Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout1142 Summit Trl - 210716302002Environmental Health
Department
P.O. Box 179
500 Broadway
Eagle, CO 81631-0179
Phone: (970) 328-8730
Fax: (970) 328-7185
Permit
Permit No. OWTS-024637-2022
Permit Type: OWTS Permit
Work Classification: New
Permit Status: Active
Issue Date: 7/11/2022 Expires: 11/14/2022
On-Site Wastewater
Treatement System
Project Address Parcel Number
1142 THE SUMMIT TRL, EDWARDS AREA,210716302002
Owner Information Address
DCP Completed Gifted Trust/Drake
Powell
Phone:
Cell:
Email: drake.powell@assetliving.com
Inspections:
For Inspections Call: (970)
328-8755
Engineer Phone Email
KUMAR & ASSOCIATES, Dave Young (970) 945-7988 dyoung@kumarusa.com
Contractor License Number Phone Email
Permitted Construction / Details:
Install the new system exactly as depicted in the Kumar & Associates design dated April 4th, 2022, stamped and
signed on April 5th, 2022 by David A Young, PE. This system is designed to accommodate the maximum daily flows
for a 5 bedroom residence.
The OWTS consists of one sewer line from the residence. The OWTS consists of a Valley Precast 1,500 gallon
three-compartment septic tank (2,000 gallon total volume) with an ORENCO PF3005 submersible effluent pump and
Biotube Vault installed in the third compartment, with floats set to pressure dose 104 gallons of effluent to the soil
treatment area (STA). The STA consists of two rows of 22 Infiltrator Quick4 Plus Standard chambers in bed
configuration for a total of 44 with distribution lines extending the length of the chambers set on a mounded sand
filter. The sand filter consists on a gravel distribution cell 6 feet wide by 88 feet long, over a basal area of secondary
sand 24 feet wide and 88 feet long, with additional area for edges sloped a minimum of 3 to 1. Distribution lateral
size, orifice size, and orifice separation shall be exact to design. A swale may be necessary along the up slope side
of the STA to deflect surface water away from the STA.
Note: Gradation of the sand media use must be completed within one month prior to the installation and confirmed
with the design engineer. If the sand does not conform to secondary or preferred sand media requirements, it
cannot be used for the sand treatment media.
An additional test pit immediately adjacent to the STA must be conducted and reviewed by the Design Engineer,
prior to installation. Any changes required to the design must first be reviewed and approved by the Design
Engineer and Eagle County Environmental Health Specialist.
A licensed installer has not been identified. No person shall install, renovate, or repair an OWTS in Eagle County
(EC) without a valid EC Systems Contractor License. Any person that conducts a business as a systems contractor
without having obtained a valid license section commits a Class 1 petty offense as defined in section 18-1.3-503,
C.R.S. Please notify the department when an installer is identified, prior to installation of the OWTS.
Contact Eagle County Environmental Health and the design engineer well in advance of requesting inspections prior
to backfilling any component of the OWTS. The design engineer is responsible for conducting all inspections
necessary to certify the installation and assure the functionality of the system. System certification, along with
photos and a record drawing is required to be submitted to and approved by Eagle County Environmental Health
prior to the use of the system or occupancy of the dwelling.
Monday, July 11, 2022 1
THIS PERIMT EXPIRES BY TIME LIMITATION AND BECOMES NULL AND VOID IF THE WORK AUTHORIZED BY THE PERMIT IS NOT COMMENCED WITHIN 120 DAYS
OF ISSUANCE, OR BEFORE THE EXPIRATION OF AN ASSOCIATED BUILDING PERMIT
Issued by: Environmental Health Department, Eagle County, CO
Danielle Salinsky
Date
July 11, 2022
CONDITIONS
1.
2.ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM
REGULATIONS ADOPTED PURSUANT TO AUTHORITY GRANTED IN CR.S. 25-10-101, et seq., AS AMENDED
3.THIS PERMIT IS VALID ONLY FOR PERFORMING WORK ON OWTS ASSOCIATED WITH STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND
BUILDING REQUIREMENTS CONNECTION TO, OR USE WITH, ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS
SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT AND WILL RESULT IN BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT4.1.6(A)(1) EAGLE COUNTY PUBLIC HEALTH AGENCY ON-SITE WASTEWATER TREATMENT SYSTEM REGULATIONS REQUIRES ANY PERSON WHO CONSTRUCTS,
ALTERS OR INSTALLS AN ON-SITE WASTEWATER TREATMENT SYSTEM TO BE LICENSED
Monday, July 11, 2022 2
Inspection Result
Eagle County, Colorado
P.O. Box 179 500 Broadway Eagle, CO
Phone: (970) 328-8730 Fax: (970) 328-7185
IVR Phone: 1-866-701-3307
Inspection Number: INSP-524099-2023 Permit Number: OWTS-024637-2022
Inspection Date: 09/25/2023
Inspector: Salinsky, Danielle
Permit Type: OWTS Permit
Inspection Type: OWTS Final Inspection
Work Classification: NewOwner:DCP Completed Gifted Trust/Drake Powell
Job Address:1142 THE SUMMIT TRL IVR Pin Number:196553
EDWARDS AREA, CO Project:<NONE>
Parcel Number:210716302002
Contractor:Phone: / Cell:
Inspection Status: Approved
Inspection Notes
Inspector Comments
Added Item: Septic Tank
Inspected and verified 7/28/2023. aA Valley Precast 1,500 gallon three-compartment septic tank
(2,000 gallon total volume) with an ORENCO PF3005 submersible effluent pump and Biotube Vault
wqas installed in the third compartment, with floats set to pressure dose 104 gallons of effluent to the
soil treatment area (STA).
