Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout1155 Green Meadow Dr - 239121403001INDIVIDUAL SEWAGE DISPOSAL SYSTEM PERMIT
EAGLE COUNTY ENVIRONMENTAL HEALTH DIVISION
P.O. Box 179 - 500 Broadway • Eagle, CO 81631
Telephone: (970) 328-8755
COPY OF PERMIT MUST BE POSTED AT INSTALLATION SITE. PERMIT NO. 2203-02 BP NO. 14310
OWNER: CRAIG AND KIM ROGERS PHONE: 970-704-0777
MAILING ADDRESS: 151 SUMMIT DRIVE, CARBONDALE, CO 81623
APPLICANT: SAME PHONE:
SYSTEM LOCATION: 850 GREEN MEADOW DRIVE, CARBONDALE TAX PARCEL NO. 2391-214-03-001
LICENSED INSTALLER: ZAMORA EXCAVATING, JOE ZAMORA LICENSE NO. 19-02 PHONE: 970-963-2553
DESIGN ENGINEER: HIGH COUNTRY ENGINEERING, ROGER NEAL PHONE NO. 970-945-8676
INSTALLATION HEREBY GRANTED FOR THE FOLLOWING: MINIMUM REQUIREMENTS FOR A 6 BEDROOM RESIDENCE
2500 GALLON SEPTIC TANK, 2383 SQUARE FEET OF ABSORPTION AREA CREDIT, VIA 77 INFILTRATOR UNITS (DESIGN CALLS FOR 80 UNITS) AS
PER ENGINEER'S DESIGN DATED 6/3/02.
SPECIAL INSTRUCTIONS: INSTALL AS PER ENGINEER'S DESIGN, WITH A CLEANOUT BETWEEN THE TANK AND THE HOUSE, AND INSPECTION
PORTALS IN EACH TRENCH. RAKE ALL TRENCH SURFACES TO PREVENT THE SMEARING OF SOILS AND DO NOT INSTALL IN WET WEATHER. DO
NOT BACK FILL WITH ANY COBBLES LARGER THAN 8 INCHES IN DIAMETER. BE SURE TO MAINTAIN ALL APPLICABLE SET BACK REQUIREMENTS.
CALL EAGLE COUNTY ENVIRONMENTAL HEALTH AND THE DESIGN ENGINEER FOR THE FINAL INSPECTION PRIOR TO BACK FILLING ANY
PART OF THE INSTALLATION, OR WITH ANY QUESTIONS REGARDING THE INSTALLATION. THE BUILDING CERTIFICATE OF OCCUPANCY
WILL NOT BE ISSUED UNTIL THE SEPTIC YST,E�M� HAS BEEN INSPECTED AND APPROVED.
ENVIRONMENTAL HEALTH APPROVAL: (,t.t/I✓ DATE: AUGUST 9, 2002
CONDITIONS:
I. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM REGULATIONS,
ADOPTED PURSUANT TO AUTHORITY GRANTED IN 25-10-104, 1973, AS AMENDED.
2. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND BUILDING
REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS SHALL
AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT.
3. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL SYSTEM TO
BE LICENSED.
FINAL APPROVAL OF SYSTEM (TO BE COMPLETED BY INSPECTOR):
NO SYSTEM SHALL BE DEEMED TO BE IN COMPLIANCE WITH THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM REGULATIONS UNTIL THE SYSTEM
IS APPROVED PRIOR TO COVERING ANY PORTION OF THE SYSTEM.
INSTALLED ABSORPTION OR DISPERSAL AREA: 2387 SQUARE FEET (VIA 77 INFILTRATOR UNITS PER DESIGN )
INSTALLED CONCRETE SEPTIC TANK: 2500 GALLONS IS LOCATED 110 DEGREES AND '_ FEET — INCHES
FROM THE CLEAN -OUT ON THE SOUTH SIDF OF THF. HnTTSF-
COMMENTS: THE FINAL INSPECTIONS WERE DONE BY THE. DFSTGN F.NGTNFFR ON OCTnRF.R 10, 2002, AND
gmm mp MERRY nF EAGLE COUNTY ENVIRONMENTAL HEALTH ON ncTnRF.R 16, 9002 THIS SvSTEM is
LARGE ENOUGH TO ACCOMMODATE A SIX BEDROOM RESIDENCE.
ANY ITEM NOT MEETING REQUIREMENTS WILL BE I CTED FOR$ F OVAL OF SYSTEM IS MADE. ARRANGE A RE -INSPECTION WHEN WORK IS
COMPLETED.
