Permit
Permit No. OWTS-020353-2020
Permit Type: OWTS Permit
Work Classification: Alteration
Permit Status: Active
Issue Date: 1/21/2021 Expires: 5/21/2021
On-Site Wastewater
Treatement System
Project Address Parcel Number
254 PINE MARTEN WY, EDWARDS AREA,210716102005
Owner Information Address
Joseph McCormick 254 Pine Marten Way
Cordillera, CO 81632
Phone: (956) 466-5577
Cell: (970) 333-4044
Email: jxsmccormk@aol.com
Inspections:
For Inspections Call: (970) 328-8755
and call the Design Engineer
Engineer Phone Email
LKP Engineering, Inc., Luiza Petrovska, PE (970) 390-0307 luiza@lkpeng.com
Contractor License Number Phone Email
Bronn Excavating bronnex4867@yahoo.com(970) 977-0261
Permitted Construction / Details:
A licensed installer has not been identified. No person shall install, renovate, or repair an OWTS in Eagle County
(EC) without a valid EC Systems Contractor License. Any person that conducts a business as a systems contractor
without having obtained a valid license section commits a Class 1 petty offense as defined in section 18-1.3-503,
C.R.S. Please notify the department when an installer is identified, prior to installation of the OWTS.
Alteration to existing OWTS, permit 2369-04IS, exactly as depicted in the LKP Engineering, Inc design stamped,
signed, and dated January 21, 2021 by Luiza Petrovska, PE. The alteration of the system is designed to
accommodate the increased maximum daily flow from the addition of two bedrooms to the existing five bedroom
residence, for a total of seven bedrooms. The soil treatment area was determined by the PE as adequately sized to
serve seven bedrooms, based on analysis of previous soils test and current regulations, and so will remain as
existing.
The alteration consists of the addition of a new 1000 gallon Valley Precast single compartment concrete tank, prior
to (or upstream to) the existing tank 1500 gallon septic tank, determined to be in working order, and will remain as
existing. The 1500 gallon tank must be pumped and a new effluent filter installed on the outlet tee.
Note: Do not install the new tank in wet or frozen ground.
Contact Eagle County Environmental Health and the design engineer well in advance of requesting inspections prior
to backfilling any component of the OWTS. The design engineer is responsible for conducting all inspections
necessary to certify the installation and assure the functionality of the system. System certification, along with
photos and a record drawing is required to be submitted to and approved by Eagle County Environmental Health
prior to the use of the system.
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS OF
ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Claire Lewandowski
Date
January 21, 2021
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Thursday, January 21, 2021 1
INSPECTION WORKSHEET (INSP-510393-2021)
FOR EAGLE COUNTY GOVERNMENT
OWTS-020353-2020Case Number:Case Module:Permit Management
10/07/2021 ApprovedInspection Status:Inspection Date:
OWTS Final InspectionInspection Type:Inspector:Claire Lewandowski
Job Address:Parcel Number:254 Pine Marten Wy
Edwards Area, CO
210716102005
Company Name NameContact Type
Applicant GRK Properties Gary Keller
Contractor Bronn Excavating David Bronn
Engineer LKP Engineering, Inc.Luiza Petrovska, PE
Owner Joseph McCormick
CommentsPassedChecklist Item
TrueSeptic Tank - Septic Tank
TrueRecord Drawing - Record Drawing
TrueRecord Photos - Record Photos
True Stamped, signed, and dated July 13, 2021 by Luiza Petrovska, PE.Final Certification Letter - Final Certification Letter
TrueGeneral Plan - General Plan
True Eagle County Licensed contractor Dave Bronn, Bronn Excavation
completed the instalation.
