HomeMy WebLinkAbout1200 Sunset Ln - 239128404002CBO Inc.
129 Cains Lane
Carbondale, CO 81623
970.309.5259
carla.ostberg@gmail.com
June 2, 2025 Project No. C1937
Mark Miesen
mwmiesen@aol.com
Onsite Wastewater Treatment System (OWTS) Design
4-Bedroom Residence
1200 Sunset Lane
Eagle County, Colorado
Mark,
CBO Inc. observed the installation of the onsite wastewater treatment system (OWTS) on May 6, 2025 for
the subject property. Alpha Excavation installed the system.
The OWTS design is based on 2-bedrooms. An average daily wastewater flow of 525 GPD was used.
The soils were verified prior to installation of the new portion of the soil treatment area (STA). The
subsurface was investigated on May 5, 2025 by digging one soil profile test pit excavation (Test Pit). A visual
and tactile soil analysis was completed by Carla Ostberg at the time of excavation.1
The materials encountered in Test Pit #1 consisted of light brown sandy loam to a maximum depth
explored of 8.0-feet. No bedrock or groundwater was encountered.
A sample of the soil was taken from Test Pit #1 at 3-feet below grade. Soil structure grade was
moderate. The soil formed a ball and a ribbon less than 1-inch in length before breaking. Soil structure
shape was blocky and consistence was friable. Soil texture was more gritty than smooth.
The soil is consistent with Soil Type 2, Sandy Loam, with moderate structure grade. A long-term
acceptance rate (LTAR) of 0.5 gallons per square foot will be used to design the STA. This
application rate is conservative for the purposes of sizing and could have been 0.6 gallons per square
foot.
1 Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile
Evaluation of Soils Training.
Test Pit #1
The existing sewer line from the house to the septic tank and existing 1250-gallon septic tank remained
in use. A 6-inch riser to the outlet side of the septic tank to bring access to grade without multiple lids
was added.
Four existing trenches consist of 9 ‘ADS’ ARC 36 chambers remained in use. Two additional trenches,
each with 9 ‘ADS’ ARC 36 chambers were added for a total of 54 chambers and 810 SF of infiltrative
area. Inspection ports were installed at the beginning and end of each new trench and at the beginning
of each existing trench. Ports were cut to grade and placed in sprinkler boxes for access.
The OWTS was generally installed according to specifications. This observation is not a guarantee of
workmanship and/or parts and materials. CBO Inc. should be notified if changes are made to the OWTS
in the future. Any additional OWTS construction must be according to the county regulations.
LIMITS: Observations are limited to components that are visible at the time of the inspection. The installer must
have documented and demonstrated knowledge of the requirements and regulations of the county in
which they are working. The quality of the installation is dependent on the expertise of the installer, soil
type, and weather conditions.
Please call with questions.
Sincerely,
CBO Inc.
Carla Ostberg, MPH, REHS
Distribution Box
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970) 328-8730
Fax: (970) 328-7185
Permit
Permit No. OWTS-031395-2025
Permit Type: OWTS Permit
Work Classification: Alteration
Permit Status: Active
Issue Date: 2/27/2025 Expires: 6/27/2025
On-Site Wastewater
Treatement System
Project Address Parcel Number
1200 SUNSET LN, EL JEBEL AREA,239128404002
Owner Information Address
Mark Miesen 3055 E. 5th Ave
Denver, CO 80206
Phone:
Cell: (303) 378-8436
Email: mwmiesen@AOL.com
Inspections:
For Inspections Call: (970)
328-8755
Engineer Phone Email
CBO Septic Consulting, Carla Ostberg (970) 309-0525 carla.ostberg@gmail.com
Contractor License Number Phone Email
Alpha Excavation LLC alpha1excavation@gmail.
com
(970) 471-6292OWTSPL-000399-20
25
Permitted Construction / Details:
This permit is for the expansion of the STA for the system originally permitted under OWTS-12-09-4108. This
expansion is designed to accommodate the maximum daily flows for a 4 bedroom house. Install the new
components exactly as depicted in the CBO Inc design dated, stamped and signed on January 20th, 2025 by
Kachayla R Cronk, PE.
The OWTS consists of one existing sewer line from the home and the existing 1250 gallon concrete septic tank. A
new Tuf-Tite distribution box equipped with flow equalizers will be installed and accessible at grade. Two new
trenches will be added to each side of the existing trenches and will contain 9 ADS Arc36 chambers each for a total
of 18 new chambers and a grand total of 54.
Contact Eagle County Environmental Health and the design engineer well in advance of requesting inspections prior
to backfilling any component of the OWTS. The design engineer is responsible for conducting all inspections
necessary to certify the installation and assure the functionality of the system. System certification, along with
photos and a record drawing is required to be submitted to and approved by Eagle County Environmental Health
prior to the use of the system or occupancy of the dwelling.
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS
OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Danielle Salinsky
Date
February 27, 2025
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Thursday, February 27, 2025 1
832‐R‐13‐002
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970) 328-8730
Fax: (970) 328-7185
Permit
Permit No. OWTS-031395-2025
Permit Type: OWTS Permit
Work Classification: Alteration
Permit Status: Active
Issue Date: 2/27/2025 Expires: 6/27/2025
On-Site Wastewater
Treatement System
Project Address Parcel Number
1200 SUNSET LN, EL JEBEL AREA,239128404002
Owner Information Address
Mark Miesen 3055 E. 5th Ave
Denver, CO 80206
Phone:
Cell: (303) 378-8436
Email: mwmiesen@AOL.com
Inspections:
For Inspections Call: (970)
328-8755
Engineer Phone Email
CBO Septic Consulting, Carla Ostberg (970) 309-0525 carla.ostberg@gmail.com
Contractor License Number Phone Email
Alpha Excavation LLC alpha1excavation@gmail.
com
(970) 471-6292OWTSPL-000399-20
25
Permitted Construction / Details:
This permit is for the expansion of the STA for the system originally permitted under OWTS-12-09-4108. This
expansion is designed to accommodate the maximum daily flows for a 4 bedroom house. Install the new
components exactly as depicted in the CBO Inc design dated, stamped and signed on January 20th, 2025 by
Kachayla R Cronk, PE.
The OWTS consists of one existing sewer line from the home and the existing 1250 gallon concrete septic tank. A
new Tuf-Tite distribution box equipped with flow equalizers will be installed and accessible at grade. Two new
trenches will be added to each side of the existing trenches and will contain 9 ADS Arc36 chambers each for a total
of 18 new chambers and a grand total of 54.
Contact Eagle County Environmental Health and the design engineer well in advance of requesting inspections prior
to backfilling any component of the OWTS. The design engineer is responsible for conducting all inspections
necessary to certify the installation and assure the functionality of the system. System certification, along with
photos and a record drawing is required to be submitted to and approved by Eagle County Environmental Health
prior to the use of the system or occupancy of the dwelling.
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS
OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Danielle Salinsky
Date
February 27, 2025
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Thursday, February 27, 2025 1
INSPECTION WORKSHEET (INSP-540900-2025)
FOR EAGLE COUNTY GOVERNMENT
OWTS-031395-2025Case Number:Case Module:Permit Management
06/13/2025 ApprovedInspection Status:Inspection Date:
OWTS Final InspectionInspection Type:Inspector:Kirk Weems
Job Address:Parcel Number:1200 Sunset Ln
El Jebel Area, CO
239128404002
Company Name NameContact Type
Applicant Mark Miesen
Contractor Alpha Excavation LLC Travor Dunsdon
Engineer CBO Septic Consulting Carla Ostberg
Owner Mark Miesen
CommentsPassedChecklist Item
True Existing 1250 gal. concrete tank was kept in place. Risers were
added to bring tank lids to grade as required.