Added Item: Record Drawing
Received 9/22/2023 from K&A.
Added Item: Record Photos
Received 9/22/2023 from K&A.
Added Item: Site and Soil
Inspected and verified 7/28/2023. Received 7/6/2022.
Added Item: Final Certification Letter
Received 9/22/2023 from K&A.
Added Item: General Plan
Received 7/6/2022.
Added Item: Soil Treatment Area (STA)
Monday, September 25, 2023
For more information visit: http://www.eaglecounty.us
Page 1 of 2
Inspected and verified 7/28/2023. The STA consists of two rows of 22 Infiltrator Quick4 Plus Standard
chambers in bed configuration for a total of 44 with distribution lines extending the length of the
chambers set on a mounded sand filter. The sand filter consists on a gravel distribution cell 6 feet
wide by 88 feet long, over a basal area of secondary sand 24 feet wide and 88 feet long, with
additional area for edges sloped a minimum of 3 to 1.
Added Item: Identification of Systems Contractor
JV Excavating was the licensed installer.
Monday, September 25, 2023
For more information visit: http://www.eaglecounty.us
Page 2 of 2
5020 County Road 154
Glenwood Springs, CO 81601
phone: (970) 945-7988
fax: (970) 945-8454
email: kaglenwood@kumarusa.com
www.kumarusa.com
Office Locations: Denver (HQ), Parker, Colorado Springs, Fort Collins, Glenwood Springs, and Summit County, Colorado
September 20, 2023
Pure Design Studio
Attn: Millie Aldrich
P.O. Box 527
Wolcott, Colorado 81655
millie@puredesign-studio.com
Project No. 20-7-595.02
Permit No. OWTS-024637-2022
Subject: Certification of Onsite Wastewater Treatment System, Proposed Powell
Residence, Lot 7, Block 2, Filing 36, Cordillera, 1142 Summit Trail, Eagle
County, Colorado
Dear Millie:
A representative of Kumar & Associates observed the installation of the Onsite Wastewater
Treatment System (OWTS) for the residence at the subject site as required by the Eagle County
Environmental Health Department. Our observations and recommendations are presented in this
report. The services are supplemental to Kumar & Associates agreement for professional
services to Pure Design Studio dated February 21, 2022.
We previously designed the OWTS for the residence as submitted in our report dated April 4,
2022, Project No. 20-7-595.02. The system was designed for five bedrooms. The OWTS was
installed by Meadow Mountain Homes under Permit No. OWTS-024637-2022.
We performed our as-built evaluations on June 16 and July 27 and 28, 2023. The OWTS
components observed included: sewer line, cleanout, septic tank, effluent line, pump, control
panel and soil treatment area (STA) and the locations of these components. The installation and
locations of the system components were verified as shown on Figure 1. Pictures of the OWTS
components made during the site visits are included with this report. The distance locations to
the septic tank shown on Figure 1 were made by taping.
On June 16, 2023, two profile pits (Profile Pits 1 and 2) were excavated to verify the subsoil
conditions to adjacent the east and west sides of the STA and located as shown on Figure 1. The
soils encountered were similar to the soils previously encountered in the area and below about
1 to 2 feet of organic topsoil, consisted of about 1 to 2 feet of gravelly Clay Loam. In both
Profile Pits, hard basalt rock was encountered at 3 feet depth and practical digging refusal was
encountered at 4 feet depth. No free water was encountered in the pits nor indications of
seasonally high groundwater were observed at the time of excavation.
On June 21, 2023, a sample of the secondary sand media was obtained and the results of
gradation analysis test are attached. On July 28, 2023, after power had been supplied to the
pump, a pump performance test was performed with adequate pump pressure observed.
