Press Alt + R to read the document text or Alt + P to download or print.
60 Squires Ln - 210935101005
HomeMy WebLinkAbout60 Squires Ln - 210935101005Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970) 328-8730
Fax: (970) 328-7185
Permit
Permit No. OWTS-018628-2020
Permit Type: OWTS Permit
Work Classification: New
Permit Status: Active
Issue Date: 5/8/2020 Expires: 8/17/2021
On-Site Wastewater
Treatement System
Project Address Parcel Number
60 SQUIRES LN, EAGLE AREA,210935101005
Owner Information Address
FCP Ltd Phone: (303) 399-3502
Cell:
Email: chluppens@gmail.com
Inspections:
For Inspections Call: (970) 328-8755
and call the Design Engineer
Engineer Phone Email
JVA Inc, Simon Farrell (303) 444-1951 sfarrell@jvajva.com
Contractor License Number Phone Email
Defina Construction, INC gary@definaconstruction.c
om
(970) 376-6702
Permitted Construction / Details:
Install the OWTS exactly as depicted in the JVA, Inc. design stamped, signed and dated March 31, 2020 by Simon A.
Farrell, PE. The OWTS is designed with capacity to serve a 5 bedroom residence.
The system consists of a Valley Precast 1,250 gallon, single compartment tank with effluent screen and alarm placed
on the outlet, followed by a 2,000 gallon Valley Precast 3 compartment recirculating/dose tank which will send
wastewater to two, Advantex AX 20 pods for nitrification using an Orenco PF 500512 pump. Nitrified effluent flows to
the splitter valve (mode 3B) for recirculation to the 1,250 gallon first tank for denitrification then is dosed using an
Orenco PF 751012 pump to 1715 square feet of soil treatment area via two beds each consisting of four rows of 18
Infiltrator Quick 4 Plus Standard chambers for a total of 144 Infiltrator chambers. Distribution lateral details, along
with orifice size, spacing and orientation are on the design drawing. The contractor must verify that all electrical
components and inspections are covered under the electrical permit associated with the Orenco Vericom control
panel (Model VCOM-AX20B2) and pump connections. The alarm must be connected to a separate circuit. Additional
pump details are on the design drawing. Advantex systems must conform to the CDPHE technology approval letter
dated May 1, 2018.
Contact Eagle County Environmental Health and the design engineer well in advance of requesting inspections prior
to backfilling any component of the OWTS. The design engineer is responsible for conducting all inspections
necessary to certify the installation and assure functionality of the system. System certification, along with photos
and a record drawing is required to be submitted to, and approved by, Eagle County Environmental Health prior to
the use of the system or occupancy of the dwelling.
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS OF
ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Claire Lewandowski
Date
May 08, 2020
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT
4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Friday, April 9, 2021 1
chluppens@gmail.com
March 27, 2020
Ms. Claire Lewandowski, REHS
Environmental Health Specialist III
PO Box 179
Eagle, CO 81631
RE: Frost Creek - Onsite Wastewater Treatment System Design – Lot 8, Eagle County, CO
Dear Claire:
JVA Inc. (JVA) has prepared a design of an onsite wastewater treatment system (OWTS) to
serve Lot 8 within the Frost Creek PUD. JVA is the designated engineer to process all OWTS
permit applications within Frost Creek. JVA has prepared the OWTS design to be in general
conformance with OWTS requirements of the PUD.
The 2019 annual Water Quality Monitoring Report prepared by Wright Water Engineers
documents exceedances of the 85th percentile background concentrations during sampling events
in 2019. The report states the following ‘The trends of water quality parameters seen throughout
the sampling of groundwater and surface water at the Frost Creek PUD have not reflected a
marked upward increase in concentrations of the sampled parameters. As more homes are
constructed on the Frost Creek PUD during 2020, the surface water and groundwater sampling
location will continue to be monitored.
Sincerely,
JVA, INCORPORATED
By: _______________________
Simon Farrell, P.E.