Septic Tank - Septic Tank
True Submitted with PE Final date 06/02/2025Record Drawing - Record Drawing
True Submitted with PE Final date 06/02/2025Record Photos - Record Photos
True Required test pits were observed at time of excavation of new
trenches, confirming soil type from original installation.
Site and Soil - Site & Soil
True Received 06/02/2025Final Certification Letter - Final Certification Letter
True All components installed generally according to plan.General Plan - General Plan
True Increased STA to cover 1 BR addition to home. Total size is now
54 ARC 36 chambers for total of 810 sf of infiltrative surface.
Soil Treatment Area (STA) - Soil Treatment Area (STA)
True Travor Dundson / Alpha ExcavationIdentification of Systems Contractor - Identification of
Systems Contractor
June 13, 2025 Page 1 of 1P.O. Box 179, 500 Broadway, Eagle, CO 81631-0179
129 Cains Lane
Carbondale, CO 81623
970.309.5259
carla.ostberg@gmail.com
January 20, 2025 Project No. C1937
Mark Miesen
mwmiesen@aol.com
Onsite Wastewater Treatment System (OWTS) Design
4-Bedroom Residence
1200 Sunset Lane
Eagle County, Colorado
Mark,
CBO Inc. performed an inspection of the existing onsite wastewater treatment system (OWTS) and
completed an OWTS design for the subject residence. The 5-acre property is located outside of
Carbondale, in an area where OWTSs and wells are necessary.
Legal Description: Subdivision: SODERBERG SUB FIL #4 Lot: 2
BK-0539 PG-0888 MAP 10-11-90
928813 EAS 09-08-05
928814 EAS 09-08-05
Parcel ID: 2391-284-04-002
SITE CONDITIONS The property is currently developed with a 2-bedroom residence and is served by an existing OWTS with
a 1250-gallon 1, two-compartment Copeland concrete septic tank followed by a soil treatment area (STA)
consisting of four gravelless chamber trenches connected serially, each with 9 ‘ADS’ ARC 362 chambers
for a total of 36 chambers and 540 square feet of infiltrative area. Permit No. OWTS-12-09-4108
documents the system. The system was sized to accommodate 2 bedrooms. The permit was issued
on May 6, 2011.
A remodel of the residence is desired. Near term, there will be an addition of a 3rd bedroom. While there
are no immediate plans for further expansion, and we are sizing the system to accommodate up to 4 total
bedrooms in the single-family residence.
We conducted an inspection of the OWTS on January 16, 2025. The septic tank is located to the south
of the residence. Both septic tank lids were accessible from grade at the time of our inspection. One foot
of risers were installed on the inlet side of the septic tank and no risers were installed on the outlet side of
the septic tank (although two lids are stacked on one another).
At the time of the inspection, liquid levels in the septic tank were normal. The septic tank was pumped by
Altitude Septic at the time of the inspection and the filter was cleaned. The outlet pipe is cocked up
slightly which is an indication of settling outside of the septic tank.
1 Documented volume is 1000-gallons; however, actual volume was verified as 1250-gallons at the time of our
January 16, 2025 inspection.
2 ‘ADS’ ARC 36 chambers measure 3’ wide by 5’ long for a total of 15 square feet per chamber.
Page 2
We walked the approximate STA. There was snow cover at the time of our inspection and we did not
observe inspection ports, but we understand they are present and should be easy to find once the snow
melts.
There should be no traffic or staging of material over the STA site to avoid compaction of soils.
Clean out
View of septic tank lids Two lids on the outlet side
Page 3
Inlet side of septic tank Effluent filter
Effluent filter cleaned at the time of the inspection
Approx STA
Page 4
Inlet tee (other pipe capped) Effluent filter clean Outlet tee cocked upward
Note outlet pipe is cocked upward / mid-tank baffle
SUBSURFACE
The subsurface was investigated prior to the original OWTS design from ALL SERVICE septic, LLC, and
documented in a report dated June 5, 2009 (enclosed). One soil profile test pit was excavated and three
percolation tests run. “…The materials in the profile pit consisted of 6 inches of topsoil, underlain by sandy
clay to 6 feet, underlain by silty sand and small basalt fragments to the maximum depth explored of 8 feet.
Groundwater was not encountered. Percolation rates ranged from 20 minutes per inch (MPI) to 80 MPI, with
an average rate of 47 MPI. A 47 MPI rate, and an application rate of 0.5 gal/SF will be used to design the
OWS.”
With this documentation and our knowledge of soils in the area, we are assuming soils are consistent
with Soil Type 2A. An application rate of 0.5 gal/SF has been used to estimate additional square footage
necessary to accommodate additional bedrooms.
A soil profile test pit must be excavated prior to installation of the additional trenches. This office must be
called to verify soils. If findings are different than described, the design may be subject to change.
Page 5
DESIGN SPECIFICATIONS
Table 1 below compares the size of the existing OWTS compared to what is needed to serve a remodel
which could include up to 4-total bedrooms in a single-family residence.
Current OWTS Regulation Calculations
75 GPD x 2 persons/bedroom x 3 bedrooms + 75 GPD (4th Bedroom) = 525 GPD
ESTIMATED WASTEWATER FLOW = 525 GPD
LTAR = 0.5 gallons/SF
525 GPD / 0.5 gal/SF = 1050 SF x 1.0 (gravity trenches) x 0.7 (chambers) = min. 735 SF
Table 1
Existing Current OWTS Regulation
Tank Size 1250-gallon, two-compartment
concrete septic tank
4 bedrooms = min. 1250-gallon
septic tank
Soil Treatment Area
(STA)
Gravity trenches,
chambers
4 trenches, each with 9 ‘ADS’
ARC 36 chambers = 36 chambers
and Infiltrative area = 540 SF
Infiltrative area = Min. 735 SF
Design Calculations:
Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms + 75 GPD (4th Bedroom) = 525 GPD
LTAR = 0.5 GPD/SF
525 GPD / 0.5 GPD/SF = 1050 SF x 1.0 (gravity trenches) x 0.7 (chambers) = 735 SF / 15 SF/chamber =
min. 49 ‘ADS’ ARC 36 chambers
Min. 735 SF – existing 540 SF = add min. 195 SF
Add 2 trenches, each with 9 ‘ADS’ ARC 36 chambers for a total addition of 270 SF
Total 54 ‘ADS’ ARC 36 chambers and 810 SF
The OWTS design is based on 4-bedrooms. An average daily wastewater flow of 525 GPD will be used.
For the purposes of this OWTS design, Benchmark Elevation has been established as 100’ as the
elevation of the sewer line existing the septic tank. It should be noted that the outlet side of the septic
tank has no risers but is approximately 6-inches below native grade (2 lids have been added). CBO Inc.
should be notified of any discrepancies or problems with grade elevations of proposed components
during installation of the OWTS.
OWTS Component Minimum Elevation
Distribution Box (NEW) Approximate horizontal distance 10’ / min. 1% fall /
min. 1.25” fall
Infiltrative Surface min. 1% fall to all trenches (we recommend
locating the beginning of each trench to determine
the elevation of the new distribution box)
*Elevations are based upon standard OWTS installation practices. Component elevations may change during
installation due to site conditions. Minimum grade refers to piping between components.