Lot 6
P
r
o
p
e
r
t
y
L
i
n
e
P
r
o
p
e
r
t
y
L
i
n
eS u m m i tT r a i l8910
89208920893089306'
@
0%
Asphalt Drive
Prop
os
e
d
5
Be
dr
o
o
m
Resi
de
nce
1142
S
u
m
mit
Tr
ail
Lot 7,
Bl
oc
k
2,
Fili
n
g
3
6,
C
or
diller
a
FFE 8936.5'
Garage
FFE 8934.5'
FFE 8924.5'
FFE 8924.5'
FFE 8936.5'
Patio
Deck
(above)
(25.9')(2%)
26
323432893032
8930
28
26
2422343289302826242236
36343228
164' @ 4%2
0
'
@
4%
26.8'
33.2'
34' @ 4%
34.5'2628
30
32
3
4 382:1
32.4'
FFE 8934.5'
Inlet Rim
El. 33.5'
25.9'
2%
12'-0"
Inlet Rim
El. 23.0'
2:1Elec
t
r
ic
/Cab
le
/Gas
Cover Storage
12" inlet
invert out 8" HDPE storm=20.5'
Daylight 8" storm 19.5'
30'@3.3% slope
install rock rip rap at outlet
12" inlet
invert out 8" HDPE storm=31.5'
Daylight 8" storm 29.0'
98'@1% slope
install rock rip rap at outlet
Kumar & Associates
GRADATION ANALYSIS TEST
LABORATORY TEST REPORT DATA
Laboratory
Client:
Location / Plant:
Sample / Product:
Sample Date:
Lab Test Date:
Job Number:
SIEVE SIEVE OPENING IN
MILLIMETERS
PERCENT
PASSING THRU
SIEVE
3"75 100.0
1.5 37.5 100.0
3/4"19 100.0
3/8"9.5 100.0
No. 4 4.75 100.0
No. 8 2.36 81.0
No. 16 1.18 64.0
No. 30 0.6 45.0
No. 50 0.3 19.0
No. 100 0.15 6.0
No. 200 0.075 2.0
GRADATION RESULTS COMPARED TO PREFERRED AND SECONDARY SAND FILTER SPECIFICATIONS
Value Units
Preferred
Sand Value
Pass / Fail
Preferred
Sand
Secondary
Sand Value
Pass / Fail
Secondary
Sand
1.06 millimeters
0.196 millimeters 0.25 to 0.60 FAIL 0.15 to 0.60 PASS
5.39 unitless ratio < or = 4.0 FAIL < or = 7.0 PASS
2.0 millimeters < or = 3 PASS < or = 3 PASS
Effective Size - D10 - Diameter that 10 percent
of the sample is finer than.
Kumar Glenwood Springs
Pure Design Studio
Western Slope Materials - Silt
Secondary Sand
06/21/2023
Uniformity Coefficient (D60 / D10)
Percent passing thru #200 Sieve
06/21/2023
20-7-595.02
Parameter
D60 - Diameter that 60 percent of the sample is
finer than.
0
10
20
30
40
50
60
70
80
90
100
0.01 0.1 1 10 100Percent Passing SieveDiameter of Particle in Millimeters
Plot of Gradation Analysis
3"1.5"3/4"3/8"#4#8#30#50#100#200 #16
OWTS PHOTOGRAPH LOG
POWELL RESIDENCE
LOT 7, BLOCK 2, FILING 36, CORDILLERA
1142 SUMMIT TRAIL
EAGLE COUNTY, COLORADO
Project No. 20-7-595.02
Photograph 1: Sewer line
exiting residence, cleanout, and
Valley Precast 1,500-gallon, 3
chamber septic tank.
Photograph 2: Pump installed
in the third chamber of the septic
tank.
OWTS PHOTOGRAPH LOG
POWELL RESIDENCE
LOT 7, BLOCK 2, FILING 36, CORDILLERA
1142 SUMMIT TRAIL
EAGLE COUNTY, COLORADO
Project No. 20-7-595.02
Photograph 3: 1.5” Schedule 40
effluent transport line to soil
treatment area (STA).
Photograph 4: Soil treatment
area (STA): Infiltrator Quick4
Plus chambers distribution cell
over sand filter.
OWTS PHOTOGRAPH LOG
POWELL RESIDENCE
LOT 7, BLOCK 2, FILING 36, CORDILLERA
1142 SUMMIT TRAIL
EAGLE COUNTY, COLORADO
Project No. 20-7-595.02
Photograph 5: Control panel.
