Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout505 Sorrel Hills Dr - 193921301014INDIVIDUAL SEWAGE DISPOSAL SYSTEM PERMIT
EAGLE COUNTY ENVIRONMENTAL HEALTH DIVISION
P.O. Box 179 - 500 Broadway • Eagle, CO 81631
Telephone: (970) 328-8755
COPY OF PERMIT MUST BE POSTED AT INSTALLATION SITE. PERMIT NO. 2262-03 BUILDING PERMIT NO. 14795
OWNER: JEFF GILL PHONE: 970-748-1348
MAILING ADDRESS: P.O. BOX 6005, VAIL, CO 81658
APPLICANT: JAMY PATTERSON PHONE: 970-376-7390
SYSTEM LOCATION: 0505 SORREL HILLS DRIVE, EAGLE, CO TAX PARCEL NO. 1939-213-01-014
LICENSED INSTALLER: EWING TRUCKING, BART EWING LICENSE NO. 15-03 PHONE: 970-926-2770
DESIGN ENGINEER: LKP ENGINEERING, LUIZA PETROVSKA PHONE NO. 970-926-9088
INSTALLATION GRANTED FOR THE FOLLOWING: MINIMUM REQUIREMENTS FOR A 5 BEDROOM RESIDENCE
1500 GALLON 3-COMPARTMENT SEPTIC TANK WITH AN AUTO SYPHON DOSING CHAMBER 938 SQUARE FEET OF
ABSORPTION AREA CREDIT VIA A SAND MOUND DESIGN DATED 3/19/03
SPECIAL INSTRUCTIONS: INSTALL AS PER ENGINEER'S DESIGN WITH A CLEAN -OUT BETWEEN THE TANK AND THE
HOUSE, AND AN INSPECTION PORT AT EACH END OF THE MOUND. DOUBLE ENCASE THE EFFLUENT LINE UNDER
THE DRIVEWAY AS NOTED ON THE ENGINEER'S PLAN. BE SURE TO MAINTAIN ALL APPLICABLE SET BACK
REQUIREMENTS AND DO NOT INSTALL IN WET WEATHER. RELOCATE THE CULVERT DISCHARGE POINTS AWAY
FROM THE MOUND SYSTEM. CALL EAGLE COUNTY ENVIRONMENTAL HEALTH AND THE DESIGN ENGINEER FOR
THE FINAL INSPECTION, AND DO NOT BACK FILL ANY PART OF THE INSTALLATION UNTIL IT HAS BEEN
APPROVED. THE BUILDING CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THE SEPTIC SYSTEM
HAS BEEN INSPECTED AND APPROVED
ENVIRONMENTAL HEALTH APPROVAL: VICTOR CROCCO DATE: APRIL 2, 2003
CONDITIONS:
1. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM
REGULATIONS, ADOPTED PURSUANT TO AUTHORITY GRANTED IN 25-10-104, 1973, AS AMENDED.
2. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND BUILDING
REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING
DEPARTMENTS SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN BOTH LEGAL ACTION
AND REVOCATION OF THE PERMIT.
3. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL SYSTEM
TO BE LICENSED.
FINAL APPROVAL OF SYSTEM (TO BE COMPLETED BY INSPECTOR):
NO SYSTEM SHALL BE DEEMED TO BE IN COMPLIANCE WITH THE EAGLE COUNTY INDIVIDUAL SEWAGE
DISPOSAL SYSTEM REGULATIONS UNTIL THE SYSTEM IS APPROVED PRIOR TO COVERING ANY PORTION OF
THE SYSTEM.
INSTALLED ABSORPTION OR DISPERSAL AREA: 1860 SQUARE FEET (VIA 60 STANDARD INFILTRATOR UNITS)
INSTALLED 1500 GALLON 3 COMPARTMENT CONCRETE SEPTIC TANK LOCATED290 DEGREES AND 30 FEET FROM THE
CLEANOUT ON THE SOUTH WEST SIDE OF THE HOUSE.
COMMENTS: THE NEW DESIGN FOR THIS RESIDENCE HAD BEEN APPROVED BUT THE PERMIT HAD NOT BEEN ISSUED
WHEN THE SYSTEM WAS INSTALLED. THE SYSTEM WAS INSTALLED IN THE WINTER WHEN WEATHER CONDITIONS
CAN PROVE DETRIMENTAL TO THE SOIL CONDITION AND FUNCTIONALITY OF THE SYSTEM SEE ENCLOSED LETTER
TO INSTALLER REGARDING THIS ISSUE. THE FINAL INSPECTIONS WERE DONE BY VICTOR CROCCO OF EAGLE
COUNTY ENVIRONMENTAL HEALTH AND THE DESIGN ENGINEER ON 2/10/04 THE ENGINEER'S FINAL CERTIFICATION
AND AS -BUILT DRAWING WERE RECEIVED ON 2/13/04. THIS SYSTEM IS LARGE ENOUGH FOR A 5 BEDROOM
RESIDENCE.
ANY ITEM NOT MEETING REQUIREMENTS WILL BE CORRECTED BEFORE FINAL APPROVAL OF SYSTEM IS MADE. ARRANGE A RE -
INSPECTION WHEN WORK IS COMPLETED.
ENVIRONMENTAL HEALTH APPROVAL i4& 0 C-1� DATE: APRIL 12, 2004
INDIVIDUAL SEWAGE DISPOSAL SYSTEM PERMIT
EAGLE COUNTY ENVIRONMENTAL HEALTH DIVISION
P.O. Box 179 500 Broadway • Eagle, CO 81631
Telephone: (970) 328-8755
COPY OF PERMIT MUST BE POSTED AT INSTALLATION SITE. PERMIT NO. 2262-03 BUILDING PERMIT NO. 14795
OWNER: JEFF GILL PHONE: 970-748-1348
MAILING ADDRESS: P.O. BOX 6005, VAIL, CO 81658
APPLICANT: JAMY PATTERSON PHONE: 970-376-7390
SYSTEM LOCATION: 0505 SORREL HILLS DRIVE, EAGLE, CO TAX PARCEL NO. 1939-213-01-014
LICENSED INSTALLER: EWING TRUCKING, BART EWING LICENSE NO. 15-03 PHONE: 970-926-2770
DESIGN ENGINEER: LKP ENGINEERING, LUIZA PETROVSKA PHONE NO. 970-926-9088
INSTALLATION HEREBY GRANTED FOR THE FOLLOWING: MINIMUM REQUIREMENTS FOR A 5 BEDROOM RESIDENCE
1500 GALLON 3-COMPARTMENT SEPTIC TANK WITH AN AUTO SYPHON DOSING CHAMBER 938 SQUARE FEET OF
ABSORPTION AREA CREDIT, VIA A SAND MOUND DESIGN DATED 3/19/03
SPECIAL INSTRUCTIONS: INSTALL AS PER ENGINEER'S DESIGN WITH A CLEAN -OUT BETWEEN THE TANK AND THE
HOUSE, AND AN INSPECTION PORT AT EACH END OF THE MOUND. DOUBLE ENCASE THE EFFLUENT LINE UNDER THE
DRIVEWAY AS NOTED ON THE ENGINEER'S PLAN. BE SURE TO MAINTAIN ALL APPLICABLE SET BACK REQUIREMENTS
AND DO NOT INSTALL IN WET WEATHER. RELOCATE THE CULVERT DISCHARGE POINTS AWAY FROM THE MOUND
SYSTEM. CALL EAGLE COUNTY ENVIRONMENTAL HEALTH AND THE DESIGN ENGINEER FOR THE FINAL INSPEC-
TION, AND DO NOT BACK FILL ANY PART OF THE INSTALLATION UNTIL IT HAS BEEN APPROVED THE BUILDING
CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THE SEPTIC SYSTEM HAS BEEN INSPECTED AND
APPROVED
ENVIRONMENTAL HEALTH APPROVAL: DATE: fv - 2 I-(• 0,3
CONDITIONS:
1. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM REGULATIONS,
ADOPTED PURSUANT TO AUTHORITY GRANTED IN 25-10-104, 1973, AS AMENDED.
2. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND BUILDING
REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF
THE PERMIT.
3. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL SYSTEM TO BE
LICENSED.
FINAL APPROVAL OF SYSTEM (TO BE COMPLETED BY INSPECTOR):
NO SYSTEM SHALL BE DEEMED TO BE IN COMPLIANCE WITH THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL
SYSTEM REGULATIONS UNTIL THE SYSTEM IS APPROVED PRIOR TO COVERING ANY PORTION OF THE SYSTEM.
INSTALLED ABSORPTION OR DISPERSAL AREA: SQUARE FEET (VIA )
INSTALLED TANK: GALLONS IS LOCATED _ DEGREES AND _ FEET —INCHES
FROM
COMMENTS:
ANY ITEM NOT MEETING REQUIREMENTS WILL BE CORRECTED BEFORE FINAL APPROVAL OF SYSTEM IS MADE. ARRANGE A RE -INSPECTION
WHEN WORK IS COMPLETED.
ENVIRONMENTAL HEALTH APPROVAL DATE:
JXJ•0VH rrWM:t;rtULt WUNI7 tutu t- 1 fbSiff( TO:9926"278 P:1/5
-14 n-_-Lons will NOT 13e Accepted
} (Site' -Ply MUST be attached)
Ism Fermi t
Building Permit #k e
APPLICATION VCR 1=:LV=UAL SEWAGE D7!9p05AL SltsT )PTERMETT
ENVIRONMENTAL HEALTH C1ppir-rE- EAGLE COUNTY
is o• BOX 1J5
pAGLE , CO 81631
Eagle (570) 328--8'755, Fax (9 70) 328-0349 , E� Jebel (970) 7 438 3
at*��*�ricyryr�k��rlr�k�rir��sMieir�t�rir•k*�'*�ta44�lr**yr�yhit�k7k*ii9k�eie�eieir#ter*k�'>k*i��r9tyrir•kir�rtiear*a�cit#�edk�rw�
FEE SCHEPULLP �
TjaS FEE INCLUDES THE ISDS p. Zp_y TT, 51:TE 'EVALUATION (PZ_H0O4&TT X TEST.,SOI�
OBSERVATION) pWFILE OBSEATION) AND rn;AL INSPEICI'ICN
,Ir bITIt]NAL FEES MY BE 'GF'.ARGED YF A REINSPECTION IS NSCESSARY. OR a �
PRE -CONSTRUCTION SITE VSS3:T t�R C=8tMTATION 18 NEEDED
gf,�s CT3:0N FEE $47.00, PRE-C=STRihCTION SITE 'VISYT FEE $85 - DD _
ar MAM ALL . Ag=TTANCE FAYABLE , TO : "EAGLE COUNTr Tnwk S•QRER"
mf3PERTY -OWNM :
MILING ADDRESS
AiPLICA I/CONTACT' sc�N, / f�
SG'�V PHONE: m&r
_ LaasHz SYSTEMS CONTRACTOR: PHONE: !$
COMPANY /DBA : u ADDRESS;
#ir�k�t#ar-rr*dlydr*�*at,rrr�rat _ �tik9k**at9e*ar9f �•k-1e*��rk�k#*�k-,tyryryta�ye*�IrJ�ricah*ale-AA•rE��ilr�•kftltir7kxr�lr�*ic
APE 2T APPLICATIDN is FOR: X NNK INSTALLA.T14N ( } ALTERATION { ? REPAIR
LOCATION OF PROPOSED INDIVIDUAL SEWAGE DISPOSAL SYSTEM:
Legal Descriptic:
z�
Tax Parcel Number. � % ��' � Lot Size;
/ J_ .ram
physical Address:
BUILDING TYPE: (Check applicable category) Number of Zdroortu3 .�
Residential./Single Family
( Residential/Multi.-Family* Type
�r o� Bedrooms
Com>nexci al / Industri.al
*These systems require design by a Reglstei�ed professional Engineer
TYPE OF TER SUPPLY: {Check
well C ) Spring
r ) Public Name of SuF,
AP-PLICANT SI--GIM
+ ,CLTl%;T PAID:
applicable category)
( ) _Surface
Date. r f, P
_ RECE1PVrAo
C CT CASHIER :i�
�11
._.-..-. r..-.,-.� -r• •� .. _ r,�.... rr _ rrr�• r i+�� n. rr.� r. n i � erne -ri i RG,�,- _ �
DEPARTMENT OF
ENVIRONMENTAL HEALTH
(970) 328-8755
FAX: (970) 328=8788
TOLL FREE:800-225-6136
www.eaglecounty.us
April 12, 2004
Jeff and Amy Gill
P.O. Box 6005
Vail, CO 81658
EAGLE COUNTY
RAYMOND P. MERRY, REHS
Director
RE: Final of ISDS Permit #2262-03, Tax Parcel #1939-213-01-014. Property location:
0505 Sorrel Hills Drive, Eagle, CO.
Dear Mr. and Mrs. Gill:
This letter is to inform you that the above referenced ISDS Permit has been inspected and
finalized. Enclosed is a copy to retain for your records. This permit does not indicate
compliance with any other Eagle County requirements. Also enclosed is a brochure regarding
the care of your septic system.
Be aware that later changes to your building may require appropriate alterations of your septic
system.
If you have any questions regarding this permit, please contact the Eagle County Environmental
Health Division at (970) 328-8755.
Sincerely,
f it
Janet Kohl YYY
Eagle County Environmental Health Department
ENCL: Educational Brochure
Final ISDS Permit
cc: files, April 2004 Chrono file
500 Broadway, P.O. Box 179, Eagle, Colorado 81631-0179
DEPARTMENT OF
ENVIRONMENTAL HEALTH
(970) 328-8755
FAX: (970) 328-8788
TOLL FREE:800-225-6136
www.eagle-county.com
DATE: June 23, 2003
TO: Ewing Trucking
EAGLE COUNTY
FROM: Eagle County Department of Environmental Health
RAYMOND P. MERRY, REHS
Director
RE: Individual Sewage Disposal System Permit #2262-03,
Tax Parcel # 1939-213-01-014, Property Location: 0505 Sorrel Hills Dr., Eagle,
CO., Gill residence.
Enclosed is your ISDS Permit #2262-03, and a copy of the engineer's design for this system. The
permit is valid for 120 days or for the duration of your current building permit for this property.
The enclosed copy of the permit must be posted at the installation site. Any changes in plans or
specifications invalidate the permit unless otherwise approved. Please note any special
requirements that may have been added to the design by this Department.
Systems that are designed by a Registered Professional Engineer must be certified by the
engineer indicating that the system was installed as specified. Eagle County Environmental
Health must also view the installation prior to back filling. Please call well in advance for
your final inspection. Your TCO will not be issued until our office receives this certification
from the engineer and views the installation.
Please note that our ISDS Permit specifications are typically minimum requirements only and
should be brought to the property owner's attention in case they may wish to install a system
capable of handling larger wastewater flows.
This permit does not indicate conformance with any other Eagle County requirements.
Please notify this office if you have not been contracted to perform this installation.
If you have any questions, please feel free to contact us at (970) 328-8755.
cc: ISDS file # 2279-03
LKP Engineering, Luiza Petrovska
Chrono file June 2003
OLD COURTHOUSE BUILDING, 551 Broadway, P.O. Box 179, Eagle, Colorado 81631-0179
DEPARTMENT OF
ENVIRONMENTAL HEALTH
(970) 3.28-8755
FAX: (970) 328-8788
TOLL FREE:800-225-6136
www.eagle-county.com
February 4, 2004
Bart Ewing
Ewing Trucking
P.O. Box 2303
Edwards, CO 81632
Dear Mr. Ewing,
EAGLE COUNTY
RAYMOND P. MERRY, REHS
Director
The purpose of this letter is to voice concerns about the septic system that you are installing for
the Gill Residence (ISDS Permit # 2262-03 ). The concerns that we have are relative to the
timing associated with soils evaluation, installation and inspection.