The existing sewer line from the house to the septic tank and existing 1250-gallon septic tank will remain
in use. We recommend adding a 6-inch riser to the outlet side of the septic tank to bring access to grade
without multiple lids. The existing sewer line exiting the septic tank is cocked upward, which is an
indication of settling of the sewer line outside of the septic tank. This sewer line should be re-aligned to
exit the septic tank level and then drop with a minimum of 1% fall to the new distribution box.
Page 6
The elevation and location of the new distribution box should be set based on the location and elevations
of the existing chamber trenches. The distribution box must be accessible from grade with flow
equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to
each trench.
Four existing trenches consist of 9 ‘ADS’ ARC 36 chambers and two additional trenches, each with 9
‘ADS’ ARC 36 chambers will be added for a total of 54 chambers and 810 SF of infiltrative area. There
must be at least 4-feet of undisturbed soil between existing and new trenches. Inspection ports must be
installed at the beginning and end of each new trench. We recommend installing inspection ports at the
beginning of each existing trench if they are not already present. Ports may be cut to grade and placed
in sprinkler boxes for access.
COMPONENT SPECIFICATIONS
The component manufacturers are typical of applications used by contractors and engineers in this area.
CBO Inc. must approve alternative components prior to installation of the OWTS. Requests must
be submitted, in writing, to our office for approval prior to installation. Component technical data
sheets are available upon request.
COMPONENT MANUFACTURER MODEL NO. COMMENTS
Riser Copeland Concrete 6” riser
Distribution Box, risers, lid and flow equalizers
Tuf-Tite Risers on distribution box to grade, 4 speed levelers Chambers ADS ARC 36 18 new ‘ADS’ ARC 36 chambers
Construction must be according to the jurisdiction’s adopted On-Site Wastewater Treatment System
Regulations, the OWTS Permit, and this design.
PERMIT APPLICATION INSTRUCTIONS
An OWTS Permit Application must be submitted to the Eagle County Environmental Health
Department. https://www.eaglecounty.us/environmentalhealth/septicsystems
All questions regarding permit submission can be directed to Eagle County Environmental Health
Department, 970-384-9813 or environment@eaglecounty.us.
INSTALLATION CONTRACTOR
CBO Inc. expects that the installer be experienced and qualified to perform the scope of work outlined in this
design. The installer must review this design thoroughly and coordinate with our office in advance of
installation. Any additional conditions in this design or county permit must be completed and documented
prior to final approval of the OWTS installation. Communication between the installer and this office is
expected throughout the installation.
INSTALLATION OBSERVATIONS CBO Inc. must view the OWTS during construction. The OWTS observation should be performed before
backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing
siphons, and other plumbing, as applicable, must also be observed. CBO Inc. should be notified 48 hours
in advance to observe the installation.
Page 7
In an effort to improve the accuracy of the record drawing, we request that the installer provide a
sketch of the installation, including path of the sewer lines, water line installation (if applicable),
septic tank location, STA location, and measurements from building corners or another fixed
objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design
Packet. Photographs of the installation and final cover are also requested to supplement our installation
documentation.
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire
disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing
characteristics (but without taproots), provides a maximum transpiration rate, and competes well with
successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
cover.
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating STAs, and any other components needing maintenance.
Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials
should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during
construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing
fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a
running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA.
If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned
annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be
flushed annually, or as needed.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS.
Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste
only.
ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high-
water conditions and shall be connected to a control breaker separate from the high-water alarm breaker
and from any other control system circuits. The pump system shall have a switch so the pump can be
manually operated.
Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil.
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backfill over the STA must be uniform and granular with no material greater than minus 3-inch.
Page 8
LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions
described in report, CBO Inc. should be notified. All OWTS construction must be according to the county
regulations. Requirements not specified in this report must follow applicable county regulations. The
contractor should have documented and demonstrated knowledge of the requirements and regulations of
the county in which they are working. Licensing of Systems Contractors may be required by county
regulation.
Please call with questions.
Sincerely,
CBO Inc.
Carla Ostberg, MPH, REHS
Tough Problem
Providing a simple, reliable, and
permanent means for dividing septic
tank effluent flow.
TUF-TITE Solution
A strong, stable, permanent,
non-corrosive Tuf-Tite Distribution
Box, with a Tuf-Tite Speed Leveler
in each outlet.
Snap-in pipe seals
They’re patented. Simply insert
your PVC pipe and push it
through the flexible, polyethylene
Tuf-Tite seal. Pipes fit watertight.
Installation couldn’t be easier.
TTuuff--TT iittee®®
DDiissttrriibbuuttiioonn BBooxx..
TTHHEE TTOOUUGGHH OONN EE!!
■Injection molded HDPE
■Non-corrosive
■Simple to install
■Easy to level
In a septic environment, no other
material can match High Density
Polyethylene in delivering a lifetime
of trouble-free service. Tuf-Tite
Distribution Boxes are injection
molded, using only premium HDPE
which contains no fillers or foam.
They’re permanent
Unlike cement-based pipe
grout, Tuf-Tite seals will not
crack or corrode in septic
conditions. They stay pliable
and watertight permanently.
Stackable Riser
Easily extend the top of the box
to grade, in 6” increments.
Stackable HDPE Risers interlock
firmly and accept a screw-on lid
or grate.
7-Hole Distribution Box
■Injection molded.
Exceptionally
strong.
■Domed Lid
is ribbed for
exceptional
strength.
■Patented
snap-in
pipe seals
simplify
installation.
Domed Lid. Can
be anchored to box
or Riser with 4
stainless screws.
Optional Risers.
They stack, in 6”
increments, to
extend Box to
grade.
Fittings included.
The 7HD2 comes
complete with a
Domed Lid and 9
snap-in fittings of
your choice.
16”
S-35 S-40
P-10
16”
6”
6”
14-1/2”
2” Drop
INSTALLATION IS
JUST THIS SIMPLE
1.Position the Distribution Box
on level virgin soil.
Do not place box on a
concrete slab.
2.Install the inlet pipe and
outlet pipes. Be sure the
bottoms of all pipes rest on
virgin soil.
3.Level the Distribution Box
and all pipes as needed.
4.Backfill the pipes to within
two feet of the Distribution
Box. Recheck the level of the
box, then backfill up to the
top lid ridge.
5.Install and adjust Tuf-Tite
Speed Levelers.
6.Place lid on the Distribution
Box and finish backfilling.
Choice of Fittings
S-35 Pipe Seal, for:
■ Sewer and Drain
■ SDR 35 ■ ASTM 3034
■ Thin Wall ■ 1500 Lb. Crush
S-40 Pipe Seal, for:
■ Schedule 40
■ 4” Corrugated
P-10 Plug, for unused holes
Tuf-Tite Speed Levelers™
Control the flow of effluent from
the Distribution Box. Simply
insert a Speed Leveler into each
outlet pipe. Rotate each Speed
Leveler so the flow is distributed
as desired. Available for 3” or 4”
PVC pipe.
Versatile Options
Drain Grate.Black 16” x 16”
HDPE grate. ADA compliant.
Can be affixed to Box or Riser
with 4 stainless corner screws.
6” Riser.Stackable 16” x 16”
HDPE Riser provides 6”
elevation to the Box or Riser.
Ribbed for added rigidity.
©2005 Tuf-Tite® Corporation
Form 7HD2-6.