ENVIRONMENTAL HEALTH APPROVAL DATE: OCTOBER 29. 2002
SE-P-20--0001 10:23A FROM:EAGLE COUNTY ENV HER 9703288788 TO:919709632396 P:1/5
Incomplete Applications Will NOT Be Accepted
(Site Plan MUST be attached)
ISDS Permit # oL�3 - U ,2—
Building Permit # 14.5 /Q -
APPLICATION FOR INDIVIDUAL SEWAGE DISPOSAL SYSTEM PERMIT
ENVIRONMENTAL HEALTH OFFICE - EAGLE COUNTY
P. O. BOX 179
EAGLE, CO 81631
Eagle (970)328-8755, Fax (970)328-0349, El Jebel (970)927-3823
* FEE SCHEDULE
* APPLICATION FEE $350.00
* THIS FEE INCLUDES THE ISDS PERMIT, SITE EVALUATION (PERCOLATION TEST,
* SOIL PROFILE OBSERVATION) AND FINAL INSPECTION
* ADDITIONAL FEES MAY BE CHARGED IF A REINSPECTION IS NECESSARY, OR A
* PRE -CONSTRUCTION SITE VISIT OR CONSULTATION IS NEEDED
* REINSPECTION FEE $47.00, PRE -CONSTRUCTION SITE VISIT FEE $85.00
* MAKE ALL REMITTANCE PAYABLE TO: "EAGLE COUNTY TREASURER"
PROPERTY OWNER:
MAILING ADDRESS:
-PPLICANT/CONTAC
LICENSED SYSTEMS
,ati 0 -/-
T
V
_ f� / Syvr►mi'� Ui[ • PHONE: 170,V'0%77
PERSON: PHONE: 2L
CONTRACTOR: �.. %L(r PHONE: qfg- 2,s5" 3
COMPANY/DBA : ()D t/'p,ADDRESS:
***************************************************************************
PERMIT APPLICATION IS FOR: ()� NEW INSTALLATION ( ) ALTERATION ( ) REPAIR
LOCATION OF PROPOSED INDIVIDUAL SEWAGE DISPOSAL SYSTEM:
Legal Description:
Tax Parcel Number: �R_3411 a 14 ®3 ego 1 Lot Size: 4/- ©3 acr�5
Physical Address; MEQ
BUILDING TYPE: (Check applicable category)
()o Residential/Single Family Number of Bedrooms
( ) Residential/Multi-Family* Number of Bedrooms
( ) Commercial/Industrial* Type
*These systems require design by a Registered Professional Engineer
TYPE OF WATER SUPPLY: (Check applicable category)
(K Well ( ) Spring ( ) Surface
( ) Public Name of Supplier: A3A?=n /L� rt < j�'� 31
APPLICANT SIGNATURE: Date:
AMOUNT PAID: 350, RECEIPT 0 21 ( 3 DATE:
CHECK #: jFr 712-6 CASHIER:
DEPARTMENT OF
ENVIRONMENTAL HEALTH
(970)328-8755
FAX (970) 328-8788
TDD: (970) 328-8797
TOLL FREE: 800-225-8136
www.eagle-county.com
EAGLE COUNTY, COLORADO
October 30, 2002
Raymond P. Merry, REHS
Director
Craig and Kim Rogers
151 Summit Drive
Carbondale, CO 81623
RE: Final of ISDS Permit #2203-02, Tax Parcel #2391-214-03-001. Property
location: 850 Green Meadow Drive, Carbondale, CO.
Dear Mr. & Mrs. Rogers:
This letter is to inform you that the above referenced ISDS Permit has been inspected and
finalized. Enclosed is a copy to retain for your records. This permit does not indicate
compliance with any other Eagle County requirements. Also enclosed is a brochure regarding
the care of your septic system.
Be aware that later changes to your building may require appropriate alterations of your septic
system.
If you have any questions regarding this permit, please contact the Eagle County Environmental
Health Division at (970) 328-8755.
Sincerely,
iv"'t
Janet Kohl
Eagle County Environmental Health Department
ENCL: Informational Brochure
Final ISDS Permit
cc: files
OLD COURTHOUSE BUILDING, 551 Broadway, P.O. Box 179, Eagle, Colorado 81631-0179
DEPARTMENT OF
ENVIRONMENTAL HEALTH
(970) 328-8755
FAX (970) 328-8788
TDD: (970) 328-8797
TOLL FREE: 800-225-8136
www.eagle-county.com
EAGLE COUNTY, COLORADO
Date: August 9, 2002
TO: Zamora Excavating
Raymond P. Merry, REHS
Director
FROM: Environmental Health Division
RE: Reissuance of Individual Sewage Disposal System Permit 92203-02. Tax Parcel
#2391-214-03-001. Property Location: 850 Green Meadow Drive, Carbondale,
CO., Rogers residence.
Enclosed is your ISDS Permit #2203-02, and a field copy of the engineer design stipulated on the
permit from the engineer. It is valid for 120 days, or for the duration of your current building
permit for this property. The enclosed copy of the permit must be posted at the installation site.
Any changes in plans or specifications invalidates the permit unless otherwise approved.
Please note any special requirements that may have been added to the design by this
department.
Systems designed by a Registered Professional Engineer must be certified by the Engineer
indicating that the system was installed as specified. Eagle County Environmental Health
must also view the installation prior to back filling. Please call well in advance for your
final inspection. Your TCO will not be issued until our office receives this certification
from the engineer, and views the installation.
Permit specifications are minimum requirements only, and should be brought to the property
owner's attention.
This permit does not indicate conformance with other Eagle County requirements. Please
notify this office if you have not been contracted to perform this installation.
If you have any questions, please feel free to contact the Environmental Health Division at 328-
8755.
cc: files
High Country Engineering, Derek Walter
OLD COURTHOUSE BUILDING, SS Broadway, P.O. Box 179, Eagle, Colorado 81631-0179
October 11, 2002
Eagle County Environmental Health Department
Attn: Ray Merry
P. O. Box 179
Eagle, CO 81631
Re: Lot 18, Sopris Mesa Subdivision, Eagle County, Colorado
HCE File Number 2021054.59
Dear Ray:
On October 10, 2002, High Country Engineering personnel observed the construction of the
ISDS for the Rogers Residence located on Lot 18, Sopris Mesa Subdivision in Eagle County,
Colorado. One 2500-gallon septic tank (labeled 2000-gallon, but with an additional
expansion ring) with baffle and 77 standard Infiltrator units were being installed in a bed
configuration. Minimal backfilling had taken place. The contractor had misread the plan and
was in the process of only installing 70 units rather than the designed 80 units. Due to
various boundary constraints, it was decided that the system would consist of the minimum
77 units in a non -uniform trench configuration of 14,15,16,16, and 16 units. The contractor
was also advised to rake the sidewalls clean of soil smears. I have enclosed pictures of the
system and an as -built drawing for your convenience. If you have any questions, or need
additional information, please contact us.
