Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutR83-036 adoption of fire safety rules for beaver creek metroe`) e
PROCEEDINGS OF THE BOARD OF
COUNTY COMMISSIONERS OF THE
COUNTY OF EAGLE AND STATE OF
COLORADO.
RESOLUTION `X0. 93'3
WHEREAS, it has heretofore been resolved by Resolution 82, No. 7 that the
Uniform Fire Code, 1979 Edition, published by the International Conference of
Building Officials, 5360 South Workman Mill Road, Whittier, California 90601
including the National Fire Code, and the Life Safety Code, published by the
National Fire Protection Association, 470 Atlantic Avenue, Boston,
Massachusetts 02210, together with Appendices K and L, is applicable within
the boundaries of the Beaver Creek Metropolitan District; and
WHEREAS, by motion adopted February 11, 1983, certain amendments thereto,
a copy of which is attached hereto as Exhibit A, were adopted by the Board of
Directors of the District; and
WHEREAS, by motion adopted April 19, 1983, certain amendments thereto, a
copy of which is attached hereto as Exhibit B, were adopted by the Board of
Directors of the District; and
NOW, THEREFORE BE IT RESOLVED, that the aforesaid amendments shall be
applicable within the boundaries of the Beaver Creek Metropolitan District as
appendices to the Uniform Fire Code, 1979 Edition.
ADOPTED the -� day of 198-3.
BOARD OF COUNTY COMMISSIONERS
i'-erk and •
OF THE COUNTY EAGLE
By:
Chairman
- 1 -
Commissioner
Commissioner
Z
FIRE SAFETY
RULES AND REGULATIONS
OF
BEAVER CREEK METROPOLITAN DISTRICT
EAGLE COUNTY, C,
PARTS I AND
PART I ADOPTED
REVISED
REVISED
PART II ADOPTED
REVISED
REVISED
)LORADO
II
11 -18 -80
11 -01 -81
12 -21 -82
04 -14 -81
02 -05 -82
02 -11 -83
EXHIBIT A
�) r
FIRE SAFETY REGULATIONS
BEAVER CREEK METROPOLITAN DISTRICT
PART II
Revised 02/05/82
Revised 02/11/83
Approved:
2/8/82 Beaver Creek Metropolitan District
2/11/82 Eagle County
Introduction
The Beaver Creek Metropolitan District is responsible to provide for fire
protection in the Beaver Creek Subdivision. As such, it is seeking to fulfill
criteria to obtain the maximum fire protection rating for the project. This.,
would not only provide exceptional fire /life safety protection for the
community, but it would also minimize insurance rates.
In order to achieve a maximum fire protection rating, the project must
demonstrate compliance in four areas:
1. Reliable water system.
2. Adequate fire fighting equipment and manpower.
3. Compliance with building construction codes and inclusion of
specific fire /smoke alarms and fire suppression systems.
4. Communications System linking f ire /smoke alarms to a central
fire fighting dispatch facility.
The Beaver Creek Metropolitan District is committed to Items 1, 2 and 4
above. The following regulations and guidelines center around Item 3, plus
provisions fov connecting to a central communications system.
The District hereby establishes the Beaver Creek Fire Board, (hereinafter
the Fire Board) . The board members shall include District's Fire Chief, and
representatives from the Beaver Creek Metropolitan District and Vail
Associates /Risk Management. The Fire Board will meet monthly to review fire
protection matters. Any variances from the regulations set forth will require
written approval of the Fire Board.
Variances shall be allowed only when it is demonstrated that granting of
the variance will cause no risk to the public safety and that undue hardship or
practical difficulty would otherwise result.
Fire Protection /Life Safety Standards
Different criteria may apply to Beaver Creek Fire Protection /Life Safety
on project location. The Village Core (Tract A) is very dense commercial area
which must be fully sprinkled, alarmed and monitored. Other locations as a
minimum need only comply with building codes, be monitored by the central
dispatch facility, and have emergency access provisions (see paragraph 5),
-providing they have no commercial function. Buildings within Tract A, and
buildings outside Tract A with commercial functions shall comply with the
following criteria.