Project Manager, Associate
Attachment A - OWTS design – Lot 8
Attachment B - Visual and Tactile Soil Evaluation
Attachment C - Discharge pump calculations
ATTACHMENT A – OWTS DESIGN – LOT 8
ATTACHMENT B – VISUAL AND TACTILE SOIL
EVALUATION
March 25, 2020
Ms. Claire Lewandowski, REHS
Eagle County Environmental Health
590 Broadway
Eagle, CO 81631
RE: Frost Creek Lot 8 – Site and Soil Investigation Report for an Onsite Wastewater
Treatment System (OWTS)
JVA Job No. 1037.7e
Dear Claire:
Enclosed in this report are the results of the site and soil evaluation for Lot 8’s proposed OWTS
located in Frost Creek, Colorado. This report provides information needed to support the design
of an OWTS including: results from the preliminary investigation, the site visit, and the soil
evaluation. Design calculations are included in the drawing Permit Set attached.
PRELIMINARY INVESTIGATION
In preparation for a more efficient and informed site visit and soil evaluation, a preliminary
investigation was conducted the week of September 16, 2019. Architectural site plans, aerial
imagery, and previous Geotechnical investigations were used for the preliminary investigation.
Geotechnical investigations were performed by HP Geotech in October 2002 across Frost Creek
for OWTS suitability; this geotechnical investigation has been submitted to Eagle County
previously. The HP Geotech report shows there were no test holes dug in this area, however the
results from a nearby test hole show that it consisted of a topsoil followed by a sandy clay layer
from 0.5 to 4 feet deep and a rocky, sandy clay from 4 to 8 feet deep. No groundwater was
encountered in either test holes.
SITE VISIT AND SOIL EVALUATION
A site visit and soil evaluation were conducted on September 30th, 2019 by Julie Gustavson; Julie
has passed the Colorado Professionals in Onsite Wastewater (CPOW) Soils Evaluation Course.
The purpose of the site visit and soil evaluation was to confirm hypotheses from the preliminary
investigation, identify the topography, landscape position, vegetation, and site constraints for the
proposed OWTS, and to conduct a visual and tactile soil evaluation of the underlying soils where
the proposed soil treatment area (STA) is to be located for both suitability and sizing.
The topography of the site is in a small valley that slopes gently from southwest to northeast. The
dominant vegetation at the proposed OWTS consists of native grasses and sage. Site Constraints
are shown in the Permit Documents. For the visual and tactile soil evaluation, two soil profile
holes were excavated using a tracked excavator in the approximate locations identified in the
Permit Documents. As seen in Table 1 below, soil morphology for each soil profile hole from the
surface up to three feet deep was consistent with a Soil Type 3, and from three to eight feet deep
with a Soil Type 3 with R-1, Option 1. Figures 1 through 4 below show the soil profile holes and
Frost Creek Lot 8 OWTS
Site and Soil Investigation
3/25/20
2 of 3
corresponding morphology. No redoximorphic features, indicating seasonally high groundwater,
were observed in either profile hole. Therefore, Soil Type R-1, Option 1 was identified as the soil
type; the LTAR of soil type 3 treatment level 1 will be used. The proposed STA will be a bed with
the existing ground as the infiltrative surface.