Sincerely,
RECEIVED
HIGH COUNTRY
Roger 13- Neal, P.E.
Project Manager
RDN/djw
G, INC.
OCT 15 2002
ENVIRONMENTAL
HEALTH DEPARTMENT
1517 Blake Avenue, Suite 101 14 Inverness Drive East Suite D-136
Glenwood Springs, CO 81601 Englewood, CO 80112
Telephone (970) 945-8676 - Fax (970) 945-2555 Telephone (303) 925-0544 - Fax (303) 925-0547
HHepworth-Pawlak Geotechnical, Inc.
tech
Glen County Road 154
G( oPGlenwood Springs, Colorado 81601
Phone: 970-945-7988
April 23, 2002 Fax: 970-945-8454
hpgeo@hpgeotech.com
Craig Rogers
151 Summit Drive
Carbondale, Colorado 81623 Job No. 101 797
Subject: Supplemental Percolation Testing, Lot 18, Sopris Mesa, Eagle County,
Colorado
Dear Mr. Rogers:
As requested, Hepworth-Pawlak Geotechnical, Inc., performed additional percolation testing at
the subject site. The work was done in addition to our agreement for professional services to
you, dated November 30, 2001. We previously performed a subsoil study for foundation
design and percolation testing at the subject site and reported our findings January 16, 2002,
Job No. 101797.
Six percolation test holes were excavated adjacent to Pit 1 (P7, P8 and P9) and Pit 2 (P4, P5
and P6). The subsoils encountered in Pit 1 and Pit 2 consisted of about 1 foot of topsoil
overlying sandy clay to the bottom pit depths fo 8 feet. The pit and percolation test hole
locations are shown on Figure 1.
The percolation test holes were presoaked with water on April 18, 2002 and testing was done
on April 19, 2002. The percolation test results are summarized on Table I. Based on the
subsurface conditions and the percolation test results, Eagle County may require that the septic
disposal system be designed by a civil engineer. The percolation tests performed in the area of
Pit 2 were significantly faster than at Pit 1. The clay soils in Pit 2 were generally more sandy
and lower density than the clay soils encountered in Pit 1.
If you have any questions, please call our office.
Sincerely,
HEPWORTH-PAWLAK GEOTECHNICAL, INC.
` Louis E. Eller �ua�aarr
Reviewed By:
Daniel E. Hardin, P.11
s ®k,
LEE/djg
attachments �''`ri, ss�} N A L `'
LEGEND:
0
GREEN MOUNTAIN DRIVE
LOT 18
APPROXIMATE SCALE
1 " = 500
P 7
r � _
PQ8
J � I
BUILDING
I PIT 1 ENVELOPE
I P 9- 1 1
I I
I I
i I
I I LOT 19
2,PROFIL
I
�P 6 l�
P 5-
PIT 2 I
�j P 4 J- Z&
PERCOLATION TEST HOLE FOR THIS STUDY.
PERCOLATION TEST HOLE FOR PREVIOUS STUDY.
1 101 797 I GEOWEOCHNICALWINC. I ANDAPERCO ATIONL TESTOHOLES S I Fig. 1 I
HEPWORTH-PAWLAK GEOTECHNICAL, INC.
TABLE I
PERCOLATION TEST RESULTS JOB NO. 101 797
HOLE NO.
HOLE DEPTH
(INCHES)
LENGTH OF
INTERVAL
(MIN)
WATER DEPTH
AT START OF
INTERVAL
(INCHES)
WATER DEPTH
AT END OF
INTERVAL
(INCHES)
DROP IN
WATER
LEVEL
(INCHES)
AVERAGE
PERCOLATION
RATE
(MIN./INCH)
P4
48
30
30
15
15
15
15
6 3/4
5
1 314
26
5
3 3/4
1 1 /4
7
6 1 /2
1 /2
6 1 /2
6
1 /2
6
5 1 /4
3/4
5 1 /4
4 3/4
1 /2
P5
40
30
30
15
15
15
15
6 3/4
4 1 /4
2 1 /4
23
4 1 /4
2 1 /4
2
6 3/4
6
3/4
6
5 1 /4
1 3/4
5 1 /4
4 1 /2
3/4
4 1 /2
4
1 /2
P6
46
30
30
15
15
15
15
6 1 /4
4
2 1 /4
16
4
2 1 /2
1 1 /2
8
6 3/4
1 1 /4
6 3/4
5 3/4
1
5314
43/4
1
4 3/4
4
3/4
Note: Percolation 'test holes were hand dug in the bottom of backhoe pits and soaked on April
18, 2002. Percolation tests were conducted on April 19, 2002. The average percolation
rate is based on the last three readings of each test.
HEPWORTH-PAWLAK GEOTECHNICAL, INC.
TABLE I
PERCOLATION TEST RESULTS JOB NO. 101 797
HOLE NO.
HOLE DEPTH
(INCHES)
LENGTH OF
INTERVAL
(MIN)
WATER DEPTH
AT START OF
INTERVAL
(INCHES)
WATER DEPTH
AT END OF
INTERVAL
(INCHES)
DROP IN
WATER
LEVEL
(INCHES)
AVERAGE
PERCOLATION
RATE
(MIN./INCH)
P7
48
30
30
30
30
7 314
7 1 /4
1/2
40
7 1 /4
6 1 /4
1
6 1/4
5 3/4
1/2
5 3/4
5
3/4
P8
40
30
30
30
30
7
6 314
1 /4
120
6 3/4
6 1/4
1/2
6 1 /4
6
1 /4
6
6
0
P9
48
30
30
30
30
6
5 3/4
1 /4
180
5 3/4
5 1/2
1/4
5 1/2
5 1/2
0
5 1/2
5 1 /4
1 /4
Note: Percolation test holes were hand dug in the bottom of backhoe pits and soaked on April
18, 2002. Percolation tests were conducted on April 19, 2002. The average percolation
rate is based on the last three readings of each test.
