Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout167 Golden Bear Dr - 210716302016INDIVIDUAL SEWAGE DISPOSAL SYSTEM PERMIT
EAGLE COUNTY ENVIRONMENTAL HEALTH DIVISION
P.O. Box 179 - 500 Broadway • Eagle, CO 81631
Telephone: (970) 328-8755
COPY OF PERMIT MUST BE POSTED AT INSTALLATION SITE. PERMIT NO. 2051-00 BP NO. 13446
OWNER: ARDEN DEVELOPMENT CO./ CROSSFIRE OF VAIL, LLC PHONE: 970-949-9232
MAILING ADDRESS: P.O. BOX 1412, AVON, CO 81620
APPLICANT: ROB HANEY PHONE: 970-949-9232
SYSTEM LOCATION: 166 GOLDEN BEAR DRIVE, EDWARDS, CO TAX PARCEL NO. 2107-163-02-010
LICENSED INSTALLER: S. RUDER EXCAVATING, STEVE RUDER LICENSE NO. 33-00 PHONE: 970-926-1056
DESIGN ENGINEER: LKP ENGINEERING, LUIZA PETROVSKA PHONE NO. 970-926-9088
INSTALLATION HEREBY GRANTED FOR THE FOLLOWING: MINIMUM REQUIREMENTS FOR A 4 BEDROOM RESIDENCE
1250 GALLON (DESIGN CALLS FOR 1500) SEPTIC TANK, 1488 SQUARE FEET OF ABSORPTION AREA CREDIT VIA 48 INFILTRA-
TOR UNITS AS PER ENGINEER'S DESIGN.
SPECIAL REQUIREMENTS: INSTALL AS PER ENGINEER'S DESIGN DATED 5/3/00. MAINTAIN ALL APPLICABLE SETBACK REQUIRE-
MENTS, AND DO NOT INSTALL IN WET WEATHER.. ENGINEER IS RESPONSIBLE FOR FINAL INSPECTION. DO NOT BACK FILL
ANY PART OF THE INSTALLATION UNTIL THE ENGINEER HAS INSPECTED AND APPROVED IT. THE BUILDING CERTIFICATE
OF OCCUPANCY WILL NOT BE ISSUED UNTIL THE SEPTIC SYSTEM HAS BEEN APPROVED.
ENVIRONMENTAL HEALTH APPROVAL: LAURA FAWCETT DATE: NOVEMBER 6, 2000
CONDITIONS:
1. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM
REGULATIONS, ADOPTED PURSUANT TO AUTHORITY GRANTED IN 25-10-104, 1973, AS AMENDED.
2. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS. CONNECTION TO, OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND
BUILDING DEPARTMENTS SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT, AND WILL RESULT IN BOTH
LEGAL ACTION AND REVOCATION OF THE PERMIT.
3. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL
SYSTEM TO BE LICENSED.
FINAL APPROVAL OF SYSTEM (TO BE COMPLETED BY INSPECTOR):
NO SYSTEM SHALL BE DEEMED TO BE IN COMPLIANCE WITH THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL
SYSTEM REGULATIONS UNTIL THE SYSTEM IS APPROVED PRIOR TO COVERING ANY PORTION OF THE SYSTEM.
INSTALLED ABSORPTION OR DISPERSAL AREA: 1488 SQUARE FEET (VIA 48 INFILTRATOR UNITS. AS PER ENGINEER'S DESIGN)
INSTALLED CONCRETE SEPTIC TANK: 1500 GALLONS IS LOCATED 218 DEGREES AND 19 FEET 6 INCHES
FROM THE CLEANOUT ON THE SOUTH SIDE OF THE HOUSE.
COMMENTS: THE FINAL INSPECTION WAS DONE BY LAURA FAWCETT OF EAGLE COUNTY ENVIRONMENTAL HEALTH AND THE
DESIGN ENGINEER ON 5/30/04. THE ENGINEER'S FINAL CERTIFICATION WAS RECEIVED ON 6/4/03. PHOTOS OF THE RISER RINGS
ON THE TANK RECEIVED ON 2/24/04. THIS SYSTEM IS LARGE ENOUGH FOR A FOUR BEDROOM RESIDENCE.
ANY ITEM NOT MEETING REQUIREMENTS WILL BE CORRECTED BEFORE FINAL APPROVAL OF SYSTEM IS MADE.
ARRANGE A RE -INSPECTION WHEN WO IS COMPLETED.