Fire Safety - 2.1
{r +
1. Fire Suppression: All portions of all buildings shall be fully
sprinklered in accordance with Ordinary Hazard Group 2 of the National
Fire Protection Association (NFPA) Pamphlet #13 entitled "Sprinkler ".
Electrical control rooms shall conform with at least one of the following
standards: a) electrical rooms shall be fully sprinklered with raintight
rated electrical equipment specified, b) electrical rooms shall have a
minimum of 2 hour fire rating. In both applications the following
specifications shall be included:
a. A main disconnect switch (raintight rated) be installed
either outside the electrical equipment room, or
outside the building.
b. A low voltage remote switch installed inside the
electrical equipment room near the door, and locally
connected to a fixed rate heat detector centrally
mounted inside the room.
C. A 17 lb. Halon 1211 extinguisher be installed just outside
of the door to the electrical equipment room.
Protection of areas inappropriate for sprinklering shall be determined by
the Fire Board. (Amended by Resolution of the Board of Directors on
February 11, 1983, to be retroactive-to April 14, 1981.)
2. Fire Fighting System:
a. Standpipes: Standpipe systems with hose cabinets shall be
installed in compliance with NFPA Pamphlet #14. The
standpipes shall be wet or dry depending upon their
susceptibility to freezing.
b. Portable Fire Extinguishers: Appropriate fire extinguishers
shall be installed at locations consistent with NFPA
Pamphlet #10. A "break glass" cabinet is required where
locations are accessible to the public.
C. Commercial Range Hoods: Fixed extinguisher systems shall be
installed in all commercial range hoods per.NFPA Pamphlet
#96.
3. Building Design Codes: All buildings shall comply with the following
codes in their most current edition and any other regulations as may be
imposed by the local building department and fire marshall:
a. Uniform Building Code
Fire Safety - 2.2
b. Uniform Fire Code '
C. Uniform Mechanical Code, and more specifically, NFPA
Pamphlet #211 in the area of kitchen and heat exchanger
ducts.
d. National Electric Code, NFPA Pamphlet #70
e. Life Safety Code, NFPA Pamphlet 4101
f. Air Conditioning and Ventilation Systems, NFPA Pamphlet #90A
4. Fire Alarm System:
a. Central Building Alarm System: All buildings shall include a
fully monitored fire detection and annunciation system.
Manual, automatic, extinguishing, waterflow alarm and
supervisory signaling service shall meet with the NFPA
standard 72A, 72C for retransmission. An exception to NFPA
72C shall be that standby power will be sized for 24 hour
capacity rather than 60. A battery status meter shall be
included on the alarm panel. The fire alarm panel shall be
capable of individual zone disconnection. Additionally, the
panel shall be provided with auxiliary dry contacts N/0 to
operate in the event of "alarm" and /or "trouble" to notify
the central communication system of all conditions monitored
by the building alarm system. System type shall be
uoncoded, continuous ring, zone annunciated. Zoning shall
be per floor, per stair access and /or per use area on floor
(i.e., kitchen, cafe /banquet, retail, trash collection
points, etc.) for precise Fire Department response as
approved by the fire chief. Separate annunciation shall be
required for main sprinkler flow, and each supply and return
duct system of air handling units over 2000 CFM. The control
panel and annunciation panel shall be located as directed by
the Fire Department. Central building signaling devices
shall be located to be heard at a minimum sound level of 80
db throughout all common areas (including restaurants, clubs
and areas-of assembly) and in each living unit (including
lock -off rooms and hotel rooms).
b. Manual Fire Alarms: Manual stations shall be of the double
acting type and shall be located per NFPA 101 and installed
Fire Safety - 2.3
4
_1%.
per NFPA 72A.