C�tech
January 16, 2002
Craig Rogers
151 Summit Drive
Hepworth-Pawlak Geotechnical, Inc.
5020 County Road 154
Glenwood Springs, Colorado 81601
Phone: 970-945-7988
Fax:970-945-8454
hpgeo@hpgeotech.com
Carbondale, Colorado 81623 Job No. 101 797
Subject: Subsoil Study for Foundation Design and Percolation Test, Proposed
Residence, Lot 18, Sopris Mesa Subdivision, Missouri Heights, Eagle
County, Colorado.
Dear Mr. Rogers:
As requested, Hepworth-Pawlak Geotechnical, Inc. performed a subsoil study and
percolation test for foundation and septic disposal designs at the subject site. The study
was conducted in accordance with our agreement for geotechnical engineering services
to you dated November 30, 2001. The data obtained and our recommendations based
on the proposed construction and subsurface conditions encountered are presented in.
this report. Hepworth-Pawlak Geotechnical, Inc. previously conducted a preliminary
subsoil study and geologic hazards evaluation for the Sopris Mesa Subdivision, report
dated October 23, 1997, Job No. 197 495.
Proposed Construction: The proposed residence will be a two story wood frame
structure over a basement level or crawlspace and located within the building envelope
shown on Fig. 1. The attached garage and basement floors are proposed to be slab -on -
grade. Cut depths are expected to range between about 4 and 8 feet if a basement level
is constructed. Foundation loadings for this type of construction are assumed to be
relatively light and typical of the proposed type of construction. The septic disposal
system is proposed to be located downhill to the southwest of the building envelope.
If building conditions or foundation loadings are significantly different from those
described above, we should be notified to re-evaluate the recommendations presented in
this report.
Site Conditions: The site was vacant at the time of our field work. The ground
surface in the building envelope is relatively flat to gently sloping down to the south.
There is about 2 feet of elevation difference across the building envelope. An irrigation
ditch is located along the southern portion of the lot. The lot is vegetated with grass
and weeds.
Subsurface Conditions: The subsurface conditions at the site were evaluated by
excavating two exploratory pits in the building area and one profile pit in the septic
disposal area at the approximate locations shown on Fig. 1. The logs of the pits are
presented on Fig. 2. The subsoils encountered, below about 1 foot of topsoil, consist of
Craig Rogers
January 16, 2002
Page 2
stiff to very stiff sandy clay to the pit depths of 8 feet. Results of swell -consolidation
testing performed on relatively undisturbed samples of the clay soils taken at a depth of
4 feet, presented on Figs. 3 and 4, generally indicate low compressibility under existing
moisture conditions and light loading and a low to moderate expansion potential when
wetted. The sample from Pit 2 at 6 feet showed no expansion potential and relatively
high compressibility upon additional loading after wetting. The laboratory testing is
summarized on Table I. No free water was observed in the pits at the time of
excavation and the soils were slightly moist to moist. Pits excavated in the area of Lot
18 as part of the preliminary study encountered similar soils and no groundwater to the
excavated depths of 81/2 and 9 feet.
Foundation Recommendations: Considering the subsoil conditions encountered in the
exploratory pits and the nature of the proposed construction, we recommend spread
footings placed on the undisturbed natural soil designed for an allowable soil bearing
pressure of 2,500 psf and a minimum dead load pressure of 800 psf for support of the
proposed residence. The soils have variable settlement/heave potential after wetting and
there could be some post -construction foundation movement if the bearing soils become
wet. The settlement/heave potential of the soils at bearing level should be evaluated at
the time of construction. Precautions should be taken to prevent wetting of the bearing
soils. Footings should be a minimum width of 16 inches for continuous walls and 2 feet
for columns. Loose and disturbed soils encountered at the foundation bearing level
within the excavation should be removed and the footing bearing level extended down to
the undisturbed natural soils. Exterior footings should be provided with adequate cover
above their bearing elevations for frost protection. Placement of footings at least 42
inches below the exterior grade is typically used in this area. Continuous foundation
walls should be heavily reinforced top and bottom to span local anomalies such as by
assuming an unsupported length of at least 12 feet. Foundation walls acting as retaining
structures should be designed to resist a lateral earth pressure based on an equivalent
fluid unit weight of at least 60 pcf for the on -site soil as backfill.
Floor Slabs: The on -site soils possess an expansion potential and slab heave could
occur if the subgrade soils were to become wet. Slab -on -grade construction may be
used provided precautions are taken to limit potential movement and the risk of distress
to the building is accepted by the owner. A positive way to reduce the risk of slab
movement, which is commonly used in the area, is to construct structurally supported
floors over crawlspace.
To reduce the effects of some differential movement, nonstructural floor slabs
should be separated from all bearing walls and columns with expansion joints which
allow unrestrained vertical movement. Interior non -bearing partitions resting on floor
slabs should be provided with a slip joint at the bottom of the wall so that, if the slab
moves, the movement cannot be transmitted to the upper structure. This detail is also
H-P GEOTECH
Craig Rogers
January 16, 2002
Page 3
important for wallboards, stairways and door frames. Slip joints which will allow at
least 11/2 inches of vertical movement are recommended. Floor slab control joints
should be used to reduce damage due to shrinkage cracking. Slab reinforcement and
control joints should be established by the designer based on experience and the
intended slab use.
