Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutR84-54 fire code for Beaver Creek Metro DistrictCommissioner _� �-�- moved adoption of the
following Resolution:
BOARD OF COUNTY COMMISSIONERS
THE COUNTY OF EAGLE,
STATE OF COLORADO
RESOLUTION NO. 84 -�
WHEREAS: the BOARD OF COUNTY COMMISSIONERS of EAGLE and
STATE OF COLORADO has .previously adopted Resolution NO.-82-7
and 83 -36, approving the fire code and certain amendments
thereto adopted by the BEAVER CREEK METROPOLITAN DISTRICT; and
WHEREAS, the Bea-ver Creek Metropolitan District by its Board
Of Directors did on April 19, 1984; and on June 19, 1984 adopt
certain amendments contained in Exhibit A attached hereto, to
its previously adopted fire code; and
WHEREAS, Section 32- 1- 1002(1)(d) of the Colorado Revised
Statutes, provides no fire code shall apply in unicorporated
portion of any county unless the governing body of the county
adapts a resolution stating that such code shall be applicable
in the unicorporated area of the County.
NOW, THEREFORE BE IT RESOLVED, that the aforesaid amendments
as reflected by Exhibit A, are approved and shall be applicable
within the boundaries of the Beaver Creek Metropolitan.
MOVED, READ AND ADOPTED by the Board of County Commissioners
of the County of Eagle, State of Colorado, at its regular
meeting held the /% h day of September,
1984.
ATTEST:
COUNTY OF EAGLE, STATE OF COLORADO
By and Through its
BOARD OF COUNTY COMMISSIONERS
By: (�
Clerk of the Board of W. Keith Troxel, Chairman
County Commissioners
David E. Mott, Commissioner
liams, Commissioner
Commissioner I.)II(I- djNjC, seconded the
adoption of the foregoing Resolution. The roll having been
called, the vote was as follows:
Commissioner W. Keith roxel
M
Commissioner David E. Mott
Commissioner Dan Williams
This Resolution adopted by 3 — Q vote of the
Board of County Commissioners of the County of Eagle, State of
Colorado.
EXHIBIT A
FIRE SAFETY REGULATIONS
BEAVER CREEK METROPOLITAN DISTRICT
PART II
Revised 02/05/82
Revised 02/11/83
Revised 04/19/83
Revised 06/19/84
Approved:
02/08/82 Beaver Creek Metropolitan District
02/11/82 Eagle County
INTRODUCTION
The Beaver Creek Metropolitan District is responsible to provide for fire
protection in the Beaver Creek Subdivision. As such, it is seeking to fulfill
criteria to obtain the maximum fire protection rating for the project. This would
not only provide exceptional fire /life safety protection for the community, but
it would also minimize insurance rates.
In order to achieve a maximum fire protection rating, the project must demon-
strate compliance in four areas: .
1. Reliable water system.
2. Adequate fire fighting equipment and manpower.
3. Compliance with building construction codes and inclusion
of specific fire /smoke alarms and fire suppression systems.
4. Communications System linking fire /smoke alarms to a central
fire fighting dispatch facility.
The Beaver Creek Metropolitan District is committed to Items 1, 2, and 4 above.
The following regulations and guidelines center around Item 3, plus provision for
connecting to a central communications system.
Any variances from the regulations set forth will require written approval of
the Beaver Creek Metropolitan District Board of Directors.
Variances shall be allowed only when it is demonstrated that granting of the
variance will cause no risk to the public safety and that undue hardship or practical
difficulty would otherwise result.
Fire Protection /Life Safety Standards
Different criteria may apply to Beaver Creek Fire Protection /Life Safety on
project location. The Village Core (Tract A) is very dense commercial area which
must be fully sprinkled, alarmed and monitored. Other locations as a minimum need
only comply with building codes, be monitored by the central dispatch facility,
and have emergency access provisions (see paragraph 5), providing they have no
commercial function. Buildings within Tract A and buildings outside Tract A with
commercial functions shall comply with the following criteria.
1. Fire Suppression: All portions of all buildings shall be fully
sprinklered in accordance with Ordinary Hazard Group 2 of the National
Fire Protection Association (NFPA) Pamphlet 213 entitled "Sprinkler ".