C. Thermal Detector Applications: Thermal detectors shall be
located in mechanical rooms, commercial kitchens, locker
areas, trash chutes and public restrooms.
d. Common Area Alarms: System area smoke detectors shall be
located in all common areas top of stairs, hall, and shafts
(elevator and dumbwaiter).
e. Elevator Alarms: Smoke /thermal detectors shall be located
in elevator equipment rooms, electric equipment rooms,
elevator lobbies, and storage areas opening onto corridors.
Elevator lobby detectors shall be located per UBC, powered
from the fire alarm control panel and contain an electrical
contact (Form C) for elevator return. All thermal detectors
and smoke detectors shall be spaced and located per NFPA
72E.
f. Dwelling Unit Alarm: Single station smoke detectors having
N/0 dry contacts shall be installed in each dwelling unit
per UBC. N10 dry contacts shall light an approved red
indicator lamp over the entry door, visible from the
hallway or outside (180 °) as appropriate. Smoke detectors
and indicator lamps shall be powered from the 120 volt
emergency panel for the building.* In addition to smoke
detectors, thermal detectors shall also be installed in each
dwelling unit, connected to and powered from from the
central building alarm system. Operation of the thermal
detector shall annunciate the floor -area alarm zone. When
two -or more single station detectors are required within a
dwelling unit, they shall be interconnected to alarm
simultaneously.
g. Ventilation System Alarm: Duct smoke detectors shall be of
the photocell type with Form C contacts. The detectors
shall contain a "power on" lamp, an alarm lamp and test
switch. The alarm lamp shall be easily observed.
Capabilities- for manual re -start and subsequent control of
ventilation system(s) are to be provided at the fire alarm
control panel.
Fire Safety - 2.4
u
h. Tamper Switch Alarm: All fire protection control valves and
"Knox Boxes " ** shall be equipped with tamper switches.
Activation of these switches will result in a "trouble ":
alarm but will not sound the building fire alarm. The Knox
Box tamper switch shall be connected to an intrusion alarm
panel.
i. Commercial Kitchen Extinguishing System Alarms: Activation
of a range hood extinguisher system will activate the
central building alarm.
j. Wiring: System wiring shall be "Class B" and installed per
NFPA Pamphlet #70, Article 760. All fire alarm system
wiring shall be solid. Stranded or braided wire shall not
be permitted. When power limited cable is used, all
components must be compatible with this application.
k. Off -Site District Monitoring System: An off -site alarm
receiving and dispatching facility shall be alerted
whenever the "building alarm system" is activated. Space
provisions for equipment which will interface with this
off -site system shall be provided. This interface equipment
will be supplied, wired and installed by the Beaver Creek
Metropolitan District or designated agent. A three inch
minimum size conduit shall be provided connecting this
interface equipment with the nearest District man -hole or
stub -out provided for this purpose.
* For condominium apartments a second N/0 contact is required
and shall be wired to the cable t.v. terminal box for that
unit.
** See Article A5.
5. Emergency Access Provisions: A locked steel box ( "Knox Box ") containing
keys for accessing all parts of the building shall be installed on the
outside of the building (location to be approved by Fire Department) . The
"Knox Box" shall also contain keys for the emergency operation of
equipment such as elevators, fire alarm panel and annunciator, mechanical
and electrical rooms. Only authorized emergency personnel will have
access to the building "Knox Box ", which shall be equipped with a tamper
switch for separate security annunciation. The requisitioning of "Knox
Fire Safety - 2.5
_. „�.
Boxes" must be coordinated with the Fire Department.
6. Exit Illumination: All emergency exit lights shall be green in color with
test switches provided.
Review Procedures
Fire protection provisions and codes are technical'in nature, and
therefore shall be reviewed as they relate to specific projects early in the
design phase with the District's Fire Chief or his designated representative.