A minimum 4 inch layer of free -draining gravel should be placed immediately
beneath basement level slabs -on -grade. This material should consist of minus 2 inch
aggregate with less than 50 % passing the No. 4 sieve and less than 2 % passing the
No. 200 sieve. The free -draining gravel will aid in drainage below the slabs and
should be connected to the perimeter underdrain system.
Required fill beneath slabs should consist of a suitable imported granular
material such as road base. The fill should be spread in thin horizontal lifts, adjusted to
at or above optimum moisture content, and compacted to at least 95 % of the maximum
standard Proctor density. All vegetation, topsoil and loose or disturbed soil should be
removed prior to fill placement.
The above recommendations will not prevent slab heave if the expansive soils
underlying slabs -on -grade become wet. However, the recommendations will reduce the
effects if slab heave occurs. All plumbing lines should be pressure tested before
backfilling to help reduce the potential for wetting.
Underdrain System: Although free water was not encountered during our exploration,
it has been our experience in the area and where clay soils are present that local perched
groundwater can develop during times of heavy precipitation or seasonal runoff.
Frozen ground during spring runoff can create a perched condition. We recommend
below -grade construction, such as retaining walls, crawlspace and basement areas, be
protected from wetting and hydrostatic pressure buildup by an underdrain system.
The drains should consist of drainpipe placed in the bottom of the wall backfill
surrounded above the invert level with free -draining granular material. The drain
should be placed at each level of excavation and at least 1 foot below lowest adjacent
finish grade and sloped at a minimum 1 % to a suitable gravity outlet. Free -draining
granular material used in the underdrain system should contain less than 2 % passing the
No. 200 sieve, less than 50 % passing the No. 4 sieve and have a maximum size of
2 inches. The drain gravel backfill should be at least 11/2 feet deep.
Surface Drainage: Positive exterior surface drainage is an important aspect of the
project to prevent wetting of the soils beneath the building. The following drainage
precautions should be observed during construction and maintained at all times after the
residence has been completed:
1) Inundation of the foundation excavations and underslab areas should be
avoided during construction. Drying could increase the expansion
H-P GEOTECH
Craig Rogers
January 16, 2002
Page 4
potential of the clay soils.
2) Exterior backfill should be adjusted to near optimum moisture and
compacted to at least 95 % of the maximum standard Proctor density in
pavement and slab areas and to at least 90 % of the maximum standard
Proctor density in landscape areas. Free -draining wall backfill should be
capped with about 2 feet of the on -site, finer graded soils to reduce
surface water infiltration.
3) The ground surface surrounding the exterior of the building should be
sloped to drain away from the foundation in all directions. We
recommend a minimum slope of 6 inches in the first 10 feet in unpaved
areas and a minimum slope of 3 inches in the first 10 feet in pavement
and walkway areas.
4) Roof downspouts and drains should discharge well beyond the limits of
all backfill.
5) Landscaping which requires regular heavy irrigation, such as sod, should
be located at least 5 feet from the building.
Percolation Testing: Percolation tests were conducted on January 10, 2002 to evaluate
the feasibility of an infiltration septic disposal system at the site. One profile pit and
three percolation holes were dug at the locations shown on Fig. 1. The test holes
(nominal 12 inch diameter by 12 inch deep) were hand dug at the bottom of shallow
backhoe pits and were soaked with water one day prior to testing. The soils exposed in
the percolation holes are similar to those exposed in the Profile Pit shown on Fig. 2 and
consist of about 1 foot of topsoil overlying sandy clay to the pit depth of 8 feet. The
percolation test results are presented in Table II. The percolation test results indicate
infiltration rates between 90 and 180 minutes per inch with an average of 120 minutes
per inch. Based on the subsurface conditions encountered and the percolation test
results, we recommend a civil engineer be engaged to design the infiltration septic
disposal system.
Limitations: This study has been conducted in accordance with generally accepted
geotechnical engineering principles and practices in this area at this time. We make no
warranty either expressed or implied. The conclusions and recommendations submitted
in this report are based upon the data obtained from the exploratory pits excavated at the
locations indicated on Fig. 1, the proposed type of construction and our experience in
the area. Our findings include interpolation and extrapolation of the subsurface
conditions identified at the exploratory pits and variations in the subsurface conditions
may not become evident until excavation is performed. If conditions encountered
during construction appear different from those described in this report, we should be
notified at once so re-evaluation of the recommendations may be made.
H-P GEOTECH
Craig Rogers
January 16,2002
Page 5
This report has been prepared for the exclusive use by our client for design purposes.
We are not responsible for technical interpretations by others of our information. As
the project evolves, we should provide continued consultation and field services during
construction to review and monitor the implementation of our recommendations, and to
verify that the recommendations have been appropriately interpreted. Significant design
changes may require additional analysis or modifications to the recommendations
presented herein. We recommend on -site observation of excavations and foundation
bearing strata and testing of structural fill by a representative of the geotechnical
engineer.
If you have any questions or if we may be of further assistance, please let us know.
Sincerely,
HEPWORTH - PAWLAK G ° INC.
,a
f� 2-7' 7 �•
Jordy Z. Adams n, J
Reviewed by:"c'°°°!,'.`.a°°
Steven L. Pawlak, P.E.
JZA/ksw
attachments
H-P GEOTECH
GREEN MOUNTAIN DRIVE
P 1
A
LOT 18
I
I ■
I BUILDING
I PIT 1 ENVELOPE
I I
I I
I I
I I
i I
i
I PROFILE I
I ■ PIT I
P 2�
PIT 2 I
� I 1
r
♦
APPROXIMATE SCALE
1"=50'
P 3.