Electrical control rooms shall conform with at least one of the- following
standards and shall be defined as any room with over 200 amp hour service
breaker panel(s).
a. An electrical room shall have a minimun of 2 hour fire
rating. A 17 lb. Halon 1211 extinguisher shall be installed
lust outside the door to the electrical room
Fire Safety - 2.1
rical room shall be fully sprinklered with raintioht
_(raintight rates) shall be installed either outside the
electrical equipment room or outside the building A low
voltage remote switch shall be installed inside the electrical
eguipment room near the door, and locally connected to a
fixed rate heat detector centrally mounted inside the room.
A 17.1b. Halon 1211 extinguisher shall be installed just
outside the door to the electrical equipment room
Protection of areas inappropriate for sprinklering shall be determined by
the Metropolitan District Board of Directors through the variance process.
Fire Fighting Systems:
a. Standpipes: Standpipe systems with hose cabinets shall
be installed in compliance with current NFPA Pamphlet #14.
The standpipes shall be set or dry depending upon their
susceptibility to freezing. _A locking "break glass" cabinet
is required where locations are accessible to the public
b. Portable Fire Extinguishers: Appropriate fire extinguishers
shall be installed at locations consistent with NFPA Pamphlet
#10. A locking "break glass" cabinet is required where locations
are accessible to the public.
C. Commercial Range Hoods: Fixed extinguisher systems shall be
installed in all commercial range hoods per current NFPA
Pamphlet #96.
* If location is acceptable (authority having jurisdiction)
cabinets for standpipes and extinguisher may be one and the
same.
3. Building Design Codes: All buildings shall comply with the following codes
in their most current edition and any other regulations as may be imposed
by the local building department and fire marshall:
a. Uniform Building Code _(current adopted version)
b. Uniform Fire Code ( current version)
C. Uniform Mechanical Code, and more specifically, NFPA Pamphlet
#211 in the area of kitchen and heat exchanger ducts. (current
version)
d. National Electric Code, NFPA Pamphlet 970 (current adopted version)
e. Life Safety Code, NFPA Pamphlet :101 (current version)
f. Air Conditioning and Ventilation Systems, NFPA Pamphlet 190A
(current adopted version)
Fire Safety - 2.2
4. Fire Alarm System:
a. Central Building Alarm System: All buildings shall include
a fully monitored fire detection and annunciation system.
Manual, automatic, extinguishing, waterflow alarm and super-
visory signaling service shall meet with the NFPA standard
72A, 72C for retransmission. An exception to NFPA 72C shall
be that standby power will be sized for 24 -hour capacity
rather than 60. A battery status meter shall be included
on the alarm panel. The fire alarm panel shall be capable
of individual zone disconnection, except for water flow
devices where disconnection will not be allowed. The panel
shall be provided with auxiliary dry contacts N/O (form C)
per zone to operate in the event of "alarm" condition. The
panel shall be provided with one of the following options
for trouble conditions.
1. The panel shall be provided with auxiliary dry
_contacts N/O (form C) per zone to operate in the
event of a trouble condition
2 The panel shall be provided with auxiliary dry
_contacts N/O (form C) to monitor two conditions:
common trouble and switch out of Position. When
the switch out of position is engaged this should
allow the common trouble relay to clear for further
trouble resound conditions
' - Any exceptions to the above shall have approval of the
authority having Jurisdiction
System type shall be noncoded, continuous rings, locking zone
annunciated. Zoning shall be per floor, per stair access and /or
per use area on floor (i.e., kitchen, cafe /banquet, retail, trash
collection points, etc.) for precise Fire Department response
as approved by the Fire Chief. Separate annunciation shall be
required for each sprinkler flow and each supply and return duct
system of air handling units over 2000 CFM. The control panel,
annunciation panel and remote annunciation shall be located as
directed by the Fire Department. Central building signaling
devices shall be located to be heard at a minimum sound level
of 60 db throughout all common areas (including restaurants,
clubs and areas of assembly) and in each living unit (including
lock -off rooms and hotel rooms).
b. Manual Fire Alarms: Manual stations shall be of the double
acting type and shall be located per current NFPA 101 and
installed per current NFPA 72A.