Identification of Systems Contractor - Identification of
Systems Contractor
October 07, 2021 Page 1 of 1P.O. Box 179, 500 Broadway, Eagle, CO 81631-0179
Gary Keller
GRK Properties
P.O. Box 3838
Eagle, CO 81631
grkeller1@gmail.com
7/13/2021
PROFILE HOLE #1DESIGN CALCULATIONS FOR OWTS REPLACEMENT SERVICING EXISTING MAIN HOUSE ANDDETACHED GARAGE WITH AN APARTMENTDESIGN LONG TERM ACCEPTANCE RATE RATE = 0.5 GPD/SFNUMBER OF BEDROOMS: 7MAXIMUM DAILY FLOW = QMAXQMAX = 7 BEDROOMS. ALLOWED 2 PERSONS FOR EACH OF THE FIRST THREE BEDROOMS PLUSONE ADDITIONAL PERSON FOR EACH ADDITIONAL BEDROOM. THREE BEDROOMS X 2 PERSONSPER BEDROOM PLUS 4 BEDROOMS X ONE PERSON PER BEDROOM = 10 PERSONSQMAX = 10 PERSONS X 75 GPD = 750 GPDSEPTIC TANKV = 1000 GALLONS FOR 2 TO 3 BEDROOMS PLUS 250 GALLONS FOR EACH ADDITIONALBEDROOMREQUIRED 2000 GALLONS, TWO-COMPARTMENT CONCRETE SEPTIC TANK. THE EXISTINGSEPTIC TANK IS 1500 GALLONS, TWO COMPARTMENT CONCRETE SEPTIC TANK. ADD1000-GALLONS, ONE COMPARTMENT CONCRETE SEPTIC TANK BY VALLEY PRECAST ANDCONNECT IN SERIES. ADD AN EFFLUENT FILTER TO THE OUTLET TEE OF THE EXISTING SEPTICTANK. THE FILTER HANDLE MUST BE EXTENDED TO WITHIN ONE FOOT OF THE RISER COVERFOR EASE OF MAINTENANCE.ABSORPTION AREABASED ON APPLICATION RATE:A = 750GPD/0.5GPD/S.F.A = 1500S.F.QUICK 4 PLUS, STANDARD INFILTRATOR CHAMBER SYSTEM IN A TRENCH CONFIGURATIONWITH AN ALLOWED 30% REDUCTION FOR INFILTRATOR CHAMBERS. A=1050 SFSURFACE AREA OF ONE QUICK4, PLUS STANDARD INFILTRATOR CHAMBER = 12 S.F.USE 88 QUICK4, PLUS, STANDARD, INFILTRATOR CHAMBERS IN TRENCHES AS SHOWN ON THEPLAN.THE EXISTING SOIL TREATMENT AREA (STA) HAS 60 STANDARD INFILTRATOR CHAMBERS WITHDIMENSIONS OF 6.25 FEET LONG AND 3 FEET WIDE FOR A TOTAL LENGTH OF 375 LF.BASED ON THE NEW OWTS #43, THE REQUIRED STA FOR 7 BEDROOMS REQUIRES (AS SHOWNABOVE) 88 QUICK4, PLUS, STANDARD, INFILTRATOR CHAMBERS WITH A TOTAL LENGTH OF 352LF.THE EXISTING STA HAS GREATER CAPACITY AND IT IS SUITABLE FOR THE PROPOSED7-BEDROOM RESIDENCE. NO ADDITIONAL TRENCHES WITH INFILTRATOR CHAMBERS WILL BEREQUIRED.NOTES:1. BENDS IN THE BUILDING SEWER SHALL BE LIMITED TO 45 DEGREES.2. THE SEPTIC TANK SHALL BE INSTALLED LEVEL.3. THE TANK SHALL HAVE RISERS OVER EACH ACCESS MANHOLE AND ALL RISERS SHALLEXTEND TO OR ABOVE FINAL GRADE.4. EACH RISER LEAD WILL HAVE A SECURE CLOSING MECHANISM, SUCH AS A LOCK,SPECIAL HEADED BOLTS OR SCREWS, OR SUFFICIENT WEIGHT TO PREVENTUNAUTHORIZED ACCESS.5. THE SEPTIC TANK AND ALL THE PIPING WILL BE BACKFILLED UP TO THE INVERTS PRIORTO SCHEDULING AN INSPECTION.6.FOR THE INSPECTION OF THE SEPTIC SYSTEM - NOTIFY THE EAGLE COUNTYENVIRONMENTAL HEALTH DEPARTMENT AND THE DESIGN ENGINEER A MINIMUM OF72-HOURS PRIOR TO BACKFILLING ANY PART OF THE SYSTEM TO SCHEDULE ANINSPECTION.7. ALL INSTALLATIONS SHALL MEET THE RULES AND REGULATIONS OF THE EAGLE COUNTYENVIRONMENTAL HEALTH DEPARTMENT AND OWTS REG 43 EFFECTIVE AUGUST 24, 2018 .EQUIVALENT LTAR = 0.5 gpd/sf,REQUIRES: Conventional, gravity systemPERCOLATION TEST RESULTSPERC NO. 1 PERC NO. 2 PERC NO. 3 40 MPI 23 MPIH 32 MPIAVERAGE PERCOLATION RATE RECOMMENDED FOR DESIGN T = 32 MINUTES PER INCH.PERC TEST AND PROFILE HOLE DONE ON JUNE 4, 2003© EXISTING, 1500 GALLONS,TWO-COMPARTMENTS,CONCRETE SEPTIC TANKPROPOSED, NEW, 1000-GALLONS,ONE-COMPARTMENT, CONCRETESEPTIC TANK INSTALLED ON LINE OFTHE EXISTING BUILDING SEWER LINE4.00'EXISTINGCLEANOUTEXISTING SOIL TREATMENT AREA,SUFFICIENT