5020 County Road 154
Glenwood Springs, CO 81601
phone: (970) 945-7988
fax: (970) 945-8454
email: kaglenwood@kumarusa.com
www.kumarusa.com Office Locations: Denver (HQ), Parker, Colorado Springs, Fort Collins, Glenwood Springs, and Summit County, Colorado
PRELIMINARY ONSITE WASTEWATER TREATMENT SYSTEM DESIGN
PROPOSED POWELL RESIDENCE
LOT 7, BLOCK 2, FILING 36, CORDILLERA
1142 SUMMIT TRAIL
EAGLE COUNTY, COLORADO
PROJECT NO. 20-7-595.02
APRIL 4, 2022
PREPARED FOR:
PURE DESIGN STUDIO
ATTN: MILLIE ALDRICH
P. O. BOX 527
WOLCOTT, COLORADO 81655
(millie@puredesign-studio.com)
Kumar & Associates, Inc. Project No. 20-7-595.02
TABLE OF CONTENTS
INTRODUCTION ...................................................................................................................... - 1 -
PROPOSED CONSTRUCTION ................................................................................................ - 1 -
SITE CONDITIONS ................................................................................................................... - 1 -
SUBSURFACE CONDITIONS ................................................................................................. - 2 -
OWTS ANALYSIS .................................................................................................................... - 2 -
DESIGN RECOMMENDATIONS ............................................................................................ - 3 -
SOIL TREATMENT AREA................................................................................................... - 3 -
OWTS COMPONENTS ......................................................................................................... - 4 -
OWTS OPERATION AND MAINTENANCE.......................................................................... - 7 -
OWTS HOUSEHOLD OPERATION .................................................................................... - 7 -
OWTS MAINTENANCE ....................................................................................................... - 8 -
OWTS CONSTRUCTION OBSERVATION ............................................................................ - 8 -
LIMITATIONS ........................................................................................................................... - 8 -
FIGURES
FIGURE 1 – OWTS SITE PLAN
FIGURE 2 – SOIL TREATMENT AREA CALCULATIONS
FIGURE 3 – SOIL TREATMENT AREA PLAN VIEW
FIGURE 4 – SOIL TREATMENT AREA CROSS SECTION
FIGURE 5 – DISTRIBUTION LINE CLEANOUT DETAIL
ATTACHMENTS
VALLEY PRECAST 1,500 GALLON, THREE-CHAMBER SEPTIC TANK DETAIL
ORENCO PF3005 PUMP PERFORMANCE CURVE
Kumar & Associates, Inc. Project No. 20-7-595.02
INTRODUCTION
This report provides the preliminary results of an onsite wastewater treatment system (OWTS)
design for the proposed residence to be located on Lot 7, Block 2, Filing 36, Cordillera, 1142
Summit Trail, Eagle County, Colorado. The purpose of this report was to provide design details
for the OWTS in accordance with the 2018 Eagle County Onsite Wastewater Treatment System
Regulations and the Colorado Department of Public Health and Environment’s Regulation #43.
The study was performed as part of our agreement to Pure Design Studio dated February 21,
2022.
BACKGROUND INFORMATION
We previously prepared a subsoil study for foundation design of the residence and submitted our
findings in a report dated December 31, 2020, Project No. 20-7-595. Information from that
report has been considered in the preparation of the OWTS design.
Profile Pits have not been excavated at the time of this report due to considerable snow cover on
the site. Soil classification for the preliminary design is based on the borings from the previous
subsoil study which encountered shallow bedrock. Profile pits need to be excavated and subsoils
further evaluated to finalize the OWTS design prior to construction.
PROPOSED CONSTRUCTION
The residence will be a five-bedroom single-family structure with an attached garage located on
the lot as shown on Figure 1. The residence will have a walkout basement with a finish floor
elevation of 8,924.5 feet. The OWTS will be designed for a total of 5 bedrooms. The proposed
OWTS soil treatment area (STA) will be located to the east of the residence. Water service will
be provided to the residence by the public water supply from Summit Trail and the water service
line will likely go along the driveway alignment.
If proposed construction is different than that described, we should be contacted to re-evaluate
our final design recommendations.
SITE CONDITIONS
The lot was vacant at the time of field exploration and the ground surface appeared mostly
natural. The terrain is relatively flat in the uphill, northwest part of the building envelope. In the
area of the proposed residence and proposed STA, the terrain slopes moderately steep down to
the southeast at a grade of about 20%. Vegetation on the lot consists oak brush, sagebrush, grass
and weeds. No surface water features were observed in the near vicinity of the lot. We are not
aware of any nearby water wells.
- 2 -
Kumar & Associates, Inc. Project No. 20-7-595.02
SUBSURFACE CONDITIONS
The field exploration for the subsoil study was conducted on October 20, 2020. Two exploratory
borings were drilled at the locations shown on Figure 1 to evaluate the subsurface conditions.
The borings were advanced with 4 inch diameter continuous flight augers powered by a truck-
mounted CME-45B drill rig. The borings were logged by a representative of Kumar &
Associates.
Log of Boring 1
Depth USDA Classification
0-½’ TOPSOIL; organic loam, firm, slightly moist, dark brown.