A
LOT 19
1 101 797 1 GEOTrECHNICALWINC. I AND PERCOLATION ORATORY
TEST HOLES S I EIg' 1 I
PIT 1 PIT 2 PROFILE PIT
0
we=12.9
0
DD=109
—200=95
N
LL=47
a)
PI=31
Li
WC=12.7
WC=9.2
1
5
DD=109
DD=103
5
t
WC=8.9
DD=95
1 10 10 _
LEGEND:
TOPSOIL; sandy clay, organic, slightly moist, brown.
CLAY (CL); slightly sandy to sandy, scattered basalt cobbles, stiff to very stiff, slightly moist
moist, brown, slightly calcareous, slightly porous, medium to high plasticity.
2" Diameter hand driven liner sample.
NOTES:
1. Exploratory pits were excavated on January 9, 2002 with a Cat 420D backhoe.
2. Locations of exploratory pits were measured approximately by pacing from features on the site plan
provided.
3. Elevations of exploratory pits were not measured and logs of exploratory pits are drawn to depth.
4. The exploratory pit locations should be considered accurate only to the degree implied by the
method used.
5. The lines between materials shown on the exploratory pit logs represent the approximate boundaries
between material types and transitions may be gradual.
6. No free water was encountered in the pits at the time of excavating. Fluctuations in water level may
occur with time.
7. Laboratory Testing Results:
WC = Water Content ( % )
DD = Dry Density ( pcf )
—200 = Percent passing No. 200 sieve
LL = Liquid Limit ( % )
PI = Plasticity Index ( % )
101 797 1 GEOWEOCHNICALWINC. I LOGS OF EXPLORATORY PITS Fig. 2 I
3
2
bt
c
_o
c
v
a
x
w
I 0
c
0
1
a
E
0
U
2
1
c
0
c
0 0
a
x
w
I
c 1
0
a,
a�
a 2
E
0
U
N
Moisture Content = 12.7 percent
Dry Density = 109 pcf
Sample of: Sandy Clay
From:Pit 1 at 4 Feet
Expansion
upon
wetting
0.1 1.0 10 100
APPLIED PRESSURE — ksf
of. Sandy Clay
mill■■Sample
E111111111��mm
ni
Dui
�n
�mi
i
0.1 1.0 10 100
APPLIED PRESSURE — ksf
101 797 HEPWORTH—PAWLAK SWELL CONSOLIDATION TEST RESULTS Fig. 3
GEOTECHNICAL, INC.
HEPWORTH-PAWLAK GEOTECHNICAL, INC.
TABLE II
PERCOLATION TEST RESULTS JOB NO. 101 797
HOLE NO.
HOLE DEPTH
(INCHES)
LENGTH OF
INTERVAL
(MIN)
WATER DEPTH
AT START OF
INTERVAL
(INCHES)
WATER DEPTH
AT END OF
INTERVAL
.(INCHES)
DROP IN
WATER
LEVEL
(INCHES)
AVERAGE
PERCOLATION
RATE
(MIN./INCH)
P-1
31
30
9 1/2
8 1/2
1
90
8 1/2
8
1/2
8
8
0
8
7 1/2
1/2
P-2
38
30
9
8
1
180
8
7 3/4
1 /4
7 3/4
7314
0
7 3/4
7 1/2
114
P-3
39
30
8 1/2
7
1 1/2
90
7
6 3/4
1 /4
6 3/4
6 1/2
1/4
6 1/2
6
1/2
Note: Percolation test holes were hand dug in the bottom of backhoe pits and soaked on
January 9, 2002. The percolation test holes were covered with rigid foam insulation to
protect against freezing. Percolation tests were conducted on January 10, 2002. The
average percolation rates were based on the last three readings of each test.
C
1
5
0
7
Moisture Content = 8.9 percent
Dry Density = 95 pcf
Sample of: Sandy Clay
From: Pit 2 at 6 Feet
No movement
upon
wetting
0.1 1.0 10 100
APPLIED PRESSURE — ksf
101 797 HEPWORTH—PAWLAK SMELL CONSOLIDATION TEST RESULTS Fig. 4
GEOTECHNICAL, INC.
r-
rn
r
0
O
z
m
O'
F-
-J
D
U)
W
VJ
w
LL
O
a
�
x F
o
J V
U
�
O 2
m
c
ca
m
U
U
U
A
'D
>
_0
—
t0
(m
m
co
N
In
N
❑ w
w 7 _
F
LL W Z LL
oa ¢ aN
Z 0 ~n
D O
U
U X
F
a o o
J z —
`—
M
�
J
a
cc
W
W
J
V
L�o
W ? N �
N
LO
N a y
a a Z
Qo
Z
O
N
F-.
Q
❑
Q
cc
iJ
J
w
>o
a
C¢'J
a
F' o z a
dT
O
0)
O
co
O
�
2
a-
o w —
N z o
CT)
i-I
N
cy)
a o o
2 Z U
N
r
N
m
00
Z
O
=
w w
CO
<
❑
U
O
J
W
J
g
Q
N
z
F
.—
N
0
m
ISDS Permit # as �l� Date I v
Tal Insoeet on
Ceteness jForm
= Tank is Son gal. Tank Material
Tank is located a ,S" ft. and Ilb degrees
—.� (ps....ec 1�eaostl
Tank is located ft. and degrees from
{puzomma of �.na..rtcl
IX Tank set level. Tank lids within 8" of finished grade.
V" size of field 2L327 ft2units %gj�� lineal ft_
. Technology �dc•� -.� I,� ��S
�Cleanout is installed in between tank and house(+ 1/100ft).