Water-tight
Lids and Risers
by Tuf-Tite®Drainage and Septic Products
Tuf-Tite®Corporation
1200 Flex Court
Lake Zurich, Illinois 60047
7-Hole Distribution Box 7HD2
THE ARC 36 CHAMBER BY INFILTRATOR
Leaching chambers are rapidly becoming the product of choice for leachfield applications
over conventional pipe and gravel systems. Their lightweight construction offers lower
installed costs and less intrusive installations.
ENGINEERED FOR OPTIMAL PERFORMANCE
The Arc 36 septic leaching chamber is a sturdy, lightweight plastic unit that combines maximized infiltrative surface area and storage capacity with an improved structural design to handle most any conventional leachfield system challenge without sacrificing performance.
FEATURES & BENEFITS:
• Injection-molded from from polyolefin for lightweight and sturdy design.
• 10-degree integral articulating joint that is ideal for either straight or contoured septic leachfield applications.
• Corrugated chamber design eliminates flat surfaces and provides increased load bearing capability in the trench.
• Designed to accommodate both gravity-fed and pressure-dosed systems.
• “Lock and Drop” joint provides a more positive connection during installation and backfill.
• A universal inlet/outlet endcap.
• Inspection vent ports on every unit with easy-to-remove knockouts for maximum job site flexibility.
• Convenient five-foot lengths are easy to handle.
• Quickly installed by one person into three-foot wide trench or bed applications.
• Increased plumbing option with Side Port Coupler component which snaps in place to allow side entry at any joint throughout trench line.
• Diamond plate texture increases slip resistance and enhances ease of installation.
Contact Infiltrator Water Technologies’ Technical Services Department for assistance at 1-800-221-4436
Diamond
Plate Texture
Overlocking Ends
Side Port
Coupler
Louvers and Feet
Arc 36Arc 36
THE ARC 36 CHAMBER BY INFILTRATOR
Contact Infiltrator Water Technologies’ Technical Services Department for assistance at 1-800-221-4436
ARC004 0522
Arc 36 CHAMBER
Length 63” (1,600 mm)
Effective Length 60” (1,524 mm)
Sidewall Height 7.5” (191mm)
Overall Height 13” (330 mm)
Overall Width 34” (864 mm)
Weight 15.5 lbs
Total Bottom Area 12.27 sq ft
Capacity 8.4 cu ft (63 gal)
CHAMBER REQUIREMENTS
Chamber shall meet the load rating of H-10 (16,000 lb per axle) with a minimum of
12 inches of cover when tested in accordance with IAPMO PS 63 and installed in
accordance with manufacturers installation procedures.
CHAMBER CONNECTION
Each chamber shall interlock with an integral articulating joint. Articulating joints shall
have a free range of horizontal rotation of 20 degrees, with a maximum of 10 degrees
in either direction. Articulating joint shall be constructed by placing the dome with
previously–installed chamber, with final engagement occurring when the lower base
flanges of the incoming chamber under-lap the raised base flanges of the previously-
installed chamber.
4 Business Park Road
P.O. Box 768
Old Saybrook, CT 06475
860-577-7000 • Fax 860-577-7001
1-800-221-4436
www.infiltratorwater.com • info@infiltratorwater.com
(a) The structural integrity of each chamber, endcap and other accessory manufactured
by Infiltrator (collectively referred to as “Units”), when installed and operated in a leach-
field of an onsite septic system in accordance with Infiltrator’s installation instructions,
is warranted to the original purchaser (“Holder”) against defective materials and work-
manship for one year from the date upon which a septic permit is issued for the septic
system containing the Units; provided, however, that if a septic permit is not required for
the septic system by applicable law, the one (1) year warranty period will begin upon the
date that installation of the septic system commences. In order to exercise its warranty
rights, Holder must notify Infiltrator in writing at its corporate headquarters in Old Say-
brook, Connecticut within fifteen (15) days of the alleged defect. Infiltrator will supply
replacement Units for those Units determined by Infiltrator to be defective and covered
by this Limited Warranty. Infiltrator’s liability specifically excludes the cost of removal
and/or installation of the Units.
(b) THE LIMITED WARRANTY AND REMEDIES IN SUBPARAGRAPH (a) ARE EX-
CLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS,
INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE.
(c) This Limited Warranty shall be void if any part of the chamber system (chamber,
endcap or other accessory) is manufactured by anyone other than Infiltrator. The
Limited Warranty does not extend to incidental, consequential, special or indirect
damages. Infiltrator shall not be liable for penalties or liquidated damages, including
loss of production and profits, labor and materials, overhead costs, or other losses or
expenses incurred by the Holder or any third party. Specifically excluded from Limited
Warranty coverage are damage to the Units due to ordinary wear and tear, alteration,
accident, misuse, abuse or neglect of the Units; the Units being subjected to vehicle
traffic or other conditions which are not permitted by the installation instructions; failure
to maintain the minimum ground covers set forth in the installation instructions; the
placement of improper materials into the system containing the Units; failure of the
Units or the septic system due to improper siting or improper sizing, excessive water
usage, improper grease disposal, or improper operation; or any other event not caused
by Infiltrator. This Limited Warranty shall be void if the Holder fails to comply with all of
the terms set forth in this Limited Warranty.
Further, in no event shall Infiltrator be responsible for any loss or damage to the Holder,
the Units, or any third party resulting from installation or shipment, or from any product
liability claims of Holder or any third party. For this Limited Warranty to apply, the Units
must be installed in accordance with all site conditions required by state and local
codes; all other applicable laws; and Infiltrator’s installation instructions.
(d) No representative of Infiltrator has the authority to change this Limited Warranty in
any manner whatsoever, or to extend this Limited Warranty. No warranty applies to any
party other than the original Holder.
The above represents the standard Limited Warranty offered by Infiltrator. A limited
number of states and counties have different warranty requirements. Any purchaser of
Units should contact Infiltrator’s corporate headquarters in Old Saybrook, Connecticut,
prior to such purchase, to obtain a copy of the applicable warranty, and should carefully
read that warranty prior to the purchase of Units.
INFILTRATOR WATER TECHNOLOGIES STANDARD LIMITED WARRANTY
U.S. Patents: 8322948; 8337119; 8297880; 7914230; 7008138. Other patents pending. Infiltrator, Quick4 and EZflow are registered trademarks of Infiltrator Water Technologies. Infiltrator Water Technologies is a wholly-owned subsidiary of Advanced Drainage Systems, Inc. (ADS).
© 2022 Infiltrator Water Technologies, LLC. Not responsible for any typographic errors. Printed in U.S.A.
13"
60.0"
(EFFECTIVE LENGTH)
34"
63.5"
13"60.0"(EFFECTIVE LENGTH)34"63.5"13"60.0"(EFFECTIVE LENGTH)34"63.5"
13"
60.0"
(EFFECTIVE LENGTH)
34"
63.5"
January 4,2005 Project No.1045
Tom and Suzanne Young
0062 Corral Drive
Carbondale,Colorado 81623
Subsurface Investigation and Percolation Test
67 Sunrise Drive
Lot 2,Soderberg Subdivision
Eagle County,Colorado
Tom Young,
ALL SERVICE septic,LLC,performed a subsurface investigation and percolation test for 67 Sunrise
Drive,Eagle County,Colorado on December 29,2004.
EXISTING CONDITIONS
The subject property is located in a rural area where Onsite Wastewater Systems (OWS)and wells are
necessary.There are no structures on the property.There is an existing well located in the
southeastern portion of the lot,as indicated on Figure 1.The slope at the area of the percolation holes
is 5%to the west,and vegetation consists of a full cover of native grasses and sagebrush.