According to our records, the application submitted to install the septic system on April 1, 2003
was based on adverse soil conditions. As such, an engineered mound was permitted for
installation on April 1, 2003. Surprisingly to us; a revised conventional system design was
submitted on January 21, 2004 outside the frame that we perform these services see [ Sec 4.01.06
of the Eagle County Land use Regulations]. This time- frame is codified because working with
frozen soil during the winter months can result in significant changes in soil characteristics,
which may affect the long- term functional ability of this system. Furthermore, the conventional
septic system design submitted on January 22, 2004 has not yet been permitted as per your
assertion to Eagle County Environmental personnel that you would install this system in the
Spring. ,
It concerns this department that you have arranged for inspections, leading us to believe that you
have installed this system during unfavorable weather conditions, outside our time frame and
without a permit.
As you are aware, the design engineer is responsible for certifying the system for which a permit
to install will be forthcoming. Please contact me when you have the permit in -hand to document
component locations. I can be reached at (970) 328-8758.
Sincerely'
Victor D. Crocco
Environmental Health Specialist
Cc; Jeff Gill Owner
Cc; Jamie Patterson General Contractor
Cc; L.K.P. Engineering
OLD COURTHOUSE BUILDING, 551 Broadway, P.O. Box 179, Eagle, Colorado 81631-0179
rJzJ LJJZuriLF 13.U0 7fCJ7L07CJ07 LPV- CI`It7IIVGr_MIIgU IlIqu r'4ur_ UI
FAX T-R-ANSMISSION.1,
ll, ENGINEEMG, !NC.
P.O. Box 2837
Edwards, 00 81632
(970)926-9088
Fax: (970) 926-8089
E-mail: ften centurytel.net
To: Victor Date: February 13, 2004
Fax: 329-8788 Pages: 3 including this cover sheet.
Phone: 328-8757
From: l_.u.iza. Petrovska, PE Project: 03010
Subject: Septic as -built - Gill Residence
COMMENTS:
I DS Permit No. 2262-03
Post -it"" Fax Note 7671
Date/p � -
#Of
TO i G�
From
Co./Dept.
Co.
Phone # y
q 70 :_ 4S3— � 3 3Gl
Phone # s.
yak- k�7�sS
Fax #
—%� G�
Fax# f70-s�7�- ��.7�
UGf 1J/ LUU'-F Lo. UO 71U7GODUO7
LK P Engineering, Inc.
CIV UGF-OTECHNICAL
February 13, 2004
L-N -LINU
Jeff & Amy Gill RE: Inspection of Septic System Installation
P.D. Box 6005 Let 7, Sorrel Hill Subdivision
Vail, CO 81658 0505 Sorrel Hills Drive
Eagle County, Colorado
Project No. 03010 - ISDS Permit No. 2262-03
Dear Jeff and Amy.
r AUM UL
.At your request, on. ,August 19, November 6, and 20, 2003, and January 15, February 6,
10, and 12, 2004, we visited the construction site on Lot 7, Sorrel Hill Subdivision, 0505 Sorrel
Hills Drive, Eagle County,. Colorado. The purpose of our site visits was to inspect the installation
of the septic system.
They installed the system in overall compliance with the revised septic system, design,
Drawing No. 03010SD-2.DWG, last dated January 19, 2004, as shown on the attached as -built
sketch. They iwtalled a.1500-gallon, three compartments, a precast, concrete, septic tank.. Two
building, sewer limes were connected to the septic tank. Cleanouts were installed onboth lines
between, the house and the septic tank. The effluent line from the septic tank to the leaebfxeld was
a 4-inch diameter, SDR35 and it had cleanouts at i00-foot intervals.
Sixty, Standard Infiltrator Chambers were installed in nine trenches. The first two
trenches had sit infiltrators each, the next three trenches had seven infiltrators each, the sixth
trench had eight, the seventh had seven, and the last two trenches had sax infiltrators each. The
infiltrators were corrected withserial distribution. In the first and last infUtrator of each trench,
inspection ports were installed. Horizontal distance between the trenches was at least six feet.
If you have any questions, please do not hesitate to call.
Sincerely,i9
LKF Engineering, I c°m�aaA°o,au
Lu1Za Petx13vska, -a °
� mm
President•. ,
Enclosure 9R -
cc: W. Victor Crocco, Eagle County Environmental Health Department, 328-8788
C AWP10-LKP10301006i.wpd
P-O. Box 2837, Edwadr4 CO 81%32, (970) 926-9088 Tel, (970) 92s-9089 Fax
rJ41 _L'jj Zcjrjt LJ. UO DfUDZLODUOD L-mrGI417114GGfC11447 -Lilf-, rlmurm rio
PROXEDT DEMWn=* KIN
LOT 7. SORRELL HILLS 03010
LKP Engineering, InC- A S- BUX 7 0505 somqm "" MVE me PEW alf
CI TUGEOTECHNICAj- SKETICH EAGLE COUNTY _00MADO AAM 2262-0
JW AND AMY Ou 2-12-04
..... .... ..
...... ....
.. . .... ... ...
...... ..... ....
.... ... ......
..... .....
.... ......
... ..... .... .... .......
......... ......
---- ... ...
.. .... .... . .. .... 'VA,
A.. . . ...... .....
.. ... ...... . ...... .... ,-,--�,-,:
...... ......
......... . . .......
. .. ... . .......... .
.... ..... ... .......
•
•
... ........
V..
..........
... .........
.. .... ..... ....
r. .. ....... ..
7777-777—
. .. ... .....
. . . ......
VN
.. ........ ....... ..
... ... . .. ........... .....
.. . . ...... ...... . .
. .... ...... .....
............. ...... .
.. . ...... ..
V
. .. .. .. . ....
N
V
t
A
/*
....... . . . ..... ....
. ....... ..
%
PA Rox 2837, Edwards, CO 81632� (0701 0?.A-9tIRR Tel, (970) 926-9089 Fax
r-r-M 4 -2_'nMMA r-MT M'-k. 4 AMM Tr-%. 17i%ef 177 e'rII 1Lrr4,' 171.I1 I "17eNI -rLI
ISDS Permit # o c (� �r,"t Inspector Date
ISDS Final Inspection
+%t 'Completeness Form
Tank is 5 ° ° gal. Tank Material
Tank is located ft. and degrees from
_ Tank is located ft. and 2A9 degrees from O v'_ -v-'
y
Tank set level. 0 Tank lids within 8" of finished grade.
Size of field ft2 units lineal ft. Technology
Cleanout is installed in between tank and house(+ 1/100ft).
0 "T" that goes down 14 inches in the inlet and outlet of the tank. Effluent filter on outlet- Yes or No
V, Inlet and outlet is sealed with tar tape, rubber gasket etc.
j Cd CL
`Tank has two compartmeets with the larger compartment closest to the house.
Measure distanceand relative direction to field.
Depth of field ft.
Soil interface raked.
Inspection portals at the end of each trench.
Proper distance to setbacks.
Chambers properly installed as per manufacturers specifications. (Chambers latched, end plates properly
installed, rocks removed from trenches, etc.)
Splash plate(s) installed at least in first trench inlet.
Type of pipe used for building sewer lin leach field_
Other
Inspection meets requirements.
Copy form to installer's file if recommendations for improvement were suggested.
ACTION TAKEN:
Setbacks
Well Potable House Property Lake Dry Tank Drain Field
Water Lines line Stream Gulch
Field
100
25
20
10
50
25
10
Tank
50
10
5
10
50
10
*
10
r
Engineering, Inc.