He shall make judgement decisions of application of the various codes to
specific situations.
Appeals of decisions made by Fire Board shall be made directly to the
Board of Directors of the Beaver Creek Metropolitan District.
The District's Fire Chief or his representative shall make a final
inspection after the building plans have been reviewed, to determine compliance
before a Certificate of Occupancy is issued.
Nonconforming Structures
Within the Beaver Creek Metropolitan District there may exist structures
which were lawfully erected or for which a building permit was issued before
this Part II was passed, but which would be prohibited, regulated or restricted
under the terms of this Part II. It is the intent of this Part II to permit
these nonconformities to continue until they are removed, abandoned, or more
than 50% remodeled or destroyed. It is the further intent of this Part II that
nonconforming structures shall not be enlarged upon, expanded or extended nor
be used as grounds for adding other structures or uses prohibited by this Part
II.
Fire Safety - 2.6
V t �
i'
FIRE SAFETY
RULES AND REGULATIONS
OF
BEAVER CREEK METROPOLITAN DISTRICT
EAGLE COUNTY, COLORADO
PARTS I AND II
PART I ADOPTED 11 -18 -80
REVISED 11 -01 -81
REVISED 12 -21 -82
PART II ADOPTED 04 -14 -81
REVISED 02 -05 -82
REVISED 02 -11 -83
REVISED 04 -19 -83
EXHIBIT B
r
�\ Y
w
FIRE SAFETY REGULATIONS
BEAVER CREEK METROPOLITAN DISTRICT
PART II
Revised 02/05/82
Revised 02/11/83
Revised 04/19/83
Approved:
2/8/82 Beaver Creek Metropolitan District
2/11/82 Eagle County
Introduction
The Beaver Creek Metropolitan District is responsible to provide for fire
protection in the Beaver Creek Subdivision. As such, it is seeking to fulfill
criteria to obtain the maximum fire protection rating for the project. This
would not only provide exceptional fire /life safety protection for the
community, but it would also minimize insurance rates.
In order to achieve a maximum fire protection rating, the project must
demonstrate compliance in four areas:
1. Reliable water system.
2. Adequate fire fighting equipment and manpower.
3. Compliance with building construction codes and inclusion of
specific fire /smoke alarms and fire suppression systems.
4. Communications System linking fire /smoke alarms to a central
fire fighting dispatch facility.
The Beaver Creek Metropolitan District is committed to Items 1, 2 and 4
above. The following regulations and guidelines center around Item 3, plus
provisions for connecting to a central communications system.
Any variances from the regulations set forth will require written approval
of the Beaver Creek Metropolitan District Board of Directors.
Variances shall be allowed only when it is demonstrated that granting of
the variance will cause no risk to the public safety and that undue hardship or
practical difficulty would otherwise result.
Fire Protection /Life Safety Standards
Different criteria may apply to Beaver Creek Fire Protection /Life Safety
on project location. The Village Core (Tract A) is very dense commercial area
which must be fully sprinkled, alarmed and monitored. Other locations as a
minimum need only comply with building codes, be monitored by the central
dispatch facility, and have emergency access provisions (see paragraph 5),
providing they have no commercial function. Buildings within Tract A, and
buildings outside Tract A with commercial functions shall comply with the
following criteria.
1. Fire Suppression: All portions of all buildings shall be fully
sprinklered in accordance with Ordinary Hazard Group 2 of the National
Fire Protection Association (NFPA) Pamphlet 413 entitled "Sprinkler ".
Electrical control rooms shall conform with at least one of the following
standards: a) electrical rooms shall be fully sprinklered with raintight
Fire Safety - 2.1
IL
�`1 •s
R
4
rated electrical equipment specified, b) electrical rooms shall have a
minimum of 2 hour fire rating. In both applications the following
specifications shall be included:
a. A main disconnect switch (raintight rated) be installed
either outside the electrical equipment room, or
outside the building.
b. A low voltage remote switch installed inside the
electrical equipment room near the door, and locally
connected to a fixed rate heat detector centrally
mounted inside the room.