ENVIRONMENTAL HEALTH APPROVAL DATE: MARCH 9, 2004
SENT BY: 10-31- 0 ; 17:54 ;CommunityDeveiopment-j ;# 2/ 6
I nCOMPlete APPlicationg Will NOT Be Accepted
.(Site Plan ]lYli'UST be attached)
ISDS Permit # J
Building Permit ##
APPLICATION FOR INDIVIDUAL SEWAGI� DISPOSAL SYSTEM PERMIT
ENVIRONMENTAL HEALTH OFFICE - EAGLE COUNTY
P. O. BOX 179
EAGLE, CO 81631
32B=8755/927-3823 (El Jebel)
*******,r*****�rrr�rve*w�r�i*w�rx�t�*•x**************t*,r�r********�r****�r*x�r*yr*�r�rrrrr***
* FEE SCHEDULE
* PERMIT APPLICATION FEE $150.00 PERCOLATION TEST FEE $200.00
* SIZING AND SITE V-1SIT FEE $85.00 (WHEN ENVIRONMENTAL HEALTH SIZES THE
* SYSTEM USING YOUR SOILS PXPOR.T)
* MAKE ALL REMITTANCE PAYABLE TO: "EAGLE COUNTY TREASURER"
PROPERTY OWNER: C'"SppSPi %kS OP 1 AA L- pW L--
MAILING ADDRESS. P© I�nX. l 2- .•.•-"ry SLE) 20 VTY PHONE: W el -et 231
APPLICANT/CONTACT PERSON: ?4T>' A"*'-j
LICENSED SYST2MS CONTRACTOR: RAE - EACA%AgTPO
PHONE: ;�(-
PHONE!
COMPANY/DBA : ADDRESS: 040 '�>0 Y 114 12 . ) 'V OLAJ
PERMIT APPLICATION IS FOR: �0 NEW INSTALLATION ( ) ALTERATION ( ) REPAIR
LOCATION OF PROPOSED IND
Legal Description:
Tait Parcel Number: Z�o"i L OS 02- 01 Q LotSize: 2 • �5� /4 �.
Physical Address:
Buri'DIN[; TYPE: (Check applicable category)
(� Residential/Single Family Number of .Bedrooms 1+
( _) Residential/Multi-Family* Number of Bedrooms__
( ) Commercial/Industrial* Type
*These systems require design by a Registered Professional Engineer
TYPE OF WATER SUPPLY: (Check applicable category)
( ) Well ( ) S r'n ( ) Surface
(7,� Public Na of S 1'a
APPLICANT SIGNATURE: Date: 01jOV 2- 2-000
�F it Yt Yt Yt 'k 7k �k At 5Y 'k -k 7k is �F Yr k * � � �Ik ����t) it k Ye W * et �F dr tk �F dr * �k 51r * Ye •k * �e k 'k •!t •k tk * k !r �e Ye Ye Yr Ye Ye Ye �!r'k. Yt 9t �F •/r it * * Ir * it
/ GZi
AMOUNT PAID : f S� RECEIPT # : (� DATE:
CHECK # : 4 CASHIER:
DEPARTMENT OF
ENVIRONMENTAL HEALTH
(970)328-8755
FAX: (970) 328=8788
TOLL FREE:800-225-6136
www.eaglecounty.us
March 9, 2004
Arden Development Company
Attn: Rob Haney
P.O. Box 1412
Avon, CO 81620
EAGLE COUNTY
RAYMOND P. MERRY, REHS
Director
RE: Final of ISDS Permit #2051-00, Tax Parcel #2107-163-02-010. Property location:
166 Golden Bear Drive, Edwards, CO.
Dear Mr. Haney:
This letter is to inform you that the above referenced ISDS Permit has been inspected and
finalized. Enclosed is a copy to retain for your records. This permit does not indicate
compliance with any other Eagle County requirements. Also enclosed is a brochure regarding
the care of your septic system.
Be aware that later changes to your building may require appropriate alterations of your septic
system.
If you have any questions regarding this permit, please contact the Eagle County Environmental
Health Division at (970) 328-8755.
Sincerely,
Janet Kohl
Eagle County Environmental Health Department
ENCL: Educational Brochure
Final ISDS Permit
cc: files, March 2004 Chrono file
500 Broadway, P.O. Box 179, Eagle, Colorado 81631-0179
Community Development Department
(970) 328-8730
FAX (970) 328-7185
TDD (970) 328-8797
Email: eccmdeva@vail.net
http: //www.eagle-county.com
EAGLE COUNTY, COLORADO
Date: November 6, 2000
TO: S. Ruder Excavating
Eagle County Building
P.O. Box 179
500 Broadway
Eagle, Colorado 81631-0179
FROM: Environmental Health Division
RE: Issuance of Individual Sewage Disposal System Permit No.2051-00. Property
Location: 166 Golden Bear Drive, Edwards, CO., Arden Development Co.
property.
Enclosed is your ISDS Permit No. 2051-00. It is valid for 120 days. The enclosed copy of the
permit must be posted at the installation site. Any changes in plans or specifications
invalidates the permit unless otherwise approved. Please note any special requirements
that may have been added to the design by this department.