CIVIL/GEOTECHNICAL
s
{
� K y y trS
SOIL AND FOUNDATION INVESTIGATION
FOR
PROPOSED RESIDENCE
PARCEL 7, SORREL HILLS
EAGLE COUNTY, COLORADO
PROJECT NO. 3010
JANUARY 30, 2003
JEFF & AMY GILL
P.O. BOX 675
VAIL, CO 81658
P.O. Box 2837, Edwards, CO 81632, (970) 926-9088 Tel, (970) 926-9089 Fax
F=
TABLE OF CONTENTS
EXECUTIVE SUMMARY............................................................ 2
SCOPE OF STUDY.................................................................. 2
SITE DESCRIPTION................................................................ 2
PROPOSED CONSTRUCTION........................................................ 2
FIELD INVESTIGATION............................................................. 3
SUBSURFACE SOIL AND GROUNDWATER CONDITION ................................ 3
FOUNDATION RECOMMENDATIONS................................................ 3
EXCAVATION DIFFICULTIES........................................................ 4
SLABCONSTRUCTION ............................................................. 4
RETAINING WALLS................................................................ 5
UNDERDRAIN SYSTEM............................................................. 5
SITE GRADING AND DRAINAGE ..................................................... 6
LAWNIRRIGATION...........................................`...................... 6
LIMITATION...................................................................... 6
FIGURES
LOCATION SKETCH ..........................................DRAWING NO. 1
SUBSURFACE EXPLORATION LOGS .......................... FIGURE NO' S 1 &2
PERIMETER DRAIN .......................................... FIGURE NO.3
LKP Engineering, Inc.
EXECUTIVE SUMMARY
The proposed residence should be supported with
conventional type spread footings, designed for an
allowable soil bearing pressure of 3000 psf. They should
construct the footings of the entire foundation on the
undisturbed, firm bedrock. See Foundation
Recommendations.
SCOPE OF STUDY
This report presents the results of a subsurface Soil and Foundation Investigation for a
proposed residence to be constructed on Parcel 7, Sorrel Hills, Eagle County, Colorado. The
purpose of the subsurface soil and foundation investigation was to determine the engineering
characteristics of the foundation soil and to provide recommendations for the foundation design,
grading, and drainage.
SITE DESCRIPTION
The building site has moderate to steep topography. Vegetation on the lot consisted of
grass, junipers and sagebrush. Drainage is to the north and west. The building site is vacant.
PROPOSED CONSTRUCTION
We have assumed that the proposed residence will consist of a two-story, wood frame
construction, with a walkout basement, on a concrete foundation. Loads are anticipated to be
light, typical of residential construction.
If the finalized plans differ significantly from the above understanding, they should notify
LKP Engineering, Inc.
us to reevaluate the recommendations of this report.
FIELD INVESTIGATION
The field investigation conducted on January 22, 2003, consisted of logging and
sampling two test pits. The test pits' locations are shown on Drawing No. 1. Excavation of the
test pits was done prior to our site visit. We show the soil profiles of the test pits on the
Subsurface Exploration Logs, Figure No's one and two. Soil samples for laboratory soil analysis
and observation were taken at selected intervals.
SUBSURFACE SOIL AND GROUNDWATER CONDITION
The soil profiles encountered in the test pits were relatively uniform. Test Pit No. 1 had
. one foot of topsoil over two feet of weathered bedrock over 4 feet of sandstone and shale
bedrock. Refusal was encountered at 7 feet. Test Pit No. 2 had one foot of topsoil over 3 feet of
weathered bedrock over 4 feet of shale bedrock. Ground water was not encountered in either test
pit.
FOUNDATION RECOMMENDATIONS
The proposed residence should be supported with conventional type spread footings,
designed for a maximum allowable soil bearing pressure of 3000 psf. The footings, for the entire
foundation, should be placed on the undisturbed, firm bedrock.
We recommend minimum width of 16 inches for the continuous footings and 2 feet for
the isolated footing pads. Continuous foundation walls should be reinforced top and bottom to
span an unsupported length of at least 10 feet.
A minimum of 48 inches of backfill cover is recommended for frost protection of the
footing subsoils. The undersigned engineer should observe the foundation excavation to verify
that the soil conditions are uniform throughout the foundation excavation.
LKP Engineering, Inc.
EM
0
The foundation excavation should be free from excavation spoils, frost, organics and
standing water. The on -site soil free from topsoil, organics, and rock fragments smaller than six
inches, is suitable backfill material. Imported fill material, approved by the undersigned
engineer, might be necessary for the foundation backfill. Voids left in the excavation, due to rock
removal, should be filled with lean concrete: Footings should be constructed on a level surface.
EXCAVATION DIFFICULTIES
From the condition of the bedrock observed in the test pits, we assume that the
excavation can be done with large excavation machinery. Excavation of narrow utility trenches
might be more difficult.
SLAB CONSTRUCTION
The natural on -site soils, exclusive of topsoil, organics, are suitable to support lightly
loaded slab -on -grade construction. The subgrade for the slab -on -grade construction,should be
proof compacted to detect and remove soft spots. They should backfill overexcavated soft spots
and other underslab fill with the on -site soil, free from topsoil and organics, or other suitable
material, compacted to a minimum of 95 percent of the maximum standard Proctor density
(ASTM D-698). Suitable material should be free from topsoil, organics and rock fragments
greater than 3 inches.
The concrete slab should be constructed over a 4-inch layer of clean gravel consisting of -
3/4 inch gravel with at least 50% retained on the No. 4 sieve and less than 3 percent passing the
No. 200 sieve.
They should reinforce the concrete slab -on -grade and score control joints according to the
American Concrete Institute requirements and per the recommendations of the designer to reduce
damage due to shrinkage. The concrete slab should be separated from the foundation walls and
columns with expansion joints to allow for independent movement without causing damage.
LKP Engineering, Inc.
Q:
RETAINING WALLS
They should design foundation walls retaining earth and retaining structures that are
laterally supported to resist an equivalent fluid density of 60 pcf for an "at -rest" condition.
Laterally unrestrained structures retaining the on -site earth should be designed to resist an
equivalent fluid density of 40 pcf for the "active" case.
The above design recommendations assume drained backfill conditions and a horizontal
backfill surface. Surcharge loading due to adjacent structures, weight of temporary stored
construction materials and equipment, inclined backfill and hydrostatic pressure due to
undrained backfill should be incorporated in the design. They should try to prevent the buildup
of hydrostatic pressure behind the retaining wall.
UNDERDRAIN SYSTEM
Perched water condition is very common in foundations constructed on bedrock. To
reduce the risk of surface water infiltrating the foundation subsoil (and the development of a
perched water condition) installation of a foundation perimeter drain is recommended. The
foundation perimeter drain should consist of a 4-inch diameter perforated pipe sloped to a
suitable gravity outlet, or to a sump pump location. The drain should slope at 1/4 inch per foot if
flexible or at 1/8 of an inch if rigid pipe is used. The bottom of the trench adjacent to the footing
should be lined with a polyethylene moisture barrier glued to the foundation wall. The drain pipe
should be placed over the moisture barrier and covered with a minimum of 6 inches of -3/4 inch
free -draining granular material. Geotextile (Mirafi 140N or equivalent) should be used to cover
the free -draining gravel to prevent siltation and clogging of the drain. The backfill above the
drain should be granular material to within 2 feet of the ground surface to prevent a buildup of
hydrostatic pressure. The top one foot of the backfill material should consist of a relatively
impervious fill. The backfill should slope away from the building.
LKP Engineering, Inc.
rel
SITE GRADING AND DRAINAGE
A site plan was not available for review at this time. The following recommendations are
general in nature. The site surrounding the building structure should slope away from the
building in all directions. A minimum of 12 inches in the first 10 feet is recommended in
unpaved areas, and three inches in the first 10 feet in paved areas. The top of the granular
foundation backfill should be covered with a minimum of I foot of relatively impervious fill to
reduce the potential of surface water infiltrating the foundation subsoils.
Surface water naturally draining toward the proposed building site or permanent cuts,
should be diverted around and away from it by means of drainage swales or other approved
methods. The roof drains and downspouts should extend and discharge beyond the limits of the
backfill. Exterior backfill should be compacted at or near the optimum moisture content to at
least 95% of the maximum standard Proctor density under pavement, sidewalk and patio areas
and to at least 90% of the maximum standard Proctor density under landscaped areas.
Mechanical methods of compaction should be used. Do not puddle the foundation excavation.
LAWN IRRIGATION
It is not recommended to introduce excess water to the foundation soils by installing ,
sprinkler systems next to the building. The installation of the sprinkler heads should insure that
the spray from the heads will not fall within 10 feet of foundation walls, porches or patio dabs.