C. A 17 lb. Halon 1211 extinguisher be installed just outside
of the door to the electrical equipment room.
Protection of areas inappropriate for sprinklering shall be determined by
the Fire Board. (Amended by Resolution of the Board of Directors on
February 11, 1983, to be retroactive to April 14, 1981.)
2. Fire Fighting System:
a. Standpipes: Standpipe systems with hose cabinets shall be
installed in compliance with NFPA Pamphlet 414. The
standpipes shall be wet or dry depending upon their
susceptibility to freezing.
b. Portable Fire Extinguishers: Appropriate fire extinguishers
shall be installed at locations consistent with NFPA
Pamphlet #10. A "break glass" cabinet is required where
locations are accessible to the public.
C. Commercial Range Hoods: Fixed extinguisher systems shall be
installed in all commercial range hoods per NFPA Pamphlet
#96.
3. Building Design Codes: All buildings shall comply with the following
codes in their most current edition and any other regulations as may be
imposed by the local building department and fire marshall:
a. Uniform Building Code
b. Uniform Fire Code
C. Uniform Mechanical Code, and more specifically, NFPA
Pamphlet 4211 in the area of kitchen and heat exchanger
ducts.
d. National Electric Code, NFPA Pamphlet 470
Fire Safety - 2.2
j r
a
' e. Life Safety Code, NFPA Pamphlet #101
s
f. Air Conditioning and Ventilation Systems, NFPA Pamphlet #90A
4. Fire Alarm System:
a. Central Building Alarm System: All buildings shall include a
fully monitored fire detection and annunciation system.
Manual, automatic, extinguishing, waterflow alarm and
supervisory signaling service shall meet with the NFPA
standard 72A, 72C for retransmission. An exception to NFPA
72C shall be that standby power will be sized for 24 hour
capacity rather than 60. A battery status meter shall be
included on the alarm panel. The fire alarm panel shall be
capable of individual zone disconnection. Additionally, the
panel shall be provided with auxiliary dry contacts N/0 to
operate in the event of "alarm" and /or "trouble" to notify
the central communication system of all conditions monitored
by the building alarm system. System type shall be
noncoded, continuous ring, zone annunciated. Zoning shall
be per floor, per stair access and /or per use area on floor
(i.e., kitchen, cafe /banquet, retail, trash collection
points, etc.) for precise Fire Department response as
approved by the fire chief. Separate annunciation shall be
required for main sprinkler flow, and each supply and return
duct system of air handling units over 2000 CFM. The control
panel and annunciation panel shall be located as directed by
the Fire Department. Central building signaling devices
shall be located to be heard at a minimum sound level of 80
db throughout all common areas (including restaurants, clubs.
and areas of assembly) and in each living unit (including
lock -off rooms and hotel rooms).
b. Manual Fire Alarms: Manual stations shall be of the double
acting type and shall be located per NFPA 101 and installed
per NFPA 72A.
c. Thermal Detector Applications: Thermal detectors shall be
located in mechanical rooms, commercial kitchens, locker
areas, trash chutes and public restrooms.
Fire Safety - 2.3
i
d. Common Area Alarms: System area smoke detectors shall be
located in all common areas top of stairs, hall, and shafts
(elevator and dumbwaiter).
e. Elevator Alarms: Smoke /thermal detectors shall be located
in elevator equipment rooms, electric equipment rooms,
elevator lobbies, and storage areas opening onto corridors.