Systems designed by a Registered Professional Engineer must be certified by the Engineer
indicating that the system was installed as specified. Eagle County does not perform final
inspections on engineer designed systems. Your TCO will not be issued until our office
receives this certification.
Permit specifications are minimum requirements only, and should be brought to the property
owner's attention.
This permit does not indicate conformance with other Eagle County requirements. Please
notify this office if you have not been contracted to perform this installation.
If you have any questions, please feel free to contact the Environmental Health Division at 328-
8755.
cc: files
LKP Engineering, Luiza Petrovska
u �+r V-�r �.+.+.+ �++J•�.J JrCJJLV JVVJ
ILK ' Engineering, Inc.
CIVILIGEOTI;CHNICAL
June 2, 2003
Rob Heaney
Arden Development
P.O. Box 1412
Avon, CO 91620
Dear Rob:
"MF G11UJ_1VGGIC1111U 111I41
RE: Inspection of Septic System Ynistailatinn
Lot 15, Bloch 2, Cordillera Filing No. 36
167 Golden Pear .Drive
Eagle County, Colorado
Project No. 2082 - ISDS Permit No. 20511-00
rHut U1
At your -request and at the request of Steve Ruder on May 27 and 28, 2003, we visited the
construction site on Lot 15, Block 2, Cordillera Filing No. 36, 167 Golden Bear Drive, Eagle
County, Colorado. The purpose of our site visits was to inspect the installation of the septic systems.
They installed the system in overall compliance with the septic systems, design, Drawing No.
2082SD.DWG, elated May 3, 2000, as shown on the attached as -built sketch. They installed a 1500-
gallon, two compartments, a precast, concrete septic tank. 'Elie septic tank will have 8 feet of risers to
bring the covers to within S inches of the finished grade. A, cleanout Was installed between the douse and
the septic tank.
Forty-eight, Standard infiltrator Chambers were installed in three trenches. The first trench, next
to the west property line, had 18 infiltrators with a 6-foot separation between the first two and the last
sixteen, infiltrators. The middle trench had sixteen infiltrators, a six-foot separation and than two more
infiltrators, The last and easternmost trench had twelve infiltrators. The infiltrators were connected with
serial distz-ibution. In the first and last infiltrator of each trench, inspection ports were to be installed. The
effluent litre was 4-inoh SDR 35 PVC.
If you have any questions, please do not hesitate to call.
Sinc=ely,
LKF Engiitacexain
29526
Luiza Petro sl[a,
President .r`-�.- .•`'t
Enclosure
cc: Mrs. Laura Fawcett, Eagle County Building Department, fax: 328-0349
C AW P 1 o-LXM 082osi. wpd
P.O. Box 2$37, Edwards, CO 81632, (970) 926-9088 Tel, (970) 926-9089 Fax
TI IM_d_CDM= I.IC'M MO- Ml e)M TTr- =n _'1 C rill lf,17V Chill UCni 7U mne'C. -1
—— _ _ _— -- ..1...r1 r...i..n"u o v•a---vvzv Im if lY
f
• f.
Engineering, Inc.
CTvx/r'EOTECIi %C: ' .
SOIL AND FOUNDATION INVESTIGATION
FOR
PROPOSED RESIDENCE
LOT 15, BLOCK 2, CORDILLERA FILING NO.36
GOLDEN BEAR MEADUWS
EAGLE COUNTY, COLORADO
PROJECT NO. 99239
29,1999
j j'zj. qq
2M
PREPARED FOR:
MR. DRREK TURNER, TRUSTEE
THE TURNER REVOCABLE TRUST
2000 SE 1571 STREET, BLDG 450
EDMOND, OK 73013
E.O. Dox 2837, Ldwards, CO 81632, (970) 926-9089 Tel, (970) 926-9089 Nix, E-mail: lkpeng@&uowcap.net
&uowcap.nct
Nnu-P-PMA TNI 1 1 P: 7�7PM Tn! PQr I P rn INTY PWIJ W1=01 TW onr_c. 4
TABLE OF CONTENTS
EXECU IVE SUMMARY ... . - -
SCOPE OF STUDY .... .. . .
SITE DESCRIPTION
PROPOSED CONSTRUCTION .... , , .
FIELD INVESTIGATION . . .
SIJBSURFACE SOIL AND GROUNDWATER CONDITION . ...........
FOUNDATION RECOMM:ET�IDATlONS
SLAB CONSTRUCTION .. .....
RETAINING, WALLS.
UNOERDRAIN SYSTEIVI...
SITE GRAVING AND DRAINAGE .. .
LAWN IRRIGATIDN ... .... .... .... , .. , .....
6
LIMITATIOTd . , .. , .... . .
FIGURES
LOCATION SKETCH ... .... • .... ..... ... . . .... DRAWING NO. t
SUBSURFACE. EXPLORATIOIq LOC3S........ ... , FI4iURE Na'S I-2
SWELL -CONSOLIDATION *"EST RESULTS... • , .... .