Lawn irrigation must be controlled.
LIMITATION
This report has been prepared according to locally accepted Professional Geotechnical
Engineering standards for similar methods of testing and soil conditions at this time. There is no
other warranty either expressed or implied.
The findings and recommendations of this report are based on field exploration,
LKP Engineering, Inc.
laboratory testing of samples obtained at the specific locations shown on the Location Sketch,
Drawing No.1 and on assumptions stated in the report. Soil conditions at other locations may
vary, which may not become evident until the foundation excavation is completed. If soil or
water conditions seem different from those described in this report we should be contacted
immediately to reevaluate the recommendations of this report.
This report has been prepared for the exclusive use of Jeff & Amy Gill, for the specific
application to the proposed residence on Parcel 7, Sorrel Hills, Eagle County, Colorado.
Sincerely,
LKP ENGINEERING, INC.
4
A-9
MRE�j'°r�;
/ r ET&
Luiza PetrovskaP 9526�
e
President 16', /-30• 0-3
RM
CAVVT10-LKP\03010ROCK.RPT.wpd
7
LKP Engineering, Inc.
r
DATE OBSERVED: January 22, 2003 Test Pit # 1
ELEVATION:
DEPTH
FEET
S
Y
M
B
0
L
S
A
M
P
IL
E
DESCRIP7701V OF MATERIAL
AND SAMPLE LOCA77ON
LABOARTORY
TEST RESULTS
REMARKS
5
- 10
- 15
- 20
Topsoil
--
Weathered Bedrock
Sandstone and Shale Bedrock
Refusal at 7 feet
No Ground Water
Encountered
LEGEND:
❑ — 2—inch O.D. California Liner Sample
■ — Bulk Sample
DD — Natural Dry Density (pcf)
MC — Natural Moisture Content (X)
—200 — Percent Passing No. 200 Sieve
LL — Liquid Limit
PI — Plasticity Index
GW — Ground water
LKP ENGINEERING, INC.
SUBSURFACE EXPLORATION LOG
PRaECT Na:
03010
Raw Na:
N
1-.
DATE OBSERVED: January 22, 2003 Test Pit # 2
ELEVATION:
DEPTH
FEET
S
Y
M
B
O
L
S
A
M
P
L
E
DESCRIP77ON OF MATERIAL
AND SAMPLE LOCA77ON
LABOARTORY
TEST RESULTS
REMARKS
s
—
10
15
20
Topsoil
--
Weathered Bedrock
Shale Bedrock
Bottom of Test Pit at 8 feet
No Ground Water
Encountered
LEGEND:
❑ — 2—inch O.D. California Liner Sample
■ — Bulk Sample
DO — Natural Dry Density (pcf)
Mc — Natural Moisture Content (Z)
—200 — Percent Passing No. 200 Sieve
LL — Liquid Limit
P/ - Plasticity Index
GW — Ground water
I" ENGINEERING, INC.
SUBSURFACE EXPLORATION LOG
PMWCT HQ
03010
RaW Na:2
1
P --.
SLOPE AWA Y FROM BUILDING
A
COVER BACKF/LL WITH ONE
FOOT OF RELA77VEL Y
' '
IMPERVIOUS SOIL
.s D• . e
ry
-'i`' '�� rt- `:� —
fit"
•D•�
e
.r: .-..i
`+�� of • •/
' Q 'o D
Z
� c:.
• a
�j w �'�
Zj
GRANULA FILL
:�' _ ��
aD-t.a ',�.:._
•tip,
_.J.
^., �`
FILTER FABRIC
(M/RAF/ 140N OR
• e> '. . s
a a •-�+..1• �•�,\'• •.Q.• Ly EQUIVALENT)
o FOOTING
_ 4a : •'- �': Q4
PLAS77C LINER, GLUED
TO THE FOUNDA770N WALL,
MM/G$OTECHNICAL
Engineering, Inc.
P.O. Box 1452 Avon, Co 81620
tel (970) 926-9088 fax (970) 926-9089
COARSE GRAVEL, 314 INCH DIAM.
W17H LESS THAN 5X FINES
4—INCH DIAMETER PERFORATED
PIPE SLOPED TO A SUITABLE OU7ZE7'
AT 1/4- PER FOOT FOR FLEXIBLE AND
A T 1/8" PER FOOT FOR R16YD PIPE
WN410 UivyXi
PARCEL 7, SORREL HILLS
EAGLE COUNTY. COLORADO
3
ISDS PERMIT �J--6,_3
PERCOLATION TEST
EAGLE COUNTY ENVIRONMENTAL HEATLH
OWNER: e
-PHSYSICAL ADDRESS: Pra7 S a ',r e e, ` \A i V S
LEGAL DESCRIPTION:
MAILING ADDRESS:
TYPE OF DWELLING: NUMBER OF BEDROOMS: Ll o r
�Y(ear&�Yk�IYe�Yfe�Wc31k,i11e�Yk,,Ik,W�,iIE .,Ik �1...,r..W..,4..rr. .,r..ui..L...y.. _,�..-,,...,�..-,�--,:.--.r- ......... ... ... ... ... .�- -•- --- - - —
TEST HOLES PRE-SOAKED: YES NO T
SOIL
TIME WATER DEPTH INCHES OF FALL RATE PROFILE
�1
mmmm
mmmmmmmm
i m
mmmmmmmmm
mmmmmmmmm
mmmmmmmmonom
mmmmmmmmmm
mmmmmmmmmr6o=
mmmmmmmmm
I
mmmmmmmmmi-
11METO DRUP LAST INCH: PERC RATE:
MINIMUM LEACH FIELD SIZE: MINIMUM SEPTIC TANK SIZE:
3 - 3-- 6.3
ENVIRONMENTAL HEALTH SPECIALIST DATE
leuutAki
0y
wii6
S t, . l e,
14A L�
� e c rock
ISDS Permit # _ 1 !v 1- O 3 Inspector Date Z • / 0 - o c{
ISDS Final Inspection
' Completeness Form
Tank is gal. Tank Material r e • C A s Ca,v r-,r e e w t •din s , )jko to rQ A,
N
Tank is located :3. 0 ft. and -2 b degrees from
Tank is located ft. and degrees from
p! A Tank set level. Tank lids within 8" of finished grade.
Y
Size of field 93 4 ft2 G Q units - 3 7.5 lineal ft. Technology "s { d Qr , I t 4^4 § or.
v/ Cleanout is installed in between tank and house(+ 1/100ft): c+i e q vo s .,bei�'w i�do s « 4, 4
N A "T" that goes down 14 inches in the inlet and outlet of the tank: Effluent filter on, outlet- Yes or No
a
Inlet and outlet is sealed with tar tape, rubber gasket etc.
� _
'�T Tank has two compartments with a larger compartment closest to the house.
Measure distance and relative direction to' field. (PI 0 �- �► N �' ° °" "
Depth of field ft. -- s ow
Soil interface raked.
Inspection portals at the end of each trench.
✓ Proper distance to setbacks. % o o' i -'wk
CfiVbers properly installed as per manufacturers specifications. (Chambers latched, end plates properl
installek rocks removed from trenches, etc.)
Splash plate(s) installed at least in first trench`iiilet.
Type, of pipe used for building sewer., line S 3S leach
Other
inspection meets requirements. -
S"�Q„ �.gsh+c+t r ��av, o,r ,vtwSa4tgN o, i o; q ��e�nckeS �.orit-�
a
Copy form to installer's file if recommendations for improvement were suggested.
ACTION TAKEN: £ 4 , 4 c,, £ N 14 < < 14' Vr < d £ Y Q r , , „'S
40 r4r%O✓t 1Gr,;tSt tawny '��p�AarScx<h� ^14hb, 11Q<F Sf.