½’-1’ SANDY CLAY; moderate blocky structure, stiff, slightly moist, dark brown.
1’-12’ WEATHERED SANDSTONE; hard, slightly moist, tan.
12’-31’ BASALT FLOW; clayey, hard to very hard, slightly moist, dark brown.
• Bottom of boring @ 31 feet.
• No free water or redoximorphic features observed at time of pit excavation.
Log of Boring 2
Depth USDA Classification
0-2’ TOPSOIL; organic loam, firm, slightly moist, dark brown.
2’-4’ SANDY CLAY; moderate blocky structure, stiff, slightly moist, dark brown.
4’-10’ WEATHERED BASALT AND ASH; clayey, sandy, hard to very hard, slightly
moist, tan and brown
10’-26’ BASALT FLOW; clayey, hard to very hard, slightly moist, dark brown.
• Bottom of boring @ 26 feet.
• No free water or redoximorphic features observed at time of pit excavation.
Based on the subsurface conditions encountered at the site and laboratory testing, the near
surface soils the site have been classified as Type 4 per State regulations, which equates to a
long-term acceptance rate (LTAR) of 0.20 gallons per square foot per day for the Clay soils.
OWTS ANALYSIS
Based on the site conditions, our previous subsoil study information and our experience in the
area, the clay soils are expansive and tend to swell when wetted. Based on these considerations
and the presence of shallow bedrock, we recommend a mounded sand wastewater treatment
system for proper treatment of the effluent. The system will consist of chambers in a bed
configuration overlying a sand filter placed on the native ground surface. The STA will be sized
five bedrooms (eight persons) using an LTAR of 0.8 gallons per square foot per day for imported
“secondary sand media”. The STA basal area of the sand will be sized for Soil Type 4 with an
LTAR of 0.20 gallons per square foot per day.
- 3 -
Kumar & Associates, Inc. Project No. 20-7-595.02
The sewage will gravity flow from the residence to the septic tank for primary treatment and then
be pressured-dosed on a regular basis to the STA for dispersal and final treatment. Pressure
dosing is necessary for the sand treatment system.
DESIGN RECOMMENDATIONS
The preliminary design recommendations presented below are based on the proposed
construction, the site and subsurface conditions encountered, and our experience in the area. A
layout of the proposed OWTS components is provided on Figure 1. If conditions encountered
during construction are different than those that are described in this report, please contact us to
re-evaluate our design recommendations. Profile Pit evaluations should be done at the STA for
final design of the system.
SOIL TREATMENT AREA
• The STA will consist of 2 rows of 22 Infiltrator Quick 4 Plus Standard chambers in a bed
configuration placed on imported secondary sand media. The sand media should be a
minimum 12 inches thick and be placed on the native ground surface. A pressure
distribution system will be used to disperse the effluent to the chambers on a regular
basis.
• The distribution cell was sized based on an LTAR of 0.80 gallons per square foot per day
for secondary sand media. The basal area was sized using an LTAR of 0.20 gallons per
square foot per day for Soil Type 4 for the natural Clay soils.
• A 30% reduction of the STA size was applied for use of Infiltrator chambers. The
proposed distribution cell will be 6 feet wide by 88 feet long (528 square feet).
• The minimum basal area of the mound is 88 feet long by 24 feet wide (2112 square feet).
• Soil treatment area calculations are shown on Figure 2.
• Vegetation should be removed and the ground surface scarified to at least 3” deep prior to
the sand placement.
• Distribution lines, consisting of 1.5-inch diameter, Schedule 40 piping, with ⅛-inch
diameter orifice holes drilled at 4-foot centers near the center of the Infiltrators, should be
installed along the complete length of the chambers, see Figure 3. The distribution lines
should be suspended approximately 2 inches from the top surface of the infiltrators by
pipe ties. The orifice holes should face up toward the infiltrator surface above.
• An ⅛-inch hole should be drilled on the bottom of each end of the distribution pipe to
allow for complete drainage of the distribution line following pressure dosing. Install
splash plates below drain holes.
- 4 -
Kumar & Associates, Inc. Project No. 20-7-595.02
• The sand bed should be oriented along ground contours to minimize soil cover.
• Sand filter material should extend one foot horizontally from the perimeter of the
chamber bed and then be sloped at 3 horizontal to 1 vertical maximum in all directions.
• The sand filter media should meet the requirements of the current Eagle County OWTS
Regulations for “secondary sand media”. ASTM C33 concrete sand is suitable for the
filter media. A sample of the sand filter media should be obtained within one month prior
to installation of the system for gradation analyses testing by us or the gradation test
results of the sand provided to us for approval.
• The sand filter material shall be placed in lifts not exceeding 10 inches thick. Each lift
shall be track or bucket compacted until settlement ceases.