. ,_..._...FIGUREIYO's3&4
PERIMETER DRAIN ..... ..... . ........... . . . . . ..FIGURE NO. 5
NjntJ-P-aGlPM TPII 1P-77PM Tn—Pnf-�I P rniIFJTV Phll1 WPCI Tu onr-o-o
EXECUTIVE SUMMARY
The proposed residence should be supported with
conventional type spread footings, designed for an
allowable soil bearing pressure of 3000 psf and a
minimums dead lead of 1000 psf. They should construct
the footings on the undisturbed, sandy clay to clayey -
sandy gravel. See Foundation Recommendations.
SCOPE OF STUDY
This report presents the results of it subsurface Soil and Foundation Investigation for a
proposed residence to be constructed on Lot 15, Block 2, Cordillera Filing No, 36, at Golden
Bear Meadows, Eagle County, Colorado, The purpose of the subsurface soil and foundation
investigation was to determine the engineering characteristics of the foundation soil and to
provide recommendations for the foundation design, grading, and drainage.
SITE DESICRIPTION
Lot 15 is a 2.957-acre lot, at 0878 Golden Bear Meadows off The Summit Trail, west of
the intersection with Sage Grouse Trail, in Cordillera, Eagle County, Colorado. The lot is on the
south side of the road. The topogrrdphy is moderate, changing to steep south of the building
envelope. Vegetation can the lot consisted of sage brush and grass with outcropping of basalt
rock. Drainage is to south. Lot 15 and the surrounding lots are vacant.
LKP Engineering, Inc.
wnt I-a-aPMM TWI 1 1 P • 77PM Tr) - COf l 17 f`ni WTV CIJI I U=nl Tu
-- - - -- ----•-••----• -I-- .... I----- ---------- - -1 -
3
PRO POSED CONSTRUCTION
We have assumed that the proposed residence will consist of a two story, woad frame
construction, with a walkout basement, on a concrete foundation, Loads are anticipated to be
light, typical of residential construction.
If the finalized plans differ significantly froth, the above understanding, they should notify
us to reevaluate the r0conunendations of this report.
FI LD INVESTIGATION
The field investigation conducted on November ill, 1999, consisted of drilling, togging
and sampling two test borings, The test boring locations are shown on Drawing No. 1. Drilling
of the test borings was done with a 4-inch diameter, continuous flight, a power auger, on a track
mounted drill rig, We shore the soil profiles of the test borings on the Subsurface Exploration
Hogs, Figure No's one and two. Soil samples for laboratory soil analysis and observation were
taken at selected intervals by advancing Standard Split Spoon and California Samplers with a
140-pound hammer, falling 30 inches.
SUBSURFACE SOIL AND GROUNDWATER CONDITION
the soil profiles encountered in the test borings were not uniforru.<Bonng No,,,1 had one
foot of topsoil over brownish -red, sandy gravel with basalt boulders. Practical drill rig refusal
was encountered in Boring No. 1 atK3:5,fe t on basalt rocks, Boring -No. 21had 2 feet of topsoil
over light, reddish -brown, sandy clay. Basalt rocks were encountered at 19 to 25 feet, We did not
encounter ground water at the time of drilling.
We sampled the soil in the test borings at random intervals. The laboratory test results are
shown on Figure No's 3 and 4.
Preliminary Geologic Site Assessment and Preliminary Geotechnicai Engineering Study
for Filing 36, 'was not available for our review.
T.XP' F�ngiineerihats Ii u.
mni I-P-,?TilMM TI-II I I P- 77PM Tn - P rni IWTV GKll 1 UPON TI-I PCtf G- a
4
FOUNDATION RECOMMENDATIONS
The proposed residence should be supported with conventional type spread footings,
designed for a maximum allowable soil bearing pressure of 3000 psf and a minimum dead load
Of 1000 psf. The footings should be placed on the undisturbed, clayey -gravelly soils.
Continuous foundation walls should be reinforced top and bottom to span an unsupported.
length of at least 10 feet, A minimum of. 48 inches of backfill cover is recommended for frost
Protection of the footing subsoils. The undersigned engineer should observe the foundation
excavation to verify that the soil conditions are uniform throughout the foundation excavation.
The foundation excavation should be free from excavation spoils, frost, organics and
standing water. Voids left in the excavation, due to rock removal, should be filled with lean
concrete. Footings should be constructed on a level surface.
SLAB CONSTRUCTION
The on -site soils exhibited low to modcratc swelling potential. The soils, however, were
not uniform over the site. If the proposed slab -on grade is within the soils with low W moderate
swelling potential, a structural fluor slab should be constructed. As another alternative, the soil
beneath the slab can be overexcavated 3 feet and replaced with a structural fill, consisting of non
swelling soil, approved by the engineer. They should backfill overexcavated soft spots and other
underslab fill with non swelling soil, free from topsoil, organics, and rock fragments greater than
3 inches. The fill should be compacted to a minimum of 95 percent of the nmimurn standard
Proctor density (ASTM D-699).