Table 1 – Visual and Tactile Soil Results
Profile
Hole
Depth
(ft.) Percent Rock Soil
Texture
Soil
Structure
Type
Soil
Structure
Grade
Soil
Type
1
0 – 2 <10% retained
on 20 mm sieve
30% retained on 2
mm sieve; Clay loam Granular Moderate 3
2 – 8 30% retained
on 20 mm sieve
70% retained on 2
mm sieve
Sandy clay
loam Granular Moderate 3; R-1,
Option 1
2
0 – 3 <10% retained
on 20 mm sieve
30% retained on 2
mm sieve; Clay loam Granular Moderate 3
3 – 8 30% retained
on 20 mm sieve
70% retained on 2
mm sieve
Sandy clay
loam Granular Moderate 3; R-1,
Option 1
Figure 1 – Profile Hole One
Figure 2 – Profile Hole One Soil Morphology
Figure 3 – Profile Hole Two
Figure 4 – Profile Hole Two Soil Morphology
Frost Creek Lot 8 OWTS
Site and Soil Investigation
3/25/20
3 of 3
Sincerely,
JVA, INCORPORATED
By: _______________________
Julie Gustavson
Design Engineer
DISCHARGE PUMP CALCULATIONS
Pump Selection for a Pressurized System - Single Family Residence Project
Frost Creek Lot 8 pump select
Parameters
Discharge Assembly Size
Transport Length
Transport Pipe Class
Transport Line Size
Distributing Valve Model
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
1.50
80
40
2.00
None
4
12
40
1.50
4
156
40
1.50
1/8
3
3
None
0
inches
feet
inches
feet
feet
inches
feet
inches
inches
feet
feet
inches
feet
Calculations
Minimum Flow Rate per Orifice
Number of Orifices per Zone
Total Flow Rate per Zone
Number of Laterals per Zone
% Flow Differential 1st/Last Orifice
Transport Velocity
0.34
212
74.3
4
17.2
7.1
gpm
gpm
%
fps
Frictional Head Losses
Loss through Discharge
Loss in Transport
Loss through Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
'Add-on' Friction Losses
16.6
6.7
0.0
0.9
1.2
0.0
0.0
feet
feet
feet
feet
feet
feet
feet
Pipe Volumes
Vol of Transport Line
Vol of Manifold
Vol of Laterals per Zone
Total Volume
13.9
1.3
65.9
81.2
gals
gals
gals
gals
Minimum Pump Requirements
Design Flow Rate
Total Dynamic Head
74.3
32.4
gpm
feet
0 20 40 60 80 100
0
20
40
60
80
100
Net Discharge (gpm)
PumpData
PF7515 High Head Effluent Pump
75 GPM, 1HP
230V 1Ø 60Hz
Legend
System Curve:
Pump Curve:
Pump Optimal Range:
Operating Point:
Design Point:
Inspection Result
Eagle County, Colorado
P.O. Box 179 500 Broadway Eagle, CO
Phone: (970) 328-8730 Fax: (970) 328-7185
IVR Phone: 1-866-701-3307
Inspection Number: INSP-520488-2023 Permit Number: OWTS-018628-2020
Inspection Date: 02/06/2023
Inspector:
Permit Type: OWTS Permit
Inspection Type: OWTS Final Inspection
Work Classification: NewOwner:FCP, Ltd
Job Address:60 SQUIRES LN IVR Pin Number:190209
EAGLE AREA, CO Project:<NONE>
Parcel Number:210935101005
Contractor:Phone: (970) 376-6702 / Cell: (970) 376-6702Defina Construction, INC
Inspection Status: Approved
Inspection Notes
Inspector Comments
Added Item: Septic Tank
A Valley Precast 1,250 gallon, single compartment tank with effluent screen and alarm placed on the
outlet, followed by a 2,000 gallon Valley Precast 3 compartment recirculating/dose tank which will send
wastewater to two, Advantex AX 20 pods for nitrification using an Orenco PF 500512 pump was
installed.
Added Item: Record Drawing
Received 2/6/2023 from JVA Inc.
Added Item: Record Photos
Received 2/6/2023 from JVA Inc.
Added Item: Site and Soil
Received 4/28/2020 from JVA Inc.
Added Item: Final Certification Letter
Received 2/6/2023 from JVA Inc.
Added Item: General Plan
Received 4/28/2020 from JVA Inc.
Added Item: Soil Treatment Area (STA)
Nitrified effluent flows to the splitter valve (mode 3B) for recirculation to the 1,250 gallon first tank for
denitrification then is dosed using an Orenco PF 751012 pump to 1715 square feet of soil treatment
area via two beds each consisting of four rows of 18 Infiltrator Quick 4 Plus Standard chambers for a
total of 144 Infiltrator chambers.
Monday, February 6, 2023
For more information visit: http://www.eaglecounty.us
Page 1 of 2
Added Item: Identification of Systems Contractor
Defina Construction was the licensed installer.