Setbacks
Well Potable House Property Lake Dry Tank Drain Field
Water Lines line Stream Gulch
i ✓ .- � i
Field 100 25 20 10 50 25 10
✓ / ✓
Tank 50 10 5 10 50 10 * 10 ,_
EAGLE COUNTY ENVIRONMENTAL HEALTH FINAL AS -BUILT SKETCH
0505 Soteco i111j
ISDS PERMIT # Z `z . o,3 DATE i -1 d • 0 LOCATION ADDRESS
■■■■■■■■■■■®■■■■■■■■■■■■■■■■■■l
■IEEE■■■■■■M■■■■■■■■■■■■■■■■■■1
■■■IEEE■■■■■■■■■■■■■■■■■■■■■■■1
■E■
■■■■■■■■■■■■■■■■■■■■■■■■■■1
■■■
■mmom
1mmono■■■■■■■■1
■■
Eiasoo■MM■
■■■■■■■■El
■N!�
M�
E��
i�■
■■■■SEEM
■ONE
■■�NI�
■®■��■
■■■■■■■■
■E1011C1
Il11111,
F
jog
■■■■■■■■
■SE
S■■■■MI1
■1121lolijiLli
NOMINEES
■■■■■■■■■i
MENEM
ml
■■■■■■■■■M■■�■■■■■■■■■■■■■OEM■■
■E■EMI■■■EEMEM■
ONE
■■ME■■■■■■■MI
■■■■■■■■■■■mN■■■■■■■MM■■■M■NM■■
■MM■■M■M■MMEM■
MMMENM
O■■■■■■MOM
■■MM■MMMMMM■►NONMENE
■■■■■■■MO■
■■■■■■■■■■■■�
ONEMMMM
M■omm■■MM■
■■■■■■■■■■■■m■■■■■■■
MMMOMM■M■
■■■■M■■■■■■■\I■■■■MM
and«110
■MMMM■MMMMMMEAMOMMME
ON
A\\SMS■
■■■■■■■■■■■■■m■■■med
■■i
i�\!■��MM■
■■■■■■■■■■■■■ommo►i■
\
■■■
MOM■■
■■■■■■■■■■■■■MENOMME►ME
■o
NO
■■■■■■■■■■■■■■oNsEMM
M■
EM�E■■
■■■■■■■■■■■■■■®■■■■■
►■■■IM■N■■
■■■■■■■■■■■■■■■■■■■■
M►
ME►N■
■■M■MM■■■■■EM■■■■MMM
ME
MmNN■
SEE■EN■■NEEMO■OMEM■■
■OBI
ME
®MI
■■■■■■■■■■■■■■■■■■■■
M■■��ESEN■
-
EMEMEMENEEMENEEMENNE
NONE
■■■■■■■■■■■■■■■■■■■■
■■NN■NNENM
■E■■■■■■■■■E■■■■■■E■
■NEMEMEEN■
■EMEME■■■■EEN■ME■EE■
ME
on
■■■■■■■■■■■■■■■■■■■
ME
N■■M■N■
■E■■■■■■■■■■■■■■■■■M
ME■EE■■
■■■■■■■■■■■■IEEE■■■■
■■NONE
N■■■
2262-03 Gill LF 11/6/03
Lot 7, Blk 1, Sorrel Hills @Castle Peak
0505 Sorrel Hills Dr., Eagle
Bul-IdIna Sewer #2 & A
2262-03
Gill LF
11/6/03
Lot7 Blk 1
Sorrel el HMIs @
Castle Peak
0505
Sorrel Hills
Dr., Eagle
. �.�x .+tic" � ,-.� =< `:-. • � �
IN
c
{
Y
40r-
Ah
r
-3-GlIt"t R "flB/03
2262 0
Lot 7, Bl.k,,'I�l#[S.orre-.1-Hiiislli@',- Castle P
1, N,
Nt A
t;k
IOL
6,
0 > 3:
ii�
TO, W) Ii
�'- . r
Wool
AW
�2262-03 Gill LF 11/6/03
,.Lot 7, Blk 1, Sorrel Hills @Castle Peak
,tM5 Sorrel Hills Dr., Eagle
IN
2262-03_Gill ..... �l �li�'�''��3
Lot 7, Blk; 1, .-Sorref-Hilldl astle
R" IA
o2-03 G-II I L F 11 /Fi/C
�16011
d r.
r owl
oz*� ti
r _low
a 8uilding sewer #2
9
AWK
6\1 *11"
. �.
81618
. r...j
Ar
ICN
LA-1
11611
.. 'S:1tK•: �Lr
2262-03 Gi 11/6/03
Lot 7 I,k 1, Sorrel Hills @ Castle Peak
5 gib I Hills Dr., Eagle
Cleanout #2
14
• .,.. `ice ,�_
4 10 L.
IA
WL
\� �� !`� �'i 1+. �' fir+. _ �• .
_�^ . _� �'� � <` +fig►
2262-03 Gi 11/6I03
�` Lot 7 1k 1, Sorrel Hills @Castle Peak
s�'� �Wat 05�-br- I Hills Dr., Eagle
It
I
N.
4N
Je.
It "
Ab.
I
At
400
411
i
'C )i 0
CD CD
CDC
t CD
CD
Y •
ti
t
s t •
r
-4
""...
C
V
-,:
�'''""�
V
1.✓
D
- h
0
V
Q.
.....,.
N
�
=
-.
N
.
�
-
N
C�
m
c�
ca
2262-03 Tax #1939-213-01-014
JOB NAME_ Lot #7, Blk 1, GILL
Sorrel Hills @ Castle Peak
f1Sl15 CnrrPl Ni 1 1 c Dr-- Fagle
JOB NO. )) " M 0��
#401nR LACOTmN
BILL TO
DATERTED .ST
1
DATE COMPLETED
DATE BILLED
tl r
-) G
A)
0,
LI
f
j y'y
fil
O
t
n�a
o w
IjKt P LI -1 Cal
• 0 tJ
Cx ' Q 6
N 1I
/t-� j' Z
1� � h a `a.�t��
5
./�i
,,gyp
V /A* rc
OD
,,
f„�cL
JOB COST SUMMARY
�� dokin
A)
t (.�
TOTAL SELLING PRICE
., P C©JM Q lr. _,,
.
N
TOTAL MATERIAL
' 1
TOTAL LABOR
• ,�
LW
INSURANCE
N a V cil vc
SALES TAX
0AQLXL-(f)�, e J\Gca;u-Ul,
MISC. COSTS
11 r
TOTAL JOB COST
_3 rGL,
Z
GROSS PROFIT
r am%
4±
LESS OVERHEAD COSTS
% OF SELLING PRICE
Q
p U
NET PROFIT
JOB FOLDER Product 278 Printed In U.S.A.
JOB FOLDE
1 N CA L -c , 1 f C,i
grSc vcj -Tt-I $
rJ ��Ulc � VA c' cJ
✓� ^�..{ �(U}{,Jp.�S /�'�L° l O(
�� _C`J k(-.Y t�- �� � v. \,�JJf V•Q C•. � Y .�tYSl 0Qjfp 14' <' +«f1.S t
^ ,rtS�-� e2 � e r2 `o ° % I ; �"'�? : X �� • ii'' ! C{ �i-C �� � �JL� rr-�? ; vni =� �'a�'- t� � �P s r cL ,,., ;, .(��_�'d �
t J %-el- l h e� 417'a- c
n�aw 5ej'L Prod+Le r- Lc Seel }ah dt1rC7�
SYSig^ Jl+li•a.v.� C3 Mhx df 1,40blpd a I�Sob 9atleN +t.rae. cu l
I'ori.,`r`% �rL c4s+- Cof re_k-c.