The concrete slab should be constructed over a 4-inch layer of clean gravel consisting of -
3I4 inch gravel with at least 50% retatned on the No. 4 sieve and less than 3 percent passing the
No. 200 sieve.
They should reinforce the concrete slab -on -grade and score control joints according to the
American Concrete Institute requirements and per the recommendations of the designer to reduce
damage due to shrinkage. If the homeowner is aware Of the swelling soils and the damages
LIT Fnsxineerina inr
Nnu-?-?ROR THI I 1 P: - FAPM Tn: Par.1 F f ni 1WTY PWIJ WP7ni TW oC)r_7. CZ
' S
associated with swelling soils are acceptable, slab on grade can, be constructed The concrete slab
should be separated from the foundation walls and columns with expansion joints to allow for
independent movement,
RETAINING WALLS
They should design foundation walls retaining earth and retaining structures that are
laterally supported to resist an equivalent fluid density of 70 pef for an -at-rest" condition.
Laterally unrestrained structures retaining the ern -site earth should be designed to resist an
equivalent fluid density of 50 pef for the "active" case.
The above design recommendations assume drained backfill conditions and a horizontal
backfill surface. Surcharge loading due to adjacent structures, weight of temporary stored
construction materials and equipment, inclined backfill and hydrostatic pressure due to
undrained backfill should be incorporated in the design. They should try to prevent the buildup
of hydrostatic pressure behind the retaining wall.
>[ NDEltDRAIN SYSTEM
To reduce the risk of surface water infiltrating the foundation subsoil, installation of a
foundation perimeter drain is recommended. The foundation perimeter drain should consist of a
4-inch diameter- perforated pipe sloped to a suitable gravity outlet. The drain should slope at 1/4
inch per font if flexible or at 1 /S of an inch if rigid pipe is used. The bottom of the trench
adjacent to the footing should be lined with a polyethylene moisture barrier glued to the
foundation wall. The drain pipe should be placed over the moisture barrier and covered with a
minimum of 6 inches of -3/4 inch free -draining granular material. Geo#extile (Mirafi 140N or
equivalent) should be, used to cover the free -draining gravel to prevent siltation and clogging of
the drain. The backfill above the drain should be granular material to within 2 feet of the ground
surface to prevent a buildup of hydrostatic pressure, The top one foot of the backfill material
should consist of a relatively impervious fill. The backfill shotild be sloping away from, the
LKP Engineering, Inc.
Kini 1-P-PfnfiM TWI I 1 P- 7PPM Tn- i=n .`I F rni [MTV PWIJ WPOI TI4 PAGP: F,
building.
SITE; GRADING AND DRAINAGr,
In
The site surrounding the building structure should slope away from the building in all
directions. A minimum of 12 inches in the first 10 feet is recommended in unpaved areas, and
three inches in the first 10 feet in paved areas. The top of the granular foundation backfill
should be covered with a minimum of 1 foot of relatively impervious fill to reduce the potential
Of surface water infiltrating the foundation subsoils.
Surface water naturally draining toward the proposed building site or toward permanent
cuts, should be diverted around and away from them by Means of drainage swales or other
approved methods. The roof drains and downspouts should extend and discharge beyond the
limits of the back1711. Exterior backfill should be compacted at or near the optimum moisture
content to at least 95% of the maximum standard Proctor density under pavement, sidewalk and
patio areas and to at least 90a/a of the maximum standard. Proctor density under landscaped areas.
Mcchanical methods of compaction should be used. Do not puddle the foundation excavation.
DAWN IRRIGATION
It is not recommended to introduce excess water to the foundation soils by installing
sprinkler systems next to the building. The installation of the sprinkler heads should insure that
the spray from the heads will not fall within 10 feet of foundation walls, porches or patio slabs.
Lawn irrigation must be controlled.
LIMITATION
This report has been prepared according to locally accepted Professialnal Geotech lical
Engineering standards for similar methods of testing and soil conditions at this time. There is no
other warranty either expressed or implied.
T.T�p F'ng'cnewring, iriU.
mnt 1-D-Dfilnn Twi 1 1 D • 7DDM Tn • Cnr-1 C f-fill Ih ITV C'hll I U=nl TU mnr=' . -7
The findings and recommendations of this report are based on field exploration,
laborataxy testing of samples obtainod at the specific locations shown on the Location Sketch,
Drawing No.1 and on assumptions stated in the report. Soil conditions at other locations may
vary, which may not become evident until the foundation excavation is completed, If sail or
water conditions seem different from those described in this report we should be contacted
immediately to reevaluate the recommendations of this report.