• A minimum of 10 inches and a maximum of 24 inches of cover soil should be placed
over the chambers. The cover soil should include 6 inches of topsoil.
• Backfill should be graded to deflect surface water away from the STA and should be
sloped at 3 horizontal to 1 vertical or flatter. This may require a swale along the up-slope
side of the STA.
• Disturbed soil should be re-vegetated as soon as possible with a native grass mix. No
trees, shrubs or other plants with deep roots should be planted on or near the STA as this
may damage the system piping.
• Four-inch diameter inspection ports should be installed vertically into the knockouts
provided in the Infiltrator end caps. Install ports at each corner of the bed. The
inspection port piping should be screwed into the top to the chambers and should not
extend down to the ground surface inside the chambers. The inspection ports should
extend at least 8 inches above the finished ground surface or be protected in a valve box
at finished grade.
• The minimum setback from the STA to the water service supply line is 25 feet. Where
the water line encroaches on the setback, the water line must be encased with larger
diameter Schedule 40 PVC pipe in a watertight manner throughout the encroachment.
• A plan view of the STA is presented on Figure 3 and a cross section of the STA is
presented on Figure 4.
• Cleanouts are required at the end of the distribution line. See Figure 5 for the cleanout
detail.
OWTS COMPONENTS
Recommended OWTS components provided below are based on our design details and our
experience with the specific component manufacturers. Equivalent components may be feasible
but need to be approved by us prior to construction.
- 5 -
Kumar & Associates, Inc. Project No. 20-7-595.02
Septic Tank
• A 1,500 gallon, three-chamber septic tank (2,000 gallons total) will be used for primary
treatment and dosing to the STA. The first two chambers of the tank will be utilized for
treatment and settling, and the third chamber of the tank will contain the dosing pump. A
detail of the tank is provided as an attachment to the report.
• A submersible effluent pump enclosed in a Biotube Pump Vault will be installed in the
third chamber.
• The tank must be a minimum of five feet from the residence and from the STA. The tank
must be a minimum of 10 feet from any potable water supply lines.
• The tank must be set level. The excavation bottom must be free of large rocks or other
objects that could damage the tank during placement. A road base or gravel bedding
material may be needed to prevent tank damage during placement and act as a leveling
course.
• The tank lids must extend to final surface grade and made to be easily located.
• Install the tank with 2 feet minimum cover soil for frost protection. Maximum tank soil
cover is 4 feet.
Sewer Pipe
• The sewer line to the septic tank should not be less than the diameter of the building
drains and not less than 4 inches in diameter.
• The sewer pipe should have a rating of SDR35 or stronger.
• The sewer pipe should be sloped between 2% to 4% to help limit disturbance of solids in
the tank and the potential for sewage bypass of the first chamber of the tank. If a steeper
slope is needed, this can be accomplished with vertical step-downs in the sewer line.
• A minimum 36 inches of cover soil should be provided over the sewer pipe. Paved areas,
patios or other areas without vegetative cover may be more susceptible to frost and we
recommend 48 inches of soil cover over the sewer pipe in these areas, and the pipe be
insulated on top and sides with 2-inch-thick blue foam insulation board. If adequate soil
cover is not possible, we should be contacted for re-evaluation prior to installation.
• The sewer pipe should be bedded in compacted ¾ inch road base or native soils provided
that the native soils contain no angular rocks or rocks larger than 2½ inches in diameter
to help prevent settlement of the pipe. Sags in the pipe could cause standing effluent to
freeze and damage the piping.
• Install cleanout pipes within 5 feet of the building foundation, where the sewer pipe
bends 90 degrees or more and at every 100 feet of sewer pipe.
- 6 -
Kumar & Associates, Inc. Project No. 20-7-595.02
• All 90-degree bends should be installed using a 90-degree long-sweep or by using two
45-degree elbows.
• The sewer line location shown on Figure 1 is considered conceptual. We assume that
there will be only one sewer line exiting the residence. It is the responsibility of the
owner/contractors to locate all sewer line exit locations and connections to the septic
tank. We should be notified if there are more than one sewer line exiting the building.
Effluent Transport Piping
• The effluent transport pipe should be 1.5-inch diameter Schedule 40 piping sloped at a
2% minimum to drain to the STA.
• The effluent transport pipe should be bedded in compacted ¾ inch road base or native
soils provided that the native soils contain no angular rocks or rocks larger than
2½ inches in diameter to help prevent settlement of the pipe. Sags could cause standing
effluent to freeze and damage to the piping.
• A minimum 18 inches of cover soil should be provided over the effluent transport pipe.
Paved areas, patios or other areas without vegetative cover may be more susceptible to
frost. We recommend 48 inches of soil cover over the effluent pipe and insulation with at
least 2 inches of rigid foam insulation in these areas. If adequate cover soil is not
possible, we should re-evaluate the condition prior to installation.