Monday, February 6, 2023
For more information visit: http://www.eaglecounty.us
Page 2 of 2
February 6, 2023
Claire Lewandowski, REHS, Environmental Health Specialist III
Eagle County Environmental Health
500 Broadway Street
Eagle, CO 81631
RE: Onsite Wastewater Treatment System Final Certification – 60 Squires Lane, Frost Creek
Lot 8
Dear Claire:
The Onsite Wastewater Treatment System (OWTS) covered under Eagle County Permit No.
OWTS-018628-2020 was installed by Defina Construction for 60 Squires Ln and is ready for
final certification from Eagle County Environmental Health. This letter certifies that the
construction of the OWTS was completed as per the approved design plan. The final record
drawings from JVA, three-year maintenance contract, and construction photographs are provided
as attachments.
As part of the final approval process JVA ensured that start-up was completed by the
manufacturer’s representative (Valley Precast, Inc) and completed a site visit to check all system
components. The system is connected and can be monitored remotely as required in the PUD.
Sincerely,
JVA, INCORPORATED
By: ________________________
Simon Farrell, P.E.
Project Manager, Associate
Enclosure:
Attachment A – Record Drawings
Attachment B – Maintenance Contract
Attachment C – Construction Photographs
CC: Chelsea Fagan, JVA
ATTACHMENT A – RECORD DRAWINGS
FROST CREEK
LOT 8 ONSITE WASTEWATER TREATMENT SYSTEM
EAGLE COUNTY, COLORADO
RECORD DRAWINGS
MARCH 2020
Set No._______
JVA, Inc.1319 Spruce Street
www.jvajva.com
Boulder, CO 80302 303.444.1951
Boulder ● Fort Collins ● Winter Park
Glenwood Springs ● Denver
49466SIMON A . FAR
RELLPROF
E
S
SIONA L E N G INEERCOLOR A D O REGIS
T
E
RED03/31/2020
©
JVA, Inc.1319 Spruce Street
www.jvajva.com
Boulder, CO 80302 303.444.1951
Boulder ● Fort Collins ● Winter Park
Glenwood Springs ● Denver
CONFORMED TO CONSTRUCTION RECORD
St
e
p
s
d
o
w
n
1
8
"
(
3
-
6
"
R
i
s
e
r
s
)
Pa
t
i
o
(Br
u
s
h
e
d
/
c
o
l
o
r
e
d
co
n
c
r
e
t
e
)Automatic Cover forLap PoolMeters
GasAutomatic Cover forSpaSt
e
p
s
d
o
w
n
1
8
"
(
3
-
6
"
R
i
s
e
r
s
)
Pa
t
i
o
(Br
u
s
h
e
d
/
c
o
l
o
r
e
d
co
n
c
r
e
t
e
)Automatic Cover forLap PoolMeters
GasAutomatic Cover forSpa©
JVA, Inc.1319 Spruce Street
www.jvajva.com
Boulder, CO 80302 303.444.1951
Boulder ● Fort Collins ● Winter Park
Glenwood Springs ● Denver
CONFORMED TO CONSTRUCTION RECORD
©
JVA, Inc.1319 Spruce Street
www.jvajva.com
Boulder, CO 80302 303.444.1951
Boulder ● Fort Collins ● Winter Park
Glenwood Springs ● Denver
CONFORMED TO
CONSTRUCTION
RECORD
©
JVA, Inc.1319 Spruce Street
www.jvajva.com
Boulder, CO 80302 303.444.1951
Boulder ● Fort Collins ● Winter Park
Glenwood Springs ● Denver
CONFORMED TO CONSTRUCTION RECORD
ATTACHMENT B – MAINTENANCE CONTRACT
ATTACHMENT C – CONSTRUCTION PHOTOGRAPHS
Lot 8
08/22/2022
To Whom It May Concern:
We have been to the following site(s):
60 Squires Lane, (Lot 8) Frost Creek, Eagle
We have verified that the system was started properly. The System went through several
cycles with no issues.
Sincerely,
Scott McIntosh
Service Manager