This report has been prepared for the exclusive use of 11+Ir. Derek Turner, Trustee, The
Turner Revocable Trust, for the specific application to the proposed development on Lot 15,
Block 2, Cordillera Filing No. 36, at Golden Bear Meadows, Eagle County, Colorado.
Sincerely, �Qq A��'1��;,rr
• r
LKP FNGINEERIN r' pErgq&�,
s Ir• *-. d,K
29526 ■ �a
uiza Petrovska, ICE
President
C:W1yFIIckDrildatlW PDOChAY92S95W.rpi.wpd
LISP Engineering, Inc.
7
wntl-P-PRP li TWI1 4P-7PPM Tfl-Faf'9 P rni[MTV F:MtJ Wl:nl TW G0I-•1:"•Q
WntJ-P-rMMM TPI 1 1 P- 7QPM TI1- POf:.`I P MI IMTV PWI I I-Il=OI TW onr_c:. 0
DATE~ DRILLED: Novomberl$, 1999 BORING NO. I
ELEVATION-.
S
S
C�L:'P'I7-I
BLOWS
M
A
M
DFSCRIPTiON OF MATERIAL
LABORATORY
FEET
PER Fr.
a
P
AND SAMPLE LOCATION
TEST RESULTS
REMARKS
a
L
Topsail
6 inches of frost
F-5
Brownish red sandy grave[
P;
with basalt boulders
sal at 3S feet
No ground water
encountered
... 15
--. 20
--30
---- 35
LEGEND.
0 2-inch 0,1). California Liner Sample (relative►y undisturbed sample)
IN 1-3/8-inch [.D. Split Spofln Sample, (disturbed ;ample)
241I2 D6vc sample blow count. Indicares that 24 blowy of a 140-pound hammer falling 30 inches were
required to drive ilia California or the Split Spoon Sampler 12 inches.
DD - Natural Dry Density (pol)
MC - Natural Moisltxc Cgptent
-200 - Percent pa9sing No. 200 sieve
LL - Liquid Limit
PI Plasticity Index
G.W Ground Water
LISP EI CINIEERING, INC. I SI BStRFACE EXPLORATION LOG
mmi-P-PARR THI I 1 P: 79PM Tn: FAr.I F r ni INTV FNI J PP:01 TH
PROJECT No. 99231
FIGURE; NO- I
pn== - 9 M
DATE DkILLED: Navctnhcr 18, 199V BORING NO. 2
ELEVATION:
S
S
BLOWS
Y
M
A
ivl
DESCRIPTION Or. MATERIAL
LABORATORY
pk`Er
PER Fr,
D
P
AND SAMPLE LOCATION
TEST RESULTSREMARKS
0
L
L
E
Topsoil
inches offr4st
--
Light reddish brown sandy cagy
-- 5
30/12
C)
Db-I I5.9 pcf
-
MC=12.7 %
---
36/12
iD
DD=107.0 pcf
--_
MC =17.1 %
---
50/7
D
DD=131.7 pcf
. 15
MC-7.3 %
`-
----• 20
Rock
Basalt rocks and boulders encountered
at 19 feet
-
Rack
- -- 25
Bottom of baring
No Ground Water
-
)Encountered
---- 35
LEGEND:
Q 74nch O.D. California Liftr Sumplo (rotatively undisturbed sample)
■ L-3/2-inch I.D. Split Spoon Sample (disturbed sample)
24/12 Drive sample blo+v count. Indicates that 24 blows of a 141-poured hummer faRing 3o inches were
required to drift tN'California or the Split Spuatt Sampler 12 inches.
DO Natural Dry Density (pcf)
MC - Natural Moisture Content ('Ys)
-200 - Percent passing No. 200 sieve
LL - Liquid Lintit
PI - Plasticity index
Q-W - flruund Water
LK P ENGINEERING, INC. ' SUBSLIRFAcIE EXPLORATION LOG
PmEcTm- 99239
FICrURE NQ. 2
wnt 1-P-aMPM TWI I 9 P- 74PM Tn - Pnr-1 t= Ml IKITV PKII I WJ Cl TI.-1 Dnf-= • 4 4
-- - - . -- -- -- ----+------ I------ ----------
I
Q
U ~
r~ KP Engineering, Inc.. Swell — Consolidation Test Results
wnt J-P-PORM TI-II I 1 P! 7qPM Tn! P7om F f" i INT`,' FNl J HFA1 TN PA(W .- 1 ?
7 TrA V! iZ
0
-yJ
-2
4
-.3
-,2
r
u
D
7 .