"-""There is a "T" that goes down, 14 inches in the inlet and
outlet of the tank:
.Inlet. and outlet is sealed with tar tape, rubber gasket etc.a� 4NS'i� o,f
T k has two =.dmpartments with the.;=•7��yege -.-:c pa tment closest to the..,:;,.t1i
house.
M+dcsa*ttre di Lance and relative direp aA to:; €a.elA,
Z Depth of field. 3-1 ft _
-Soil interface raked.
Inspection portals at the -end of each trench..
Proper distance to setbacks.
Chambers properly installed as per manufacturers specifications.
(Chambers latched, end plates properly installed, rocks 'removed from
/trenches, etc.)
✓ Type of pipe used for building sewer Line!SOf leach fiel .�.
Other
Inspection meets reauirementn.
.4 .
—_ Copy form to installer's file if reeomendations for improvement Pere
suggested.
ACTION TAKW :
setbacks
Well Potable House Property Lake Dry Tank Drain
Water Lines line Stream Gulch
Field 100
25
20
10
50
25 10
10
50
10
5
10
50
10 *
10
- ESE--COUNTY-Siff; RML-FH
P.O. BOX 179
EAGLE, CO 81631
YMUUUC; 1104-1 JWAWII]tel11 Cam- 1 TiMPlV IV[ I. 1---Ll—�-OVIF(L}O.lOV
SHEET NO Dp
CALCULATED BY.
DATE
CHECKED BY DATE
SCALP
IL
vol
4 wM1.
0
�����
'�i y� i GrjT•.LY�j`_T.j � "]�(.1'�� -+a � i 1J. y.. �J_
- yi ••/`�`.�\ F1�.. -. � ��5 �y� Z,,. �� _ I• \ i�i lrr� ✓�,,r KR � � •'�•�
•hri �i ";ill � .) t I 1 ,yt� �/�!,,�r s=�W��'�Y•r' s ( �. �i _' j � � � � �'T _ •it 3 •
Or
a iy 41 t �,_. i ,, `�� j1 j� .I ,•� _ A �- f �i ` t•?-L L"rCF/
At
_ ' � ` S• `i, -ilk • ! ,� � � _ , r _ yi. v` � ` .; `- Y,e :.
"'i 4.. J ��4`. � � is i � .�•" 'tit + 'a r �
��i
•# G r'KK.
• � � try .' ' �� „R.,,.•.. - �•, ,�i*, ... •-� 1,.
f�`.' - _ •tip _ ti
era-'ti�•�, ♦♦YY � •�...
2203-02 Tax #2391=214-03-001
JOB NAME Lot #18, Sopris Mesa ROGERS
850 Green Meadow Drive, Carbondale
JOB NO,8 P — )L
OB
BILL TO
DATE TART`ElD
DATE COMPLETED
DATE BILLED
Z
v
! ' . ' ` -" r
V'Ar_e�-7nosl
r < 6 n
166"s '00
r
UA 'L N1 . Z C/ JQ&.
l Ova 1 -- r I�. f 0
,
cm
4 0
_
JOB COST SUMMARY
TOTAL SELLING PRICE
r 1.
TOTAL MATERIAL
oe
r G(/-- i� �l r.-�, .�
�S 6� --7�-�
_ TOTAL LABOR
INSURANCE
Iuu
SALES TAX
.
MISC. COSTS
i � I
I'd '�^ T /� Ivsr ry s !
TOTAL JOB COST
rrn v vi c s',Low .� ,� -�
GROSS PROFIT
�r
LESS OVERHEAD COSTS
% OF SELLING PRICE
-
NET PROFIT
JOB FOLDER Product 278 ;� t .i �yvc r� j� `ti l <, 7 f in c1�— y ei i U! —JOB FvOLDli§
on. -Me Emma
II
Ij I
--
• ,�
�
-=
� � T `
r"'•
',
,�
_ _ r
Y `_�� -
ARM
I
N •
Q—
JO��h.�-
85
Printed In U$.A
a,
6072
�s
1�
J
40 a `
Recycled Content
10% Post•Consumer
GREEN MEADOW DRIVE<
Av%LT JA
7130
O \
O \
ULIN I KAL KAIN UI--1
\ 20' TRAIL
EASEMENT
PROPERTY
BOUNDARY
i
GRAPHIC SCALE
20 0 10 20 40
( IN FEET )
1 inch = 20 ft.
t£
3
a
t
SAME
MINTY
T
H
.F
F
s
Ot low"
2
n
1 SITE
PaAIN
4
:.
.
`
k
IM
.
Now
r
n
t '.•
I :.:
A -.
::
" is
cops �
Y
i
t
.:..:
•
.:
k
!
...
Am 7
21
r:#
VICINITY MAP
SCALE: 1 "=2000'
C4ENEPAL NOTES
1. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE EAGLE COUNTY
REGULATIONS OF INDIVIDUAL SEWAGE DISPOSAL SYSTEMS, EVEN THOUGH
ALL SUCH REQUIREMENTS ARE NOT SPECIFICALLY NOTED ON THE DRAWINGS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR SUCH SPECIFIC DETAILS AS
ARE REFERRED TO IN THE ABOVE MENTIONED REGULATIONS.
2, FLOW FOR BED:
6 BEDROOMS * 2 PERSONS/BEDROOM * 75 GALLONS/PERSON/DAY IS:
900 GPD = AVERAGE DAILY FLOW.
DESIGN FLOW = 1.5 * AVERAGE = 1350 GPD (Q)
***INCREASE BY 20% FOR USE OF GARBAGE GRINDER, Q=1620 GPD***
SEPTIC TANK:
MINIMUM TOTAL TANK SIZE:
Q * 1 DAY/24 HRS * 30 HRS = 2025 GPD
INSTALL ONE 2500-GALLON CONCRETE TANK WITH BAFFLE
***INSTALL EFFLUENT FILTER IN SEPTIC TANK OUTLET***
STANDARD ABSORPTION AREA:
A = DESIGN FLOW APPLICATION RATE BASED ON PERCOLATION
APPLICATION RATE TEST RESULTS OF 16, 23 AND 26 MPI.