• The effluent pipe should be encased with larger diameter Schedule 40 PVC pipe
underneath driveway surfaces and be provided with at least 48 inches of soil cover and be
insulated on top and sides with 2-inch-thick foam insulation board.
• All 90-degree bends should be installed using a 90 degree long-sweep or by using two
45-degree elbows.
• The minimum setback from the effluent line to the water supply line is 5 feet. Where the
water line encroaches on the setback and crosses the effluent line at the driveway, either
the water line or the effluent line must be encased with larger diameter Schedule 40 PVC
pipe in a watertight manner throughout the encroachment.
Effluent Pumping System
• An Orenco PF3005, 115-volt, submersible effluent pump with a 1.5-inch diameter
discharge assembly, or equivalent, will be required for the effluent pumping.
• The maximum effluent transport distance from the pump discharge to the STA estimated
to be 60 feet.
• The elevation difference from pump discharge to the STA is estimated to be 4 feet of
drop.
- 7 -
Kumar & Associates, Inc. Project No. 20-7-595.02
• The pump should be enclosed in an Orenco Biotube Pump Vault for effluent filtering and
protection of the pump from vibration.
• An equivalent pump must be capable of operating at 20.0 gallons per minute at 4.1 feet of
total dynamic head. A pump performance curve is provided as an attachment to this
report.
• The floats should be set to provide a dose volume of approximately 104 gallons. The
actual dose volume will be about 104 gallons in the transport line. To achieve the desired
dose volume, the upper (“ON”) and lower (“OFF”) floats should be set approximately
10½ inches apart.
• The flow differential between the first and last orifices is estimated to be 2.0%.
• The high-water alarm float should be placed approximately 3 inches above the “ON”
float in the dose tank. The high-water alarm must be wired on a separate electrical circuit
from the pump.
• An ⅛-inch diameter weep hole should be drilled in the effluent transport line prior to
exiting the dose tank so the transport line can drain after each pumping cycle.
OWTS OPERATION AND MAINTENANCE
The OWTS will require periodic inspection and maintenance to function properly. A properly
designed, installed and maintained system can greatly increase its lifespan. The level of
maintenance will vary depending on the complexity of the system and water use habits of the
residents. We recommend that an OWTS Operation and Maintenance (O&M) Manual be
developed. Depending on the complexity of the system, a contract with an OWTS maintenance
provider may be prudent. Below are some basic recommendations for the OWTS O&M.
OWTS HOUSEHOLD OPERATION
• Use of high efficiency water fixtures is recommended to decrease the hydraulic load on
the OWTS system.
• Fix plumbing leaks immediately as this may cause a hydraulic overload of the soil
absorption system.
• Do not irrigate the area on top of or directly upgradient of the soil absorption field as this
may cause a hydraulic overload.
• Do not dispose of household waste down drains as this may clog or damage OWTS
components. Examples of household waste includes: dental floss, cotton swabs, coffee
grounds, paper towels, feminine products and many other kitchen and bath items.
• Use of kitchen garbage disposals is not recommended. If a garbage disposal is utilized,
kitchen wastewater should be screened thoroughly. Many kitchen solids are not
decomposed in the septic tank and may cause increased tank pumping frequency.
- 8 -
Kumar & Associates, Inc. Project No. 20-7-595.02
• Do not dispose of household chemicals, greases, oils, paints, hot tub water or water
softener backwash in household drains. A separate drywell, if feasible, may be necessary
for hot tub water or water softener backwash disposal.
• Limit the use of bleach as this may harm useful bacteria in the septic tank and soil
absorption system.
• Liquid dishwasher and clothes washer detergent is recommended for households served
by an OWTS. Clay substances used as fillers in powder detergents may result in
clogging of the soil absorption system.
• The effluent in septic tanks can freeze during extended periods of non-use in cold
weather. We recommend that a tank heater be installed in this system to help prevent
freezing.
OWTS MAINTENANCE
• Inspect the septic tank, pump, pump vault filter and STA at least annually for problems or
signs of failure.
• The filter should be cleaned annually by spray washing solids into the first chamber of
the septic tank.
• The septic tank should be pumped and cleaned about every 3 to 5 years depending on
use. Longer pumping intervals may increase the amount of solids that reach the STA,
which may shorten its life span.
• Pumping of the septic tank should take place when the level of the sludge and scum
layers combined take up 25 to 33% of the capacity of the first chamber of the tank.
OWTS CONSTRUCTION OBSERVATION
The Eagle County Environmental Health Department requires that the designer of the system
provide a record drawing and certification of the OWTS construction (As-Built inspection). We
should be provided with at least 48-hour notice prior to the installer needing the inspections.