0
4
O
4
at
off, 1, o APPLIED PRESSUI?E -- ksf lv lcao
Sample Of from --
Noturol Qry Unit Weight = pcf
Ncturcl Moisture Content = percent
+rcvxcr rtv.:
Lift' Engineering, Inc. Swell — Consolidation Test Results ssas
Actprf NU_
Kith J-P-PMMM TWI 1 1 P • Qri MM Tn • C0r-'I C r'f'II IKITV Ch11 1 Ul=nl TU rin . 4 �
l mrl f Lz
SLOPE AWAY FROM BUILDING
P
COVER BACKFILL i{4714 LINE
FOOT OF RELATlV�ZY
P d lYPERVIOU$ SOIL
P
h '
t
GRANULAR F11.L
hP e P
e
_ 4 p 0
U \�
PLASTIC LINER- GL UCD
TO THE FODUNNDATION WALL,
(NO r NEEDED- WHEN (WOUND
WATER is PRESE'NT)
G_RAYEL TRIC'KNESS SHOULD- BE
AT LEAST -94 INCHES AND SHOULD
tNCREASE` IF HEA WER SEEPAGE IS.
ANTICIPA TED
F/L_TLR FABRIC
(,VIRAFI 140N OR
EQUIVALENT)
COARSE GRAVEL, J14 INCH DIAM_
WITH LESS THAN 5%'FIII+ES
4--I1V0I/ DIAUETER PERFORA TED
PIPE SLOPED TO A SUITA44E OUTLET
A T 114 "- PER F'DOT FOR F4E,1 &F AND
AT 1/6" PZ-R FOOT FOR RIGID PIPE
PRl?$G�' NO.r
PERIMETER DRAIN 9-0219
_ C1V3L/CE6TEUHhICItL
LOT IS. &OGK Z, CORDILLERA *7LWa No. 36 SCA&E.' �T
L e£ADNTSLKP Engineering, In C. CAGUNr. =40RO
aara::
h,D. BOX 1452 Aver CO 6182Q PHLEPARED rL"e
tot (970) 920-9080 fur (970) 9ZEi-Baas THF. PURNE'R REVOCABLE TRUST
5
mnL1-P-PMMM TWI 1 1 P- APIPMI TIC-PMr-1 G rni IKITV rKlt I WG01 TI-I var=C- 4 d
ISDS Permit # 9,051 00
Date5/30103
ISDS Final Inspection
COmDleteness Form
4. Tank is 156D gal. Tank Material
✓ Tank is located 12ft. and Lt degrees from
(permanent landmark)
Tank is located ft. and degrees from
(permanent landmark)
Tank set level. : Tank lids within 8" of finished grade.
Size of field ft' units lineal ft.
Technology CY1, L IJA; t.E 0
v
�Cleanout is installed in between tank and house(+ 1/100ft).
There is a "T" that goes down 14 inches in the inlet and
outlet of the.tank.
Inlet and outlet is sealed with tar--.tape,rubber gasket etc.
✓Teink las two compartments with the, :l:arger.:compartment closest to the
house.
CKeabure7 distance and relative direction.to.:.f eld
_Depth of field.-:!) ft.
✓� Soil interface raked.
Inspection portals at the end of each trench_:" ...
w' Proper distance to setbacks.
Chambers properly installed as per manufacturers specifications.
(Chambers latched, end plates properly installed, rocks removed from
trenches, etc.)
Type of pipe used for building sewer line leach field
Other
Inspection meets requirements.
Copy form to installer's file if recommendations for improvement were
suggested.
ACTION TAKEN:
Setbacks
Well Potable House Property Lake Dry Tank Drain
Water Lines line Stream Gulch
Field 100 25 20 10 50 25 10 10
Tank 50 10 5 10 50 10 * 10
o
C
A
12
"lows
At
y
17
0
2051-00 Tax #2107-163-02-010
JOB NAME Lot #15, Filing 36 ARDEN DEV.
