank with effluent screen on the outlet
tee and an Orenco Model 310 dosing siphon, followed by 500 square feet of new STA arranged in two shallow 55'
long by 3' wide trenches, each receiving equal amounts of effluent from a new distribution box equipped with flow
equalizers.
Contact Eagle County and the design engineer well in advance of scheduling inspections. All inspections necessary
to certify the system must be conducted by the design engineer. System certification along with photos and a
record drawing must be submitted to, and approved by, Eagle County Environmental Health prior to the use of the
system or occupancy of the dwelling.
Friday, August 13, 2021 1
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS
OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Claire Lewandowski
Date
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Friday, August 13, 2021 2
________________________________________________________________________________________________________
826 ½ Grand Avenue, Glenwood Springs, CO 81601
P: 970.945.5544 F: 970.945.5558 www.mountaincross-eng.com
January 19, 2021
Mr. Tristan Francis
2757 Design Build, Co.
417 Main Street, Suite Y
Carbondale, CO 81623
RE: On-Site Wastewater Treatment System – Emma Barn, 1633 Emma Spur Road
Dear Tristan:
The purpose of this correspondence is to inform you about the modifications proposed to the
existing onsite wastewater treatment system (OWTS) for the Emma Barn. The project proposes
to reconstruct an existing OWTS that was built to serve a barn with a two bedroom residence at
1633 Emma Spur Road. This is a gravity system from the barn to a conventional septic tank where
a siphon doses to a leach field comprised of infiltration chambers. The barn is currently served by
an existing well that will be relocated greater than 100’ from the proposed leach field. The OWTS
is not within a 100-year flood plain boundary. The project proposes to keep the existing septic
and dosing tanks but relocate the leach field and distribution box to allow vehicle access over the
area where the leach field is constructed currently. There are practical constraints that you should
be aware of when considering the proper design, construction, and operation of the OWTS.
Subsurface
The LTAR was determined from tests performed by HP-KUMAR and the results are reported in
the Subsoil Study dated February 07, 2018. The LTAR was estimated to be 0.60 gallons per day
per square foot based on USDA rating of sandy loam and was used for the OWTS design. No high
water table or bedrock was encountered within 8’. The soils will need to be verified at the proposed
location prior to construction of the new leach field.
Design Calculations
The barn contains a bathroom with shower, a utility sink, and a shower area. The water use from
the existing fixtures is estimated to be on the order of 100 gallons per day (GPD). In an effort to
oversize the OWTS for any potential future use, the design assumes a two bedroom dwelling.
Using Eagle County Table 6-1, which associates 4 people to a 2 bedroom household and a flow
rate of 75 gallons per person per day, this equates to 300 GPD. The design calculations for sizing
of the septic system and the leach field follow:
• Emma barn: Square footage is less than 6,000 sq. ft.
• Design flow = Assumed 2 bedrooms, per Eagle County Table 6-1 = 300 GPD
• USDA soil type = sandy loam, LTAR = 0.60
• Soil treatment area = 300 GPD / 0.60 = 500 sq. ft.
• Reduction in soil treatment areas for chamber/trench treatment with dosing
Emma Barn
January, 2021
Page 2 of 3
Mountain Cross Engineering, Inc.
Civil and Environmental Consulting and Design
826 ½ Grand Avenue, Glenwood Springs, CO 81601
P: 970.945.5544 F: 970.945.5558 www.mountaincross-eng.com
= 500 sq. ft. * 0.7 * 0.9 = 315 sq.ft required leach area
• Required Chamber Rows to be two rows of 3’ wide by 55’ wide. Number of leaching
chambers per row is to meet or exceed the 55’ length.
• Required septic tank volume, per Eagle County Table 9-1 = 1,000 gallons
The existing 1,000-gallon septic tank and the dosing tank will remain in place. The distribution
box shall be a precast concrete box with 1 inlet and 7 outlets. Alternatives may be considered by
contacting this office. Construction must be in accordance with the specifications of Eagle County
Environmental Health, the OWTS permit, and this design.
Setbacks
The existing septic and dosing tanks are to remain. The leach field setback requirements are:
• 100’ FROM WELL
• 25’ FROM WATER SUPPLY LINE
• 20’ FROM BUILDING
• 10’ FROM PROPERTY LINE
• 50’ FROM UNLINED DITCH OR POND
• 10’ FROM A LINED DITCH OR POND
• 25’ FROM TOP OF BANK
• 5’ FROM SEPTIC TANK
The setback requirements deal primarily with buildings and potential contamination from the and
leach field to either culinary water or surface water. The existing well is proposed to be relocated.
The well will need to be constructed greater than 100’ from the proposed leach field. These
setbacks have been included on the plans for reference.
Operation Information and Maintenance
The Owner will need to be responsible for the operation and management of the OWTS. Geo-
fabrics or plastics should not be used over the absorption area. Topsoil should be placed over the
OWTS and planted with native grasses. No large vegetation and/or plants with taproots should be
planted over the absorption area nor grasses that require excessive irrigation. No heavy equipment,
parking of machinery, or materials should be placed on the absorption area. Livestock should not
graze on the absorption area. Plumbing fixtures should be checked to ensure that no additional
water is being discharged to OWTS; for example, running toilets or leaky faucets can discharge
hundreds of gallons of water a day and harm the absorption area.
Garbage disposal use should be minimized, and non-biodegradable materials should not be placed
into the OWTS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS.
The OWTS is engineered for domestic waste only.
new berm + treesnew barnproperty lineIRRIGATIONOUTLETDITCHEND DITCHBEGIN PIPEDRIVEGRAVEL DRIVEFOUND REBARW/ YELLOW CAPLS# 14111FOUND REBARBUILDING SETBACK(PER PLAT)BUILDING SETBACKIRRIGATIONOUTLETDITCHEND DITCHBEGIN PIPEDRIVEGRAVEL DRIVEFOUND REBARW/ YELLOW CAPLS# 14111FOUND REBARBUILDING SETBACK(PER PLAT)BUILDING SETBACKEAGLE COUNTYPITKIN COUNTYproperty line65566557655565546556655865586557655665586558655965606557655665566557655865556556APPROXIMATE LOCATIONOF PROPOSED WELL(LOCATION TO BEVERIFIED PRIOR TOCONSTRUCTION OF OWTS)WEmma Spur BarnOWTS SITE PLAN1633 Emma Spur Road, Basalt, COph 970.945.5544 fx 970.945.5558 www.mountaincross-eng.com826 1/2 Grand Avenue Glenwood Springs, CO 81601ENGINEERING, INC.Civil and Environmental Consulting and DesignMOUNTAIN CROSSC1Know what'sbelow.before you dig.CallR
ON-SITE WASTE-WATER TREATMENTph 970.945.5544 fx 970.945.5558 www.mountaincross-eng.com826 1/2 Grand Avenue Glenwood Springs, CO 81601ENGINEERING, INC.Civil and Environmental Consulting and DesignMOUNTAIN CROSSC2Emma Spur Barn1633 Emma Spur Road, Basalt, CO