13 a,, wr+ amyl,c..F,piv ra.}IL O-P •JOS ylpld p/Sq/+i- +ke 41►Stlrp4ld , Grew t8 1�60 41°1), V 5+ l� '4-1,C
S�artdGra \,^ , arc CA S0% Gre.d\� wes v9ac� �0 Cale le- �t c+bSar}row creG4 L)Jp4
r 1. = 6� 5�4Kd�.ra ►r,-C\�Fra�of lath to q al0 aTuft�., rray.�hcs ►k fS¢vL s
iS.S JiG / CCT NOW ola5,�+-Gc�S'%Sjt'hL�
t N S�cl�w�LU'U � O+w
�O d �lGlvt pCCrt
V t 5 4 jv � 6 �S cC e 1 �t c � 1 � S S \( S 4-� w o, �A
v u e -C or ti•�-ci
QYiCe.v�k�o�
l e
or,4
-!(S c (- �\a� cv,. ��cae b w.\�. L rd'iY � 5 were Cv,; Q,!`��
tv k , i C .+ i r t r C \ \ v. f $ w e c Q Q, p O S Q. �. . �. �', C •� O : \, c �, a, ' ( ti e. L. k 1'
{{ l 1 (( 1 ii 'y S Q. rL d rt
Q it 1�� �� Y Q� C U @Y\� BAN �S yv S 1 C- cl r C CMf tv(�", A
gwa,l �<cn.l %\Ouse .laec4v5' r
r �. N.- �� r ca ; far L,.2h 4ua cir Icy 4 LoS,5 , VV
ciwk 'IfPf- ue� h/ew yN does c-c 4 Yp ,ire-
1 Mry ir0t^ kar'm r s A oe.�, of S �a4lar,
2^IO•bt{ - Calt¢d L kt� 1 btTked 14.e� Fv v`e�1ouN �o,SfrS
6t7 rtiZt @ Ckea}5. ,- 5t 114e.' o� �a. 1R 6vccw, 1� �q i..0 .rrar�rl4vti��5
A w �
a } G'1S al l4 d 0,u,ig, Sr,r.� lneug�, W�}t +�� "'N !�/+"t �i4 ►ti , 9 c>�A,, css� r
b V e, +► 4 y/ t1 { S A4 G a r i 5 - S e k •S l c f ire s i t e r2 Cp L `r �\-► C .� �' r v L
'�( N• l� Icy �nz TvSeci
a
10%'Post ns�mr�'' r� l� -lam
/-
C.��i-`t / v ' i' ivy �YU/G cS� S� �i vyt l�a5� �=�%1 ✓I� C� �n� �17-LTr 14
(�o � � � jay �t, � �� c�c-s�'%r2 y�C � �%i -�Y� • �n.�s � G�-� �� � �7 6 � %t
tT
A
Gl�p
M ■
21" clear insert access
Sohan
Mumber
Dlsdwrge
Par CycM
w
L
H
A
B
12' — B'
5' — 10'
1106
333
570
135/1B0/240
GaNan.
NOTE. The above septic tank is produced by Front Range Precast Concrete
NOTES'
1. Bends in the building sewer shall be limited to 45
degrees.
2. The septic tank shall be installed level. The tank shall
8- have removable covers or manholes to within 8 inches of the
finished grade, for inspection and cleaning.
J. Avoid vehicle traffic over the system.
4. All installations shall meet the rules and regulations of the
Eagle County Environmental Health Division, for Individual
Sewage Disposal Systems.
5. The Septic System Installation shall be inspected by the
Design Engineer and by the Eagle County Environmental Health
Department prior to backfilling.
10"
AL SOIL PRE
0 to 1 foot Topsoil
1 to 4 feet Weathered bedrock
4 to 8 feet Shale and
Sandstone Bedrock
NOTE.• — SITE PLAN E—MAILED BY RICK DOMINICK, ARCHITECT
MO UND DIMENSIONS
DESCRIP T/GU
SYMBOL
DIMENSION
(feet)
BED WID TH
A
12. 0
BED LENGTH
B
79.0
MOUND DEPTH
D
MOUND DEPTH
E
BED DEPTH
F
0.7
CAP AT EDGE OF BED
G
1.0
CAP A T CENTER OF BED
H
1.5
DOWNSLOPE SETBACK
1
45.0
UPSLOPE SETBACK
J
8.0 --,
SIDESLOPE SE78ACK
K
13.0%,,"
MOUND LENGTH
L
105.0
MOUND W1D TH
W
65.0
ri,
` � � -7
Gf�-�- I v
to 7 X
i o-76 d- � �3�1j� L I
Z J
4
X/S77NG GRADE AT PROPOSED MOUND
S STEM YA71•I A 23R SLOPE
Design percolation rate T > 420 minutes per inch
Because of the closeness of th�i bedroc o the ground surface (less than four feet) a
MOUND TYPE SYSTEM with a pressurized distribution network is recommended for this site.
Loading Rate for a Medium Texture Sand = 1.2 gpd/sf
Number of bedrooms = 5 /
Maximum daily Flow, = Qmax j
Qmax = 5 bdrms x 2 perso,�s/bdrm x 75 gallons/person/day x 150%
Qmax = 1125 gpd
SEPTIC TANK
V = Qmax/24hrs x 30 his
V = 1406 gallons
Use 1500 Gallon Electric ift Septic Tank by Front Range Precast Concrete or equivalent
ABSORPTION AREA
A = Qmax/1.2gpd/sf
A = 112,511.2 = 938/s. f.
/
The absorption bed lmensio,7 within the Mound System will be 12 feet wide by 79 feet long.3 '412
The absorption bed shall be parallel to the surface contours. The perimeter of the mound
shall be 105 feet long and 65 feet wide.
Site Preporo Lion t t CS 4, a S
Stake out the mound perimeter. Cut a bench along the contour (as close as possible) with a
slope of 159' versus the existing slope of +/--239a This will require on approximate cut of 5.2
feet at the top of the slope, and a cut of about 6 inches at the base of the mound. Install
the delivery pipe from the dosing chamber to the mound. Bockfill and compact the pipe
trench. Plow the area within the mound perimeter. Plowing should not be done when the soil
is too wet. Grade the uneven areas.
Fill Placement
Place the fill material over he prepared site. The fill material_ should consist_ of Medium
Texture Sand with the following characteristics:
88 to 939 Sand
7 to 129 Finer Grained Materials
The infiltration rate of a Medium Texture Sand is 1.2 gpd/sf. The height of the sand fill
should be the elevation of the top of the absorption bed. Shape the sides of the mound to
the recommended slope, as shown on the details.
Distribution Network Placement
Carefully place the coarse aggregate on the bed. The coarse aggregate shall consist of 3/4
to 2-1/2 inch rock. Level the aggregate to a minimum depth of 6 inches. Assemble the
distribution network over the aggregate. The distribution network shall consist of four 39—feet
laterals, 1-1/4 inch diameter (two on each side of a 3—inch diameter center manifold). The
inverts of the laterals shall be perforated with 1/4—inch holes spaced every 36 inches. For
the pressure distribution network use schedule 40 pvc (ASTM D 2665) or ABS (ASTM 2661)
pipe. The laterals shall be laid level. Place additional aggregate over the crown of the pipes
of at least 2 inches depth. Place a suitable backfill barrier, such as filter fabric, over the
aggregate.
Covering of the Mound System
Place a finer textured soil, such as clay or silt loam over the top of the bed, to a minimum
thickness of 6 inches. Place 6 inches of good quality topsoil over the entire mound surface.
Plant grasses and wild flowers that do not require watering and adaptable to the climate
over the mound system. Over the back portion of the mound system, uphill from the
absorption area other vegetation, such as sage brush or other shrub (also adaptable to the
high altitude and arid climate) can be planted.
"hon Selection
Due to sufficient elevation difference (greater than the required 2.5 feet) between the siphon
invert and the elevation of lateral inverts, Single Auto Siphon in its own compartment, capable
of delivering 240 gallons per cycle should be used.
Inspection Pipe
Install a 4 inch diameter inspection pipe on both ends of the Gravel Bed. The pipe shall be
open on the bottom. The bottom of the pipe shall be at the some elevation as the bottom
of the gravel bed. The bottom 8 inches of the inspection pipe shall be perforated. The pipe
shall be covered with a ven! cap.
PROPOSE CUT GRADE FOR
BASE OF ROPOSED MOUND
SYSTEM TH A 15Z SLOPE 1.5'
--- 1' I—
1Z�=
?Sct'i
1 Zen
-
3—INCH DIAMETER, SCH40 /
PVC, CENTER MANIFOLD f
1-1/4 INCH, SCH 40 PVC LATERALS,
PERFORATED AT THEIR INVERTS WITH 1/4—INCH
HOLES AT 36—INCH INTERVALS
-FILTER FABRIC
5.