Block 2, Cordillera Subdivisio
166 Golden Ranr Driva - PA -.-A.
JOB NO.��y`��
LOCATION
BILL TO
DATE( S ARTED
4
DATE COMPLETED
DATE BILLED
Gl
l
�,-
U
C)
1Z���
K
c�
w
Y3') 0 3
—
/L� d 2L /1
_z�
d� 2 �,t_
I Soo Qo
JOB COST SUMMARY
I a
�k e�
TOTAL SELLING PRICE
I-- S�,
�I.I e I 1 _ �, {
�t�{u
TOTAL MATERIAL
1 /
Q - (. S!:JO/`-WQ�O_-, �12.I6 3 J
TOTAL LABOR
;D \O ��Gt �C L z.G C_ c'�.'L- �`- ��G� _
INSURANCE
SALES TAX
^.t� #' 1(1�
MISC. COSTS
L�
TOTAL JOB COST
GROSS PROFIT
LESS OVERHEAD COSTS
% OF SELLING PRICE
NET PROFIT
JOB FOLDER Product 278 JOB FOLDER Printed in U.SA
.Y
v [ " F "w
, ��..4
W*4
,
,L~
° ^ a,
-.. '^rod -•�y
SOIL PROFILE
PERCOLA 77ON TEST RESUL TS ►
PROFILE HOLE
- _ GRHl� SCAj,E Perc No. 1 Perc No. 2 Perc No. 3 0 to 2.5 feet Topsoil
- 20 minutes per inch 20 minutes per inch 20 minutes per inch 2.5 to 8 feet Reddish brown,
so
20 ; . o 10 : . •o ---- -- - - - - - \� _ silty -sandy clay
\ Average percolation rate recommended for design T = 20 minutes per inch. No Ground Water
No Bedrock
i inch 20 !i \
tp \ \ COLD -
- `r�\ e�A DESIGNCAL CULA 110NS
- R DR/ Vc
s C Design percolation rate T = 20 minutes per inch
Number of bedrooms = 4
886 Maximum doily Flow = Qmax
`rs \ 6 Omox = 4 bdrms x 2 persons/bdrm x 75 gallons/person/doy x 15OX
886 — —� Qmax = 900 gpd
LOT 16 677C TA
EP VQmax/24hrs x 30 hrs
V = 1125 gallons
/ Use 1500 gallon, two compartment precast concrete tank by Copland Concrete or equivalent
ABSORPTION AREA .
CP� A = Qmax 5 x VT
A = 900155 x 1/20 - 805 S. f.
\` Based on Applicotio Rate.
A = 900gpd/0.6 gpd/s. f.
A = 1500 s. f.
cs0 8g64
\ / i Standard /n6/trotor Chamber System in a trench con6guratron with on allowed 50 percent
\ 8 6 reduction in the absorption area is recommended.
�610—Acorrected = 750 s. f.
5� Surface area of one Infiltrctor Chamber = 15.5 s.f.
b Use 48 /nfi/trotor Chambers in three trenches with 16 /nfi/trotors in each.
N
1. The building sewer line from the house to the septic tank shall have a maximum slope of 114 inch per
foot. Bends in the building sewer shall be limited to 45 degrees.
2. The septic tank shall be installed level. The tank shall have removable covers or manholes to within 8
inches of the finished grade, for inspection and cleaning.
J. Excavate three (3) feet wide trenches. The horizontal distance from sidewa/l to sidewall between the
trenches shall be a minimum of six (6) feet.
8856
SERIAL DISTRIBUT/ON 4. The bottom and the sidewalls of the trenches shall be raked to eliminate smearing.
SEE DETAIL A -A ` I / 8854
5. Assemble and install the Infiltrator Chambers in the trenches accordingto the manufacturers
I . , x • / / / /' �recommendations.
852 /
INSPEC71oN PORT I / l •• 3" // / , / / / / / / / /' 6. Backfill the sidewall area with native on -site _ soil for proper support.
- / 4' D/AM1BLDG SE➢ R 8� / / ' / / / / $41) um of h itcover.'
STANDARD 1NFXMATOR TWICA AT 1/ft PER FOOTLOT 14
/ � / 6 7. Backfill the trenches with a minim 12 inches of tamped so
• / / / Ire, / / / 8. Avoid vehicle traffic over the system.
• / /
MAIN LEVEL 8861.5 /p� ! / / / / / / / 9. All installations shall meet the rules and regulations of the Eagle County Environmental Health Division,
/ LOWER LEVEL 8850.5 / $� / / / / / / / / / �a�2 Chapter 4, Individual Sewage Disposal Systems.
10. The Septic System Installation shall Go
be inspected b the Design En meer rior to backfillin
p ys P Y 9 9• P 9•
1 0,/ / / /
/
/ 1500 GAL TWO COUP.L ON TWO COMPARTMENT
j CONC SEPTIC TANK -.•�, - .•,r.; O O GAL
- _ - LOT 15 � ...: i,.^�:�i � .,,�` / � _
' / CONCRETE SEP TIC TANK
coLn// / / / // / / // /� �/ �/
8 / co / / // / // ///
_ 8856 �/� o� ��g� // ,// /// /� // // //� ' // / /8818
00 00
/ ,LO
11-1 00 P / / ! j 01
/ Ile/
/ / pIle
m
-
o
a
12
W
_
o
Q
0
0
Z
2
E.
v1
C-D
NA
O
_W
__j _
u
w
�+1
OW2
Q
CL
Y Q1 W
Wr
A
`
O
V
00
Oo
n�
CD
_
00 Nr-
v
b(1
0)
�x
W
•�
v
� o
OH
w
00
00
\
0
ro
00 M
N i
U
x (V
.�
rn
m^
�V
O r-
� iu�rinmm�ny,/Z
�,.p0 REsfs�.,,f%
p ETigO•. F,p%
2952
DRAWN BY L.P.
CHECKED BY L.P.
PROxcT NO.: 2082
DATE.•
05-03-2000
DRAwNG Na. 2082SD.DWG
SHEET 1 OF 1