GEOLOGY
A geologic map for the area is the RECONNAISSANCE GEOLOGIC MAP OF THE CONIFER
QUADRANGLE,JEFFERSON COUNTY,COLORADO MISCELLANEOUS FIELD STUDIES
MAP MF-597.A portion of the map is presented on Figure 5.Subsurface conditions were exposed in
test pit excavated at the proposed repair field location and at an outcrop of rock west of the existing
well.The test pits indicate the site is underlain by a thin layer of topsoil,underlain by sandy clay to 3
feet,underlain by intensely weathered gneiss bedrock to a depth of 8 feet.The result of a joint and
fracture analysis of the test pit and outcrop west of the well indicate a resultant flow to the southwest.
The results of the gradation analysis are presented on Figure 7.
A topographic map of the area is the UNITED STATES GEOLOGIC SURVEY,CONIFER
QUADRANGLE,JEFFERSON COUNTY,COLORADO.A portion of the map is represented as
Figure 6.The topographic analysis,as represented on Figure 8,indicates a topographic flow to the
southeast.
ANALYSIS
Upon the establishment of geologic,topographic,and development conditions at the site,the goal of
our investigation was to:1.evaluate whether the proposed location of the repair drain field is suitable
from a geologic point-of-view and 2.provide recommendations for construction of the repair OWS to
provide a low risk of contamination of wells.The investigation indicates the angles between geologic
and topographic flow range between 85 degrees and 147 degrees at the proposed repair onsite drain
field.The lines connecting the onsite well exceed the 60o,as required by the JCDHE.The results are
presented as Table 1.The proposed repair onsite field can be installed with a low risk of
contamination to the proposed onsite well.The proposed repair onsite field can be installed with a
low risk of contamination to the existing well at the adjacent parcel to the east.Based on observations
and analysis of the topography and surrounding development it is not reasonable to obtain a 200-foot
separation between the onsite well and the proposed repair onsite drain field.
SUBSURFACE
The subsurface was investigated by evaluating a profile pit,and digging 3 percolation holes,at the
locations indicated on Figure 1.The materials in the profile pit consisted of 6 inches of topsoil,
underlain by sandy clay to 6 feet,underlain by silty sand,with calcium deposits and small basalt
fragments to the maximum depth explored of 8 feet.Groundwater was not encountered.Percolation
rates ranged from 20 minutes per inch (MPI)to 80 MPI,with an average rate of 47 MPI.
LIMITS:
Results are based on field investigations and data provided by the client.If soil conditions
encountered are different from conditions described in report,ALL SERVICE septic,LLC should be
notified
Please call with questions.
ALL SERVICE septic,LLC Reviewed By:
Timothy R.Petz Richard H.Petz,P.E.
3 copies
EAGLE COUNTY ENVIRONMENTAL HEALTH DEPARTMENT
Percolation Test and Soils Data Form - TABLE 1 - PROJECT 1045
PROFILE PIT Date of Test: 12-29-04
0 - 6"Topsoil, Root Zone, Clayey
6" - 6'Clay, Sandy, Stiff, Moist, Brown
6' - 8'Sand, Silty, Heavy Calcium Deposits, Small Basalt Rock Fragments
Hard, White
No Groundwater was Encountered
Hole
No.
Hole
Depth (in.)
Interval
(min.)
Measurement at
Start of Interval
(in.)
Measurement at
End of Interval
(in.)
Change (in.) Percolation Rate
(min./in.) MPI
1 24 20 9.50 12.50 3.00
20 12.50 14.00 1.50
20 14.00 15.00 1.00
20 15.00 15.75 0.75
20 15.75 16.25 0.50 40
20 16.25 17.00 0.75
2 26 20 4.25 5.25 1.00
20 5.25 6.75 1.50
20 6.75 7.50 0.75
20 7.50 8.00 0.50
20 8.00 8.25 0.25 80
20 8.25 8.75 0.50
3 32 20 8.75 10.25 1.50
20 10.25 12.00 1.75
20 12.00 13.50 1.50
20 13.50 14.75 1.25
20 14.75 15.75 1.00
20 15.75 16.75 1.00 20
AVERAGE RATE = 47 MPI
Performed By All Service Septic, LLC
December 14,2011 Project No.1601
Shirley Aguilar
9 Summer Street
Bedford,MA 01730
Installation Observations
0067 Sunrise Lane
Eagle County,Colorado
Shirley,
ALL SERVICE septic,LLC reviewed the installation of the onsite wastewater system (OWS)on
November 2nd 2011 for the subject property.
The installation included a 1000-gallon,two-compartment concrete septic tank with an effluent filter
on the outlet,followed by 4 gravelless chamber trenches.Each trench had 9 Arc-36 chambers for a
total area of 445 SF.Serial distribution was used to distribute effluent.
The OWS was generally installed according to specifications.This observation is not a guarantee of
workmanship and/or parts and materials.ALL SERVICE septic,LLC should be notified if changes
are made to the OWS.
LIMITS:
The observations were based on information submitted.If conditions are different from conditions
described in this letter,ALL SERVICE septic,LLC should be notified.All additional OWS
construction must be according to the county regulations.The installer should have documented and
demonstrated knowledge of the requirements and regulations of the county in which they are
working.
Please call with questions.
Sincerely,
ALL SERVICE septic,LLC Reviewed By:
Timothy R.Petz Richard H.Petz,P.E.
2 copies sent
Copy sent to Eagle County
Work Classification: NewPermit
CO
Address Owner Information
Permit Status: Active
Project Address
239128404002
Permit Type: OWTS Permit
Permit NO. OWTS-12-09-4108
Expires: 9/3/2011 Issue Date: 5/6/2011
Parcel No.
000067 SUNRISE LN EL JEBEL AREA, CO
Private Wastewater
System
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970)328-8755
Fax: (970)328-8788
Phone: (617)495-7462
Cell:
Inspection
For Inspections call: (970) 328-8755
Inspections:
IVR
OWTS Partial Inspection 093
OWTS Final Inspection 095
PhoneEngineer(s)
(970)618-5033ALL SERVICE SEPTIC
Contractor(s)Phone Primary ContractorLicense Number
JACOBER BROTHERS
CONSTRUCTION INC
(970)963-9420 Yes18140
DAVID & SHIRLEY AGUILAR
Permitted Construction / Details:
Install as per engineer design dated June 5, 2009. Installation shall consist of a 1000 gallon precast,
concrete, two compartment septic tank with an effluent filter on the outlet and 45 'Quick 4' Infiltrator
chambers installed in three trenches, in serial distribution. Maintain all required setbacks including at
least 100 feet from each of the wells to the leachfield. Call Eagle County and design engineer for a final
inspection before covering any portion of the system.
Issued by: Environmental Health Department, Eagle County, CO
May 06, 2011
Date
Customer Copy
Andrew Jessen
CONDITIONS:
1. THIS PERMIT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT
COMMENCED WITHIN 120 DAYS OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
2. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN C.R.S. 25-10-101, et seq., AS AMENDED
3. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND
BUILDING DEPARTMENTS SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN
BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL
SYSTEM TO BE LICENSED
Work Classification: NewPermit
CO
Address Owner Information
Permit Status: Active
Project Address
239128404002
Permit Type: OWTS Permit
Permit NO. OWTS-12-09-4108
Expires: 9/3/2011 Issue Date: 5/6/2011
Parcel No.