FOR A 7-BEDROOMRESIDENCE THAT INCLUDED THETWO-BEDROOM ADDITIONEXISTING 5-BEDROOMRESIDENCE WITH APROPOSED 2-BEDROOMADDITIONNEW EFFLUENTFILTERGENERAL NOTES1. BEFORE DIGGING NOTIFY ALL APPLICABLE UTILITY COMPANIES.2. ALL WORK SHALL COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES.3. NOTES AND DETAILS ON SPECIFIC DRAWINGS TAKE PRECEDENCE OVER GENERAL NOTES ANDTYPICAL DETAILS.4. CONFLICTS OR DISCREPANCIES WITH GRADES SHALL BE BROUGHT TO THE ATTENTION OF THEENGINEER IMMEDIATELY AND PRIOR TO PROCEEDING WITH WORK.5. ALL FINISH GRADES SHALL PROVIDE FOR NATURAL RUNOFF OF WATER WITHOUT LOW SPOTSOR POCKETS.6. ALL EXCAVATION, BACKFILLING AND COMPACTION SHALL BE DONE IN ACCORDANCE WITH THESOILS REPORT PREPARED FOR THIS SITE.7. ALL DISTURBED AREAS WILL BE RESTORED AND REVEGETATED WITH NATIVE VEGETATIONSUITABLE FOR THE REGIONExisting systemISDS Permit Number 2369-04DRAWN BY:CHECKED BY:PROJECT NO.:SHEET:DRAWING NO.:DATE:BYDESCRIPTIONDATENO.L.P.L.P.C-103069NOVEMBER 18, 202003069OWTS-ADD.DWGONSITE WASTEWATER TREATMENT SYSTEMREPAIRLOT 5, BLOCK 1, CORDILLERA FILING 36254 PINE MARTEN WAYEAGLE COUNTY, COLORADOP.O. Box 724 EAGLE, CO 81631Tel (970) 390-0307www.LKPEngineering.comSCOTT S. TURNIPSEED AIAARCHITECTURE & CONSTRUCTION INC.L.P.01/21/20211.CHANGE EFFLUENT FILTERLOCATIONSEE REVISIONS BOX AT TOP01/21/2021
P.O. Box 724, Eagle, CO 81631 Tel (970) 390-0307 www.LKPEngineering.com
January 21, 2021
Brennen Scott Fitzgerald, A.I.A.| Partner
Scott S. Turnipseed, AIA
Architecture & Construction Inc.
P.O. Box 3388
Eagle CO 81631
brennen@sstaia.com
RE: Engineering Services for the McCormick
Residence Addition - OWTS for 7 bedrooms
Lot 5, Block 1, Cordillera Filing 36
0254 Pine Marten Way
Eagle County, Colorado
Project No. 03069
Old ISDS Permit Number 2369-04
Dear Brennen:
The following report is a summary of our evaluation, of the existing Onsite Wastewater
Treatment System and the required improvements for the proposed two-bedroom McCormick
Residence Addition on Lot 5, Block 1, Cordillera Filing 36, 0254 Pine Marten Way, Eagle
County, Colorado. The calculations and the layout of the required improvements are shown on
the attached drawing C-1.
The existing system, ISDS Permit Number 2369-04, was designed for a 5-bedroom
residence and it was constructed on October 18, 2004. The system consists of a 1500-gallons,
two compartments concrete septic tank and a Soil Treatment Area with 60, Standard Infiltrator
Chambers constricted in four trenches with 16 chambers in each of the first two trenches and 14
chambers in each of the last two trenches.
The proposed addition will add two more bedrooms to the existing five for a total of 7
bedrooms. An additional, 1000-gallons, one compartment concrete septic tank will be added just
before the existing, 1500-gallon, two compartment concrete septic tank, as shown on the attached
drawing. An effluent filter (per the OWTS #43 regulations) will be installed on the outlet tee of
the second (existing) tank.
The existing Soil Treatment Area (STA) was re-calculated based on the present OWTS
#43 regulations for the total number of 7 bedrooms (existing and proposed). Per the new
regulations the Maximum Daily Flow was calculated for the allowed 2 persons per bedroom for
the first three bedrooms plus one additional person for each additional bedroom for a total of 10
people. The maximum daily flow was calculated to be 750 gpd.