C. Thermal Detector Applications: Thermal detectors shall be
located in mechanical rooms, commercial kitchens, locker areas,
trash chutes and public restrooms.
Fire Safety - 2.3
d. Common Area Alarms: System area smoke detectors shall be
located in all common - areas top of stairs, hall and shafts
(elevator and dumbwaiter).
e. Elevator Alarms: Smoke /thermal detectors shall be located in
elevator equipment rooms, electric equipment rooms, elevator
lobbies and storage areas opening onto corridors. Elevator
lobby detectors shall be located per UBC, powered from the
fire alarm control panel and contain an electrical contact
(form C) for elevator return. All thermal detectors and smoke
detectors shall be spaced and located per NFPA 72E.
f. Dwelling Unit Alarm: Single station smoke detectors having
N/O dry contacts shall light an approved red indicator lamp
over the entry door, visible from the hallway or outside
(180 degrees) as appropriate. Smoke detectors and indicator
lamps shall be powered from the 120 volt emergency panel for
the building.* In addition to smoke detectors, thermal
detectors shall also be installed in each dwelling unit,
connected to and powered from the central building alarm
system. Operation of the thermal detector shall annunciate
the floor -area alarm zone. when two or more single station
detectors are required within a dwelling unit, they shall be
interconnected to alarm simultaneously.
g. Ventilation System Alarm: Duct smoke detectors shall be of
the photocell type with Form C contacts. The detectors shall
contain a "power on" lamp, an alarm lamp and test switch. The
alarm lamp shall be easily observed. Capabilities for manual
restart and subsequent control of ventilation system(s) are to
be provided at the fire alarm control panel.
h. Tamper Switch Alarm: All fire protection control valves
and "Knox Boxes " ** shall be equipped with tamper switches.
Activation of these switches will result in a separate trouble
non - locking alarm but will not sound the building fire alarm.
The trouble alarm shall be provided with N/O (form C) contacts
for transmission of this condition
i. Co=ercial Kitchen Extinguishing System Alarms: Activation
of a range hood extinguisher system will activate the central
building alarm.
j. Wiring: System wiring shall be "Class B" and installed per
NFPA Pamphlet #70, Article 760. All fire alarm system wiring
shall be solid. Stranded or braided wire shall not be
permitted. When power limited cable is used, all components
must be compatible with this application.
Fire Safety - 2.4
k. Off -Site District Monitoring System: An off -site alarm
receiving and dispatching facility shall be alerted whenever
the "building alarm system" is activated. Space provisions
for equipment which will interface with this off -site system
shall be provided. This monitoring equipment will be
supplied, wired and installed by the Beaver Creek Metropolitan
_ Distract or designated agent- Interface equipment shall be
provided by the developer to include: plywood mounted
(size dependent on system) bridge with all alarm and trouble
zones terminated and labeled for interface, 110 ac power
source with receptacles (number of dependent on system)
and proper phone line(s) interface
* For condominium apartments a second N/O contact is required
and shall be wired to the cable television terminal box for
that unit.
** See Article A5.
5. Emergency Access Provisions: A locked steel box ( "Knox Box ") containing
keys for accessing all parts of the building shall be installed on the
outside of the building (location to be approved by Fire Department). The
"Knox Box" shall also contain keys for the emergency operation of equipment
such as elevators, fire alarm panel and annunciator, mechanical and electrical
rooms and building master(s). Only authorized emergency personnel will have
access to the building "Knox Box ", which shall be equipped with a tamper
switch for separate trouble annunciation. The requisitioning of "Knox Boxes"
must be coordinated with the Fire Department.
6. Exit Illumination: All emergency exit lights shall be green in color with
test switches provided.
Review Procedures
Fire protection provisions and codes are technical in nature and therefore
shall be reviewed as they relate to specific projects early in the design phase
with the District's Fire Chief or his designated representative. He shall make
judgement decisions of application of the various codes to specific situations.