000067 SUNRISE LN EL JEBEL AREA, CO
Private Wastewater
System
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970)328-8755
Fax: (970)328-8788
Phone: (617)495-7462
Cell:
Inspection
For Inspections call: (970) 328-8755
Inspections:
IVR
OWTS Partial Inspection 093
OWTS Final Inspection 095
PhoneEngineer(s)
(970)618-5033ALL SERVICE SEPTIC
Contractor(s)Phone Primary ContractorLicense Number
JACOBER BROTHERS
CONSTRUCTION INC
(970)963-9420 Yes18140
DAVID & SHIRLEY AGUILAR
Permitted Construction / Details:
Install as per engineer design dated June 5, 2009. Installation shall consist of a 1000 gallon precast,
concrete, two compartment septic tank with an effluent filter on the outlet and 45 'Quick 4' Infiltrator
chambers installed in three trenches, in serial distribution. Maintain all required setbacks including at
least 100 feet from each of the wells to the leachfield. Call Eagle County and design engineer for a final
inspection before covering any portion of the system.
Office Copy
May 06, 2011
Issued by: Environmental Health Department, Eagle County, CO Date
Andrew Jessen
CONDITIONS:
1. THIS PERMIT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT
COMMENCED WITHIN 120 DAYS OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
2. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN C.R.S. 25-10-101, et seq., AS AMENDED
3. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND
BUILDING DEPARTMENTS SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN
BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL
SYSTEM TO BE LICENSED
1200 Su n set Lane Legend
1200 Suns et Ln
W iz a
100 ft
N➤➤N
MH552 LLC
3055 E 5TH AVE
DENVER, CO 80206-4345
Account: R032537
Tax Area: 007 - EL JEBEL (AREA) -
007
Acres: 5.000
Parcel: 2391-284-04-002
Situs Address:
001200 SUNSET LN
EL JEBEL AREA, 0
Value Summary
Value By:Market Override
Land (1)$565,000 N/A
Single Family
Residence (1)
$921,050 N/A
Extra Feature (1)$4,230 N/A
Total $1,490,280 $1,490,280
Legal Description
Subdivision: SODERBERG SUB FIL #4 Lot: 2
BK-0539 PG-0888 MAP 10-11-90
928813 EAS 09-08-05
928814 EAS 09-08-05
Sale Data
Doc. #Sale Date Deed Type Validity Verified Sale Price Ratio Adj. Price Ratio Time Adj.
Price
Ratio
202305534 05/24/2023 SWD QV Y $1,725,000 83.20 $1,725,000 83.20 $1,725,000 83.20
929407 09/09/2005 WD QV Y $360,000 156.94 $360,000 156.94 $360,000 156.94
R726136 03/28/2000 WD QV Y $160,000 353.13 $160,000 353.13 $160,000 353.13
B: 000624 P:
000912
11/04/1993 WD QV Y $88,600 637.70 $88,600 637.70 $88,600 637.70
Land Occurrence 1
Abstract Code 1112 - SINGLE FAM.RES.-LAND Percentage 100.0
Use Code 1000 - RESIDENTIAL Neighborhood 1010.2 - MOUNTAIN MEMORIES
Land Code 9056 - MOUNTAIN MEADOWS Super Neighborhood 900 - BASALT / EL JEBEL AREA
Size 5
SubArea ACTUAL EFFECTIVE HEATED FOOTPRINT
Land L 1
Property Record Card
Eagle
A#: R032537 P#: 239128404002 As of: 01/17/2025 Page 1 of 3
Land Occurrence 1
Total 1.00
Value Rate Rate Rate Rate
$565,000 565,000.00
Single Family Residence Occurrence 1
Abstract Code 1212 - SINGLE FAM.RES-
IMPROVEMTS
Percentage 100
Use Code 1000 - RESIDENTIAL Neighborhood 1010.2 - MOUNTAIN MEMORIES
Building Type 121200 - SFR Arch Style 3 - 2 STORY
Exterior Wall 10 - WOOD SD GD
31 - STONE VEN
Percentage 80
20
Roof Cover 6 - ASP SHINGL Roof Structure 3 - GABLE/HIP
Interior Wall 5 - DRYWALL Percentage 100
Floor 12 - HARDWOOD
14 - CARPET INV
Percentage 70
30
Heating Fuel 3 - GAS Heating Type 8 - RAD WATER
Actual Year Built 2011 Bedrooms 2
Bathrooms 2 Construction Quality 5 - GOOD
Effective Year Built 2011 Fixtures 10
Rooms 5 Units 1
Units 1 Super Neighborhood 900 - BASALT / EL JEBEL AREA
Stories 2 - STORIES 2.0 Use Code 1000 - RESIDENTIAL
Garage 1.5 - GARAGE 351-500
SubArea ACTUAL EFFECTIVE HEATED FOOTPRINT
BAS 1062.0 1062.0 1062.0 1062.0
FUS 432.0 432.0 432.0 432.0
GDF 352.0 352.0
PTO 505.6 50.6 505.6
UDU 240.3 96.1 240.3
Total 2,591.90 1,640.70 1,494.00 2,591.90
Value Rate Rate Rate Rate
$921,050 355.36 561.38 616.50 355.36
Property Record Card
Eagle
A#: R032537 P#: 239128404002 As of: 01/17/2025 Page 2 of 3
Single Family Residence Occurrence 1
Sketch by Apex Sketch v5 Pro™
24'8.5'8.5'24'34'6'3.5'12'3.5'6'1.5'8.5'BAS
1062.0 sf 19'6'19'48.4'
PTO 441.6 sf
18'24'18'24'FUS
432.0 sfOPEN TO BELOW8'8'
PTO
64.0 sf
15.5'15.5'15.5'15.5'UDU
240.3 sf
TELESCOPE BUILDING
MOVABLE ROOF
16'22'16'22'S GAR DETACHED FIN
352.0 sf
8'16'8'16'Storage
128.0 sf
Extra Feature Occurrence 1
XFOB Code 120 - FIREPL. G.Abstract Code 1212 - SINGLE FAM.RES-
IMPROVEMTS
Percentage 100 Use Code 1000 - RESIDENTIAL
Neighborhood 1010.2 - MOUNTAIN MEMORIES Building Number 1
SubArea ACTUAL EFFECTIVE HEATED FOOTPRINT
XFOB Units 1
Total 1.00
Value Rate Rate Rate Rate
$4,230 4,230.00
Abstract Summary
Code Classification Actual Value Taxable
Value
Actual
Override
Taxable
Override
1112 SINGLE FAM.RES.-LAND $544,150 $36,460 NA NA
1212 SINGLE FAM.RES-IMPROVEMTS $891,130 $59,710 NA NA
Total $1,435,280 $96,170 NA NA
Property Record Card
Eagle
A#: R032537 P#: 239128404002 As of: 01/17/2025 Page 3 of 3
Email *
mwmiesen@aol.com
MM
/
DD
/
YYYY
Proper ty Information
https://property.eaglecounty.us/assessor/taxweb/search.jsp
1200 Sunset Lane, El Jebel, CO 81623
2391-284-04-002
Application For Onsite Wastewater Treatment
System- New OWTS, Major, and Minor Repairs
INCOMPLETE APPLICATIONS MAY NOT BE ACCEPTED
It is recommended that you apply for an OWTS Permit and Building Permit concurrently. State law requires
the OWTS Permit to be issued prior to the Building Permit. OWTS Permits expire after 120 days without an
active building permit.