With the LTAR = 0.5 gpd/sf, based on the Percolation Rate of 32 minutes per inch, done
on June 4, 2003, the required STA was calculated to be 1500sf. With the allowed 30% reduction
for Infiltrator Chambers the size of the required area is 1050 sf. Based on the allowed 12sf for
the surface of Quick 4 Plus Infiltrator Chambers, the required number of infiltrators will be 88
with 88 infiltrators x 4 feet = 352 lineal feet. The existing STA has 60 chambers at 6.25 feet =
375 lineal feet. The existing STA has greater capacity than the required 352lf, thus no additional
McCormick Residence Addition - OWTS
Page 2 of 2
January 21, 2021
Project 03069
P.O. Box 724, Eagle, CO 81631 Tel (970) 390-0307 www.LKPEngineering.com
trenches with infiltrator chambers will be required.
You or your licensed installer will apply for a repair permit, for the installation,
connection and backfilling of the new tank, and will make sure that all the required setbacks are
met. Once the new septic tank is installed with all the connections completed, you or your
installer will give a 48-hour notice to LKP Engineering and the ECEH Department to schedule
the inspection. DO NOT backfill any part of the system prior to the inspection. If you have any
questions, please do not hesitate to call.
Sincerely,
LKP ENGINEERING, INC.
Luiza Petrovska, PE
cc: Eagle County Environmental Health Department, e-mail: environment@eaglecounty.us
J:\_WP X4-LKP\2003\03069OWTS-SEPTIC-TANK-ADDITION.DOCX
01/21/2021
PERMIT CORRECTIONS REPORT RES-020147-2020
FOR EAGLE COUNTY GOVERNMENT
PARCEL:210716102005PERMIT ADDRESS:254 Pine Marten Wy
APPLICATION DATE:11/19/2020
Building Residential - Addition Review v.1
REVIEW ITEM STATUS REVIEWER
Building - Inherit Due Date - VG1.Completed JR Mondragon, Ph: (970) 328-8768
email: jr.mondragon@eaglecounty.us
Correction Comments: No Correction
Corrective Action:
Environmental Health - CL2.Denied Claire Lewandowski, Ph: (970) 328-8747
email: claire.lewandowski@eaglecounty.us
Correction Comments: The OWTS permit application and fee have not been submitted to allow Environmental Health to begin review of the design.
Building permit cannot be release for properties on private sewer without an active septic permit.
Corrective Action:
Engineering - JP3.Completed Julie Pranger, Ph: (970) 328-3563
email: julie.pranger@eaglecounty.us
Correction Comments: No Correction
Corrective Action:
Planning - Inherit Due Date - SO4.Completed Colton Berck, Ph:
email: colton.berck@eaglecounty.us
Correction Comments: No Correction
Corrective Action:
December 28, 2020 Page 1 of 1P.O. Box 179, 500 Broadway, Eagle, CO 81631-0179
OFFICE
970-471-0913
P.O. Box 1534
Eagle, CO 81631
altitudeseptic@gmail.com
www.altitudeseptic.com
1/15/2021
254 Pine Marten Way
Edwards, CO 81632
To Whom It May Concern,
As requested, Altitude Septic performed a septic system inspection at the above address on January 11, 2021. The
2.968-acre lot is located southwest of Edwards in an area that requires utilizing an OWTS and is listed under parcel
number #210716102005. The system was installed under permit #2369-04 which called for a 1,500-gallon,
concrete, tank with 60 infiltrator chambers in four trenches, and was finalized in November of 2004. The original
design was sized to accommodate a five-bedroom residence.
The septic tank is on the west side of the structure with both lids accessible at the surface. A clean-out was visible
between the house and the tank. There are two risers on the inlet side and one on the outlet with both baffle tees
in place as required. The liquid level in the tank was normal and the concrete is in good condition. Sludge levels
were measured during the inspection and were about 40% of the septic tank capacity. We would recommend
pumping the tank out and installing an effluent filter on the outlet side of the tank to help prolong the life of the
STA (Soil Treatment Area).
The STA is northeast of the septic tank in a trench configuration utilizing serial distribution. With snow cover
present we were unable to locate the inspection ports for the trenches, but the area was walked and observed
with no visible indications of surfacing or failure. We were informed that the residence had been occupied from
June through December of last year, so if a failure existed it would have been visible because of the occupancy and
use of the drains. As mentioned above, the septic tank was at normal level as well.
After the inspection we would make the following recommendations:
• Pump the septic tank. Every 3-5 years is recommended for full time occupants.
• Install an effluent filter on the outlet side of the tank. The filter should be checked every 2-3 years and
cleaned as needed.
Please contact me directly with any additional questions at (970) 471-6292.
Sincerely,
Travor Dunsdon
Please be aware of the following disclaimer: Altitude Septic accepts no responsibility for the proper operation of this
septic system. The septic system is the property of the homeowner who is responsible for the maintenance and operation
of this system. This inspection does not constitute a guarantee nor is any warranty expressed or implied that the system
will function properly in the future. Altitude Septic can only make observations based on the condition of the septic system
at the time of inspection and will make no prediction on the future functionality of any part of the septic system.