Elevator lobby detectors shall be located per UBC, powered
from the fire alarm control panel and contain an electrical
contact (Form C) for elevator return. All thermal detectors
and smoke detectors shall be spaced and located per NFPA
72E.
f. Dwelling Unit Alarm: Single station smoke detectors having
N/O dry contacts shall be installed in each dwelling unit
per UBC. N/O dry contacts shall light an approved red
indicator lamp over the entry door, visible from the
hallway or outside (180 °) as appropriate. Smoke detectors
and indicator lamps shall be powered from the 120 volt
emergency panel for the building.* In addition to smoke
detectors, thermal detectors shall also be installed in each
dwelling unit, connected to and powered from from the
central building alarm system. Operation of the thermal
detector shall annunciate the floor -area alarm zone. When
two or more single station detectors are required within a
dwelling unit, they shall be interconnected to alarm
simultaneously.
g. Ventilation System Alarm: Duct smoke detectors shall be of
the photocell type with Form C contacts. The detectors
shall contain a "power on" lamp, an alarm lamp and test
switch. The alarm lamp shall be easily observed.
Capabilities for manual re -start and subsequent control of
ventilation system(s) are to be provided at the fire alarm
control panel.
h. Tamper Switch Alarm: All fire protection control valves and
"Knox Boxes " ** shall be equipped with tamper switches.
Activation of these switches will result in a "trouble ":
alarm but will not sound the building fire alarm. The Knox
Fire Safety - 2.4
Box tamper switch shall be connected to an intrusion alarm
panel.
i. Commercial Kitchen Extinguishing System Alarms: Activation
of a range hood extinguisher system will activate the
central building alarm.
J_ Wiring: System wiring shall be "Class B" and installed per
NFPA Pamphlet #70, Article 760. All fire alarm system
wiring shall be solid. Stranded or braided wire shall not
be permitted. When power limited cable is used, all
components must be compatible with this application.
k. Off -Site District Monitoring System: An off -site alarm
receiving and dispatching facility shall be alerted
whenever the "building alarm system" is activated. Space
provisions for equipment which will interface with this
off -site system shall be provided. This interface equipment
will be supplied, wired and installed by the Beaver Creek
Metropolitan District or designated agent. A three inch
minimum size conduit shall be provided connecting this
interface equipment with the nearest District man -hole or
stub -out provided for this purpose.
* For condominium apartments a second N/0 contact is required
and shall be wired to the cable t.v. terminal box for that
unit.
** See Article A5.
5. Emergency Access Provisions: A locked steel box ( "Knox Box ") containing
keys for accessing all parts of the building shall be installed on the
outside of the building (location to be approved by Fire Department). The
"Knox Box" shall also contain keys for the emergency operation of
equipment such as elevators, fire alarm panel and annunciator, mechanical
q ,
and electrical rooms. Only authorized emergency personnel will have
access to the building "Knox Box ", which shall be equipped with a tamper
switch for separate security annunciation. The requisitioning of "Knox
Boxes" must be coordinated with the Fire Department.
6. Exit Illumination: All emergency exit lights shall be green in color with
test switches provided.
Fire Safety - 2.5
Review Procedures
Fire protection provisions and codes are technical in nature, and
therefore shall be reviewed as they relate to specific projects early in the
design phase with the District's Fire Chief or his designated representative.
He shall make judgement decisions of application of the various codes to
specific situations.
Appeals of decisions made by Fire Board shall be made directly to the
Board of Directors of the Beaver Creek Metropolitan District.
The District's Fire Chief or his representative shall make a final
inspection after the building plans have been reviewed, to determine compliance
before a Certificate of Occupancy is issued.
Nonconforming Structures
Within the Beaver Creek Metropolitan District there may exist structures
which were lawfully erected or for which a building permit was issued before
this Part II was passed, but which would be prohibited, regulated or restricted
under the terms of this Part II. It is the intent of this Part II to permit
these nonconformities to continue until they are removed, abandoned, or more
than 50% remodeled or destroyed. It is the further intent of this Part II that
nonconforming structures shall not be enlarged upon, expanded or extended nor
be used as grounds for adding other structures or uses prohibited by this Part
II.
Fire Safety - 2.6