1620 GPD = 2383 SF
0.68 GPD SF
USE OF STANDARD INFILTRATOR UNITS IN TRENCH CONFIGURATION:
50% REDUCTION- (2383 S.F.*0.50) ® 15.5 S.F,/UNIT,
77 UNITS REQUIRED. INSTALL 5 ROWS AT 16 UNITS PER ROW.
3. CLEAN OUTS ARE REQUIRED AT ALL BENDS AND AT LEAST EVERY 100
FEET ALONG THE HOUSE SEWER.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING ALL
WATER TIGHT COMPONENTS, PRIOR TO THE ABSORPTION AREA,
TO PREVENT INFILTRATION.
5. TOPSOIL COVER MAY BE VARIED (WITH 1 FOOT MINIMUM) TO ALLOW
LANDSCAPING.
6. INSTALL RISERS AS NECESSARY TO BRING ALL ACCESS POINTS TO
WITHIN ONE-HALF FOOT OF FINAL GRADE.
7. LOCATIONS OF ALL COMPONENTS MAY BE VARIED AS NECESSARY AS LONG
AS ALL MINIMUM DISTANCES AND SLOPES MEET THOSE REQUIRED.
8. PROVIDE POSITIVE DRAINAGE OF SURFACE WATER AWAY FROM ABSORPTION
FIELD AREA USING DRAINAGE SWALES AS NECESSARY.
9. SOILS AND PERCOLATION INFORMATION PROVIDED BY H.P. GEOTECH,
JOB #101 797, DATED APRIL 23, 2002.
10. THIS DRAWING DOES NOT CONSTITUTE AN ISDS PERMIT. PERMIT MUST BE
OBTAINED FROM APPROPRIATE CITY OR COUNTY OFFICIALS.
ENGINEER MUST OBSERVE CONSTRUCTED SYSTEM BEFORE BACKFILL
AND PROVIDE REPORT TO COUNTY.
11. THIS SYSTEM IS SIZED FOR TYPICAL DOMESTIC WASTES ONLY, BACKWASH
OR FLUSHING FLOWS FOR REVERSE OSMOSIS UNITS OR WATER SOFTENERS
OR FILTERS SHOULD NOT BE INTRODUCED INTO THIS SYSTEM.
12. SITE PLAN INFORMATION FROM MATA DESIGN COMPANY, VIA EMAIL, MAY 15, 2002.
13. INSTALL BLUEBOARD INSULATION OVER SEWER PIPE WHEREVER DEPTH IS
LESS THAN 5.0 FEET,
14. THE ENGINEER SHALL BE CONTACTED FOR SITE INSPECTION PRIOR TO
BACKFILLING OF SYSTEM COMPONENTS.
15. DESIGN OF ABSORPTION TRENCHES BASED ON SOIL PROFILE INDICATING
1' TOPSOIL OVERLYING SANDY CLAY TO A PROFILE DEPTH OF 8-FEET,
SAL AB30RP 110N TRENCH NOTES
1. ABSORPTION LATERALS SHALL NOT EXCEED 100-FEET IN LENGTH.
2. THE BOTTOM OF EACH ABSORPTION TRENCH SHALL BE LEVEL.
3. DRAINAGE SWALES ARE TO BE PROVIDED ABOVE AND AROUND TRENCHES, AS
NECESSARY, TO PREVENT SURFACE RUNOFF FROM ENTERING ABSORPTION AREA.
4. TRENCH LATERALS SHALL FOLLOW CONTOURS.
5. INSTALL INFILTRATOR IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
6. TRENCH BOTTOM AND SIDEWALLS MUST BE RAKED TO REMOVE SOIL SMEARS
INCURRED DURING EXCAVATION,
7. NO EXCAVATION OF ABSORPTION FIELD IS TO BE DONE DURING WET WEATHER
AND USE OF RUBBER TIRE VEHICLES OVER ABSORPTION AREA IS PROHIBITED
it BOULDERS EXISTING WITHIN THE TRENCH SHALL BE EXCAVATED AND
BACKFILL SHALL CONSIST OF ONSITE SELECT OR PIT -RUN MATERIAL.
9. IN ALL TRENCH CONFIGURATIONS, SERIAL DISTRIBUTION SHALL BE USED
INSTEAD OF EQUILATERAL DISTRIBUTION TO INCREASE SETTLING TIME AND
PROTECT THE BACTERIAL BIO-MAT.
10. BEND IN TRENCH SHALL BE MADE WITH END PLATES AND 4"0 PVC OR
MANUFACTURER'S PREFABRICATED BENDS.
m
z
O
U)
W
ry
W
Q
O
z
N
z
J
`I
V
W
w
Y
Q
p
U
n
c0
U co
z°
_ co
Wcm
Z
W 8
609
z w8cqc
C�
W w�
0
70
Z co
� z��
O Q�00 �
Y
U
O 0,
0 V
m
PW�s
I ,00L
411
Q
Lw
Q
Goo
Q
� U5
_ _
O
m
j
m
W�
O
d
�<
0Cp
z
W
w
0
c�
�C)
U
Q
U�
w
rc
55
W�
w
o
adb
~
�
0
cc
Z
PROJECT NO.
2021054.0218
SHEET 1