Date *
02 26 2025
Physical Address *
Tax Parcel Number:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…1/17
5 Acre
Residential/Single Family
Residential/ Multi Family
Commercial/Industrial
Other:
2
Private Well
Public
Spring
Surface
Lot Size:
Building Type:*
Number of Bedrooms (if residential), or type of use (if commercial)*
Water Supply:*
If Public, Name of Supplier
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…2/17
Ownership and Contact Information
MH552 LLC
303-378-8436
3055 E 5th Ave, Denver, CO 80206
mwmiesen@aol.com
Mark Miesen
303-378-8436
Proper ty Owner *
Owner Phone Number *
Owner Mailing Address
Owner Email Address *
Applicant/Contact Person:*
Applicant Phone Number *
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…3/17
mwmiesen@aol.com
Licensed Systems Contractor
Only Licensed Systems Contractors approved by Eagle County are authorized to perform work on OWTS in
Eagle County. A list of Licensed Systems Contractors is available on the website:
https://cms5.revize.com/revize/eagle/Departments/Environmental%20Health/Documents/2024%20Eagle
%20County%20OWTS%20Professionals%20List.pdf
OWTSPL-000399-2025
970-471-6292
alpha1excavation@gmail.com
Applicant Email Address *
Licensed System Contractor Name/ License #*
Contractor Phone Number *
Contractor Email *
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…4/17
New Installation- $1423 - New Builds of Residence or ADU
Major Repair- $1023 - Full OWTS or Soil Treatment Area (STA) repair or replacement
Minor Repair- $623- Tank Replacement Only
Alterations - Alteration- $623- Bedroom Additions/ADU Additions/Remodels to an existing permitted
OWTS.
Small Repair- $223 - Sewer pipe replacements, pump replacements. Like-for-like replacement of
component in the original Professionally Engineered Design. Does not change the way the system
was designed to function. may include connections to auxiliary structures that do not increase daily
ow rate.
Work that does not require a permit includes : adding risers and/or tank lid replacements, tee
replacement, cleanout replacements, and very minor ve feet or less of straight sewer pipe
replacement where the contractor will submit scope of work and before and after photos to ECPHA
New Installation- $1423 - New Builds of Residence or ADU
The State Law requires that the OWTS permit be issued before the building permit is issued. If
your application is incomplete, it will delay the issuance of your OWTS permit, and the issuance of
the building permit.
Eagle County Board of Health declares that its general policy is to require the use of public sewer systems
where and whenever feasible and to limit the installation of OWTS only to areas that are not feasible for
connection to public sewer. Eagle County will not issue an OWTS permit where the structure to be served is
within the applicable Water and Sanitation District that provides public sewer, unless the public service
provider is not willing to serve the structure, and authorizes the use of an OWTS.
ALL OWTS IN EAGLE COUNTY MUST BE DESIGNED BY A COLORADO REGISTERED
PROFESSIONAL ENGINEER.
https://www.eaglecounty.us/environmentalhealth/septicsystems
OWTS Permit Application is for :
For permit types, go to:
https://docs.google.com/document/d/10KeutJAAb3GKeDvynMjuAiW6aek4-
n3Utn723ulspIs/edit?usp=sharing
*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…5/17
All of the Following Must be Summitted to be Considered a Complete Application:
Electronically (preferred) to environment@eaglecounty.us
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
Professional Engineer Name:*
Engineer Phone Number:*
Engineer Email:*
Satisfactory design with site plan and soil profile results from a Colorado Registered
Professional Engineer will be submitted
*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…6/17
Online (2.5% convenience fee) https://client.pointandpay.net/web/eaglecoenvhealth
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
The State Law requires that the OWTS permit be issued before the building permit is issued.
Incomplete application, designs, will delay the issuance of the OWTS permit, and the issuance of the
building permit/
An OWTS permit must be issued to the Licensed Systems Contractor prior to any installation, repair,
or alteration work is performed. The contracted Licensed Systems Contractor must receive the
permit from ECEH before the OWTS is installed.
Completing this application does not constitute a permit. Eagle County’s review and approval of the
Engineer’s design is required before a permit will be issued.
Major Repair- $1023
Full Replacement of the System or Tank and/or Soil Treatment Area (STA) repair or replacement.
Tank Only Replacement is considered a Minor Repair.
Environmental Health Prioritizes the Review of Repair Applications and Designs
Repair means restoration of functionality and/or treatment by reconstruction, relocation, or replacement of
an on-site wastewater treatment system or any component thereof in order to allow the system to function
as intended.
The $1423 Permit Fee will submitted *
I agree and understand that:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…7/17
Emergency Use Permit May Be Required
Concurrently with the issuance of a repair permit, the ECPHA may issue an emergency use permit
authorizing continued use of a malfunctioning system on an emergency basis for a period not to exceed
the period stated in the repair permit. Such an emergency use permit may be extended, for good cause
shown, in the event repairs may not be completed in the period stated in the repair permit through no fault
of the owner or occupant and only if the owner or occupant will continue to make repairs to the system.
Malfunctioning. The OWTS or component within is not performing as designed, but not failing
Failing. Sewage is leaking on the gound, into the ground untreated. Sewage is backing up into the
house. Euent is ponding, daylighting, or being disposed of without secondary treatment from a
STA.
Other:
ALL OWTS IN EAGLE COUNTY MUST BE DESIGNED BY A COLORADO REGISTERED
PROFESSIONAL ENGINEER.
https://www.eaglecounty.us/environmentalhealth/septicsystems
The system is *
If the system is failing please describe any emergency use steps being taken.
Professional Engineer Name:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…8/17
All of the Following Must be Summitted to be Considered a Complete Application:
Electronically (preferred) to environment@eaglecounty.us
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
Online (2.5% convenience fee) https://client.pointandpay.net/web/eaglecoenvhealth
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
Engineer Phone Number:*
Engineer Email:*
Satisfactory design with site plan and soil profile results from a Colorado Registered
Professional Engineer will be submitted
*
The $1023 Permit Fee will submitted *
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…9/17
The State Law requires that the OWTS permit be issued before the building permit is issued.
Incomplete application, designs, will delay the issuance of the OWTS permit, and the issuance of the
building permit/
An OWTS permit must be issued to the Licensed Systems Contractor prior to any installation, repair,
or alteration work is performed. The contracted Licensed Systems Contractor must receive the
permit from ECEH before the OWTS is installed.
Completing this application does not constitute a permit. Eagle County’s review and approval of the
Engineer’s design is required before a permit will be issued.
Minor Repair- $623- Tank Replacement Only
“Repair” means restoration of functionality and/or treatment by reconstruction, relocation, or replacement
of an on-site wastewater treatment system or any component thereof in order to allow the system to
function as intended.
Please note: repairs or replacement of the Soil Treatment Area are considered a Major Repair, other
components may qualify for a small repair permit
Emergency Use Permit May Be Required
Concurrently with the issuance of a repair permit, the ECPHA may issue an emergency use permit
authorizing continued use of a malfunctioning system on an emergency basis for a period not to exceed
the period stated in the repair permit. Such an emergency use permit may be extended, for good cause
shown, in the event repairs may not be completed in the period stated in the repair permit through no fault
of the owner or occupant and only if the owner or occupant will continue to make repairs to the system.
I agree and understand that:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…10/17
Malfunctioning. The tank or component within is not performing as designed, but not failing
Failing. Sewage is leaking on the ground, into the ground untreated. Sewage is backing up into the
house. Tank is not water-tight.