All variances shall be made to and approved by the Board of Directors of
the Beaver Creek Metropolitan District
The District's Fire Chief or his representative shall make a final inspection
after the building plans have been reviewed, to determine compliance before a
Certificate of Occupancy is issued.
Nonconforming Structures
Within the Beaver Creek Metropolitan District there may exist structures
which were lawfully erected or for which a building permit was issued before
Part II was passed, but which would be prohibited, regulated or restricted under
the terms of this Part II. It is the intent of this Part II to permit these
nonconformities to continue until they are removed, abandoned, or more than
508 remodeled or destroyed. It is the further intent of this Part II that
nonconforming structures shall not be enlarged upon, expanded or extended nor
be used as grounds for adding other structures or uses prohibited by this Part II.
Fire Safety - 2.5
- ? jig jSy
The next proposed amendment was for the Fire Safety Regulations, the rationale
for which is attached hereto as Exhibit F and incorporated herein by this
reference. Upon motion duly made and seconded it was unanimously
RESOLVED that Beaver Creek Metropolitan District
Fire Safety Regulations, Part II, Paragraph 1,
Fire Suppression, be amended to read in its
entirety as follows:
1. Fire Suppression: All portions of all
buildings shall be fully sprinklered in
accordance with Ordinary Hazard Group 2 of
the National Fire Protections Association
(NFPA) Pamphlet 1113 entitled "Sprinkler ".
Electrical control rooms shall conform with
at least one of the following standards: a)
electrical rooms shall be fully sprinklered
with raintight rated electrical equipment
specified, b) electrical rooms shall have a
minimum of 2 hour fire rating. In both
applications the following specifications
shall be included:
a. A main disconnect switch (raintight
rated) be installed either outside the
electrical equipment room, or outside the
building.
b. A low voltage remote switch installed
inside the electrical equipment room near
the door, and locally connected to a fixed
rate heat detector centrally mounted inside
the room.
c. A 17 lb. Halon 1211 extinguisher be
installed just outside of the door to the
electrical equipment room.
Protection of areas inappropriate for sprinklering
shall be determined by the Fire Board.
The Secretary then reported to the Board that Messrs. Jim Funk and Jay
Hosburgh had began a process of inventorying fire lanes for future signage.
It is their intent to provide a map of the identified egress lanes for the
next Board meeting. Signage will be the financial responsibility of the
District.
The next item was the January Fire Operations Report, attached hereto as
Exhibit G and incorporated herein by this reference. No Board action was
- 6 -
i
t '}
tw.w
Next, upon motion duly made and seconded, it was unanimously
RESOLVED to appoint Ms. Kristi Rosten to serve as
Secretary to the Board beginning May 1, 1983.
The next item before the Board was discussion of the Beaver Creek
�_/1-1A
Metropolitan District Fire Board and a series of recommendations from Mr. Tom
Hickey attached hereto as Exhibit Q and herein incorporated by this reference.
There was considerable discussion of the fact that the Fire Board had in
effect been dissolved by virtue of the resignations of its three members, Jay
Hosburgh, Tom Hickey, and Dave Mott
was unanimously
Upon motion duly made and seconded, it
RESOLVED that the Beaver Creek Metropolitan
District Fire Safety Regulations be amended as
follows:
(a) by omitting reference to the Fire Board on
the Title Page, Part II;
(b) Paragraph 2.1 be amended by omitting the
words, "The District hereby establishes the
Beaver Creek Fire Board, (hereinafter the
Fire Board). The board members shall
include District's Fire Chief, and
representatives from the Beaver Creek
Metropolitan District and Vail
Associates /Risk Management. The Fire Board
will meet monthly to review fire protection
matters" and changing the last
sentence of that paragraph to read, "Any
variances from the regulations set forth
will require written approval of the Beaver
Creek Metropolitan District Board of
Directors; and be it further
RESOLVED that Messrs. Jim Funk and Tom Hickey be
appointed to serve as special advisors to the
Board for the interim one -month period.
No action was taken on the recommendations for Pre - qualified Bidders for
Fire Alarm Systems, also described in Exhibit Q. The Board agreed to table the
amendments 113 and 114 referred to in Exhibit Q as well.
- 9 -