71
y':.wr':?i:�_'..:'. .�:..y.,' �:,� ;;:.•1•; .'•`•• •, i/////////////// EDIUM SAND FILL
6" CUT �:7—
:,�>• �- :'`"� 3/4" TO 2-1/2" WASHED ROCK
A.
ARED AND RAKED SURFACE
CROSS SECTION A —A
NOT TO SCALE
FROM SIPHON
.tS
m
2
O
U
W
0
Q
0
d
z
T�T^
v�
W
O
A
Q
J
Wc
V
�1 ~
� A
�1 ^ O
U �
O W
J Q
W
W
•
rn
00
o
C14 0)
0000 cV
rn
•` o
rn
z
x LX
0 Ld �
00
00
0
\
1r)
v � �
U X tV
. O
b�n
o�
L
"` ,
•v
- 29526
�N
{{f{llFbjsllk
�'# �A`Nt`i.•l
DRAWN BY.• L. P.
CHECKED BY L.P.
PROJECT NO.: 03010
DA M 03-19-2003
DRAWING NO.: 03010sd. d wg
SHEET 1 of 1
NQ TES
FERCOLAPON TEST RESULTS DESIGN CAL CUL 4 TONS
1. Bends in the building sewer shr
Perc No. Perc No. Perc- No. J Design percolation rote T 12 minutes per inch be limited to 45 degrees.
Number of bedrooms = 5
10 minutes per inch 15 minutes per inch 10 minutes per inch
Maximum daily Row = 0max
0mcy = 5 bdrrns x 2 personsAdrm x 75 gallons/person/day x 1150Z
2. The septic tank shall be instai,14d level. The tank shall have removable
Average percolation rate recommended for design T = 12 minutes per inch. 0mcx = 1125 !7pd covers or manholes to within 8 inches of the finished grade, for
Fercalaticn test done January 13, 2004. inspection and cleaning.
SEP n C TANK
SOIL PROFILE V = OmoYI24hrs x JO hrs
X V = 1406 gallons J. Excavate three (3) feet wide trk-nches. The horizontal distance from
Use the existing 1500 gallon, three compartment precast concrete tank, remove the siphon. sidewag to sidewag between the trenches shall be a minimum of six
(6)
PRORLE HOLE h'1 A feet.
3SORPRON AREA
0 to I foot Topsoil
1 to 8 feet Light brown, silty, gravelly sand A = Omcxl,'Sx T 4. The bottom and Me sidewalk of the trenches shall be raked to
J A = 11251;',�ox 12 780 s.f
No ground water encountered eliminate smeonng.
CRY GULL`1-1 f I
Based on Applicatio Rate:
L/ FROF'XE HOLE 5. Assemble and install the Infiltrator Chambers in the trenches
I., 112�7,pdlO. 605 gpd1s. f
0 to 1 foot Topsoil A = - according to the manufacturers roc mmendations.
A = 186 s. f I .................... 1 to 8 feet Light brown, silty, gravelly sand
No ground water encountered 6. Backfil! the sidewall area with native on —site te soil for proper support.
Standard Infiltrator Chamber System in a trench configuration with an allowed 50 percent
�� ��`�� �; f�// \ `!`I \ \ \ [i \ \ Acorrected = 9JO s.f
Profile holes togged December 31, 2003. reduction in the absorption area is recommended. Z 8cckfM' the trenches with a mirimum of 12 inches of tamped soil
cover.
A -A Surface area of one InAltrotor Chamber = 15.5 s.f
Use 60 Infiltrator Chambers in trenches, as shown on the plan.
f s ; \ �\ \ \\ ' \ ,8. Avoid vehicle traffic over the system.
N35
9. All installations shall meet the rules and regulations of the Eagle
County Environmental Health Division, Chapter 4, Individual Sewage
5 TAA0Aq9 TRA TOR Disposal Systems.
5. 10. The Septic System Installation shall be inspected by the Eagle County
Environmental Health Department and by the Design Engineer prior to
7
bcckfilling.
.,Per Pe �'fi i��-
ILr/ � it ! ! '� + l \\\ � � \ ` } \ \ \ `\' , , ` t � % r 1` i'f � � ' �\ \ \ \ \ � � '� ,i `j4F 4 `, i t , [
EA POLE N ) I/ t \ �• / f / ; i i / , �-\ . - - } \ ; ,\ ; \ \\ \ , i c ` t \- t' - f j � �f � \ \ '\ ` It \ `' \ � � ` \ `� 't�1 ` � � �• � { it j � 4 }
N
Per 3 � J T k \ � \ \\ �`',, t � \ + [i \ ,\ � E ` \ � � \ \\ \ \ \ °! ` � \ ` •\\ / � /f �, j i � � \ ;t � , � \ , t ?(. t ! , ! ``� 1 \ � ', �j `4
AV-W C nOM PCR
75 Of7LE HCX,E
\ '•.� t r ` ; \.\ `t, \ }/t } , \ \ \ \ \ 't \ s\ \ \ - - 1 ' i \ [ t \ \ [ \ 1 i t ` \` `-l. ,t., \� \` \ 1 ( A it
X Z 0
it
730
` r`� � - �, �[ f i /, r` I � ' � t �; �:� `, \ � `1 \ \ \ \ \ `\ ` \`tt \ I 1 � t { � It � t � C \ \ 1 � 't ` \ ,t \. \\_ 4\ \\ �. `` -
4
X
\ \ \ s i \ \ \ \ \
Z
1Z, X
N\
X t3`0810U
i 1 i ' \ \ \ \ \ \ \ �� \ 1 1 ' \ r \ \
Z \ \ \ \, \ `�` e } 1 \ \ \ \ \V
X- 1Z
"A
X X
Xx 94 N
l / •' % � l ' PROPOSED AMX'
A T54
A
82 G- GARACe," N,
1,17 X
\ � f r 1. � f/ l �' O � _ f /++J�J�
t \ � � l� � ' �, li
- t �� i' `� \ � j it � � ' f ' f �' -J, �/
6, -, 8,
9C ELSOW
SURFACE
21' clec- insert access MrX MA MR OqAmx*l
jj
E- DETAIL A A
N. TS.
5' 10"
A B
4'
2
TT-1-1 1
S �-4 GIV
REMO�F SIPHON AND cur NEw OUTLEj
STANDARD TAT17TT TPA Tf) P
Dknenvk"
cvocpim
-%¢Aan
Owmaw
Dirdmrqe
Per CedeF
L
A
a
6. -s.
12' - a
J'- 10'
1106
535
GWIGns
M TS.
7
I r -
NOTE. - SITE PLAN E-MAILED BY RICK DOWNICK, ARCHITECT
NOTIN MT
r-7e above septic tank is protluced, by Front Range Precast Concrete
1-1 �-h
30
:
4
8X
8
LV5TWa'j-1W WV.
n4REF CCAdVAR -N r
\COYCWT& SW77C
WUf\A slaw
\AE PEVOKD
\ \ A
T
CL&
72189.0 V,
Z
e9..
I CCAIWAF
so
SEK
y
<
f
PATIO L0119. I --T
t I I
APWRCYAWA T LOMaWG DCA TXW 8 STA
OF VUSING f
SEWER y it D
13 4
f
8
0-
f
N t J
4
X it
X - CLEAIjOUT
If
j
zil
4V
IV
----------------
CO
4U
LQ
C)
Q)
'i
•
CV
Uj
Z
0-4
X
C)
Ld
00
00
Q) 0
Q) 0G)
f
>
0-4
C-4 L6
C-4
L)
X
0
• M,
.0
C
'Fig
a. PE %
MA'L
D":17r-1
L.P.
0-Ilf-CXED sy- L.P.
FROZC T h-
SESE FEV--o"'i5 BOIX
CIA 7E.-
03-19-2CJ.J
07-Ak-liX NO.: 0j0lw06d-27.C"*-V
of