Other:
ALL OWTS IN EAGLE COUNTY MUST BE DESIGNED BY A COLORADO REGISTERED
PROFESSIONAL ENGINEER.
https://www.eaglecounty.us/environmentalhealth/septicsystems
The tank is *
If the system is failing please describe any emergency use steps being taken.
Professional Engineer Name:*
Engineer Phone Number:*
Engineer Email:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…11/17
All of the Following Must be Summitted to be Considered a Complete Application:
Electronically (preferred) to environment@eaglecounty.us
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
Online (2.5% convenience fee) https://client.pointandpay.net/web/eaglecoenvhealth
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
An OWTS permit must be issued to the Licensed Systems Contractor prior to any installation, repair,
or alteration work is performed. The contracted Licensed Systems Contractor must receive the
permit from ECEH before the OWTS is installed.
Completing this application does not constitute a permit. Eagle County’s review and approval of the
Engineer’s design is required before a permit will be issued.
Alteration- $623
Satisfactory design with site plan from a Colorado Registered Professional Engineer will be
submitted:
*
The $623 Permit Fee will submitted *
I agree and understand that:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…12/17
Bedroom Additions/ADU Additions/Remodels to an existing permitted OWTS.
State Law requires that the OWTS permit be issued before the building permit is issued. If your application
is incomplete, it will delay the issuance of your OWTS permit, and the issuance of the building permit.
No permit yet
ALL OWTS IN EAGLE COUNTY MUST BE DESIGNED BY A COLORADO REGISTERED
PROFESSIONAL ENGINEER.
https://www.eaglecounty.us/environmentalhealth/septicsystems
CBO Septic Consulting
970.309.5259
carla.ostberg@gmail.com
All of the Following Must be Summitted to be Considered a Complete Application:
Existing OWTS Permit Number of Alteration:*
Professional Engineer Name:*
Engineer Phone Number:*
Engineer Email:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…13/17
Electronically (preferred) to environment@eaglecounty.us
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
Online (2.5% convenience fee) https://client.pointandpay.net/web/eaglecoenvhealth
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
The State Law requires that the OWTS permit be issued before the building permit is issued.
Incomplete application, designs, will delay the issuance of the OWTS permit, and the issuance of the
building permit/
An OWTS permit must be issued to the Licensed Systems Contractor prior to any installation, repair,
or alteration work is performed. The contracted Licensed Systems Contractor must receive the
permit from ECEH before the OWTS is installed.
Completing this application does not constitute a permit. Eagle County’s review and approval of the
Engineer’s design is required before a permit will be issued.
Small Repair- $223
Satisfactory evaluation of existing design and proposed changes required with site plan and soil
profile results from a Colorado Registered Professional Engineer will be submitted
*
The $623 Permit Fee will submitted
I agree and understand that:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…14/17
Sewer pipe replacements, pump replacements. Like-for-like replacement of component in the original
Professionally Engineered Design. Does not change the way the system was designed to function. May
include tanks. May include connections to auxiliary structures that do not increase daily ow rate.
All repairs and connections must be completed by a licensed Eagle County OWTS Contractor.
State Law requires that the OWTS permit be issued before the building permit is issued. If your application
is incomplete, it will delay the issuance of your OWTS permit, and the issuance of the building permit.
All of the Following Must be Summitted to be Considered a Complete Application:
Online (2.5% convenience fee) https://client.pointandpay.net/web/eaglecoenvhealth
By mail to Eagle County Environmental Health, PO Box 179, Eagle, CO 81631
Dropped off at Depar tment of Public Health and Environment, Old Court House Building, 550
Broadway in Eagle
Dropped off at Eagle County Oce, 20 Eagle County Drive in El Jebel
Existing OWTS Permit Number:*
Describe the repair work to be done:*
The $223 Permit Fee will submitted *
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…15/17
The State Law requires that the OWTS permit be issued before the building permit is issued.
Incomplete application, designs, will delay the issuance of the OWTS permit, and the issuance of the
building permit. It is best to submit the building permit to Community Development concurrently with
this permit as most building permits have longer review times.
An OWTS permit must be issued to the Licensed Systems Contractor prior to any installation, repair,
or alteration work is performed. The contracted Licensed Systems Contractor must receive the
permit from ECEH before the OWTS is installed.
Completing this application does not constitute a permit. Eagle County’s review and approval of the
work and existing PE design is required before a permit will be issued.
Work that does not require a permit
May Include: adding risers and/or tank lid replacements, tee replacement, cleanout replacements, and very
minor ve feet or less of straight sewer pipe replacement where the contractor will submit scope of work
and before and after photos to ECPHA
All work on a OWTS must be completed by a licensed Eagle County OWTS Contractor.
I agree and understand that:*
Existing OWTS Permit Number: (if not known please state so)*
Describe the repair work to be done:*
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…16/17
Photos of before and after will be submitted to Eagle County Environmental Health
environment@eaglecounty.us
Only an Eagle County Licensed Systems Contractor must perform work on an OWTS.
Any additional work may require a permit and will be submitted for review to Eagle County EH
This form was created inside of Eagle County Government.
I agree and understand that:*
Forms
2/27/25, 10:48 AM Application For Onsite Wastewater Treatment System- New OWTS, Major, and Minor Repairs
https://docs.google.com/forms/d/1JEp6VTO_YlvOuG7DGY78Oi60DTRdCCQM_2Ty7QqUOhE/edit#response=ACYDBNgtd6u4GUqKMPAXNJicSb3…17/17
Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970) 328-8730
Fax: (970) 328-7185
Permit
Permit No. OWTS-031395-2025
Permit Type: OWTS Permit
Work Classification: Alteration
Permit Status: Final
Issue Date: 2/27/2025 Expires: 6/27/2025
On-Site Wastewater
Treatement System
Project Address Parcel Number
1200 SUNSET LN, EL JEBEL AREA,239128404002
Owner Information Address
Mark Miesen 3055 E. 5th Ave
Denver, CO 80206
Phone:
Cell: (303) 378-8436
Email: mwmiesen@AOL.com
Inspections:
For Inspections Call: (970)
328-8755
Engineer Phone Email
CBO Septic Consulting, Carla Ostberg (970) 309-0525 carla.ostberg@gmail.com
Contractor License Number Phone Email
Alpha Excavation LLC alpha1excavation@gmail.
com
(970) 471-6292OWTSPL-000399-20
25
Permitted Construction / Details:
This permit is for the expansion of the STA for the system originally permitted under OWTS-12-09-4108. This
expansion is designed to accommodate the maximum daily flows for a 4 bedroom house. Install the new
components exactly as depicted in the CBO Inc design dated, stamped and signed on January 20th, 2025 by
Kachayla R Cronk, PE.
The OWTS consists of one existing sewer line from the home and the existing 1250 gallon concrete septic tank. A
new Tuf-Tite distribution box equipped with flow equalizers will be installed and accessible at grade. Two new
trenches will be added to each side of the existing trenches and will contain 9 ADS Arc36 chambers each for a total
of 18 new chambers and a grand total of 54.
Contact Eagle County Environmental Health and the design engineer well in advance of requesting inspections prior
to backfilling any component of the OWTS. The design engineer is responsible for conducting all inspections
necessary to certify the installation and assure the functionality of the system. System certification, along with
photos and a record drawing is required to be submitted to and approved by Eagle County Environmental Health
prior to the use of the system or occupancy of the dwelling.
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS
OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Danielle Salinsky
Date
February 27, 2025
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Friday, June 13, 2025 1