Prior to issuance of our certification letter, we require observation of all system components
prior to backfill. The As-Built inspection will include a pump test for the system. The number
of site visits required for the inspection will depend on the installer’s construction schedule.
LIMITATIONS
We have conducted this design in accordance with generally accepted engineering principles and
practices in this area at this time. We make no warranty either expressed or implied. The
recommendations provided in this report are based on the site conditions, the proposed
construction, assumed subsurface conditions and our experience in the area. Additional profile
pit evaluations should be done at the soil treatment area prior to construction.
Lot 6
P
r
o
p
e
r
t
y
L
i
n
e
P
r
o
p
e
r
t
y
L
i
n
e
Lot 8 S u m
m i t
T r a i l
8890
89008910
891089208920893089306'
@
0%
Asphalt Drive
Prop
ose
d 5
Be
dr
o
o
m
R
esi
d
e
nce
1142
S
u
m
mit
Tr
ail
Lot 7,
Bl
oc
k
2,
Fili
n
g
36,
C
or
diller
a
FFE 8936.5'
Garage
FFE 8934.5'
FFE 8924.5'
FFE 8924.5'
FFE 8936.5'
Patio
Deck
(above)
(25.9')(2%)
26
24
8930
32323432893032
8930
28
26
2422343289302826242236
36343228
164' @ 4%2
0
'
@
4%
26.8'
33.2'
34' @ 4%
34.5'2628
30
32
34 382:1
32.4'
FFE 8934.5'
Inlet Rim
El. 33.5'
25.9'
2%
12'-0"
Inlet Rim
El. 23.0'
2:1Ele
c
t
r
ic
/Cab
le
/Ga
s
Electric/
Cable/
Gas
Cover Storage
12" inlet
invert out 8" HDPE storm=20.5'
Daylight 8" storm 19.5'
30'@3.3% slope
install rock rip rap at outlet
12" inlet
invert out 8" HDPE storm=31.5'
Daylight 8" storm 29.0'
98'@1% slope
install rock rip rap at outlet
Kumar & Associates
Kumar & Associates
Kumar & Associates
NATIVE SOILS
REMOVE VEGETATION AND SCARIFY
UPPER 3" OF GROUND SURFACE
PRIOR TO SAND PLACEMENT
INFILTRATOR QUICK 4 PLUS
STANDARD CHAMBERS
EXISTING
G
R
O
U
N
D
S
U
R
F
A
C
E
SAND FILTER PLACED ON
EXISTING GROUND SURFACE
4" DIAMETER
OBSERVATION PORT
6.0'
8.0'
10" COVER SOIL.
3:1 MAX. SLOPE.
24.0' MINIMUM
BASAL WIDTH
1.0' MIN SAND
FILTER UNDER
CHAMBERS
Kumar & Associates
Notes:
1.Chambers should be installed level on top of minimum 1 foot of concrete sand.
The ground surface should be scarified prior to sand placement.
2.Care should be taken by the contractor to avoid compaction of the native soils in
the bed area.
3.Changes to this design should not be made without consultation and approval
by Kumar and Associates.
Kumar & Associates
NOT TO SCALE
NRWHV
AOO SLSLQJ ILWWLQJV DQG YDOYHV VKRXOG EH SFK 39C
,QVWDOO GLVWULEXWLRQ OLQH FOHDQRXWV DW WKH HQG RI HDFK GLVWULEXWLRQ OLQH
Pump Selection for a Pressurized System - Single Family Residence Project
20-7-595.02 / 1142 Summit Trail
Parameters
Discharge Assembly Size
Transport Length
Transport Pipe Class
Transport Line Size
Distributing Valve Model
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
1.50
66
40
1.50
None
-4
3
40
1.50
2
88
40
1.50
1/8
4
5
None
0
inches
feet
inches
feet
feet
inches
feet
inches
inches
feet
feet
inches
feet
Calculations
Minimum Flow Rate per Orifice
Number of Orifices per Zone
Total Flow Rate per Zone
Number of Laterals per Zone
% Flow Differential 1st/Last Orifice
Transport Velocity
0.43
46
20.0
2
2.0
3.2
gpm
gpm
%
fps
Frictional Head Losses
Loss through Discharge
Loss in Transport
Loss through Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
'Add-on' Friction Losses
1.2
1.6
0.0
0.0
0.2
0.0
0.0
feet
feet
feet
feet
feet
feet
feet
Pipe Volumes
Vol of Transport Line
Vol of Manifold
Vol of Laterals per Zone
Total Volume
6.9
0.3
18.6
25.9
gals
gals
gals
gals
Minimum Pump Requirements
Design Flow Rate
Total Dynamic Head
20.0
4.1
gpm
feet
0 5 10 15 20 25 30 35 40
0
50
100
150
200
250
300
Net Discharge (gpm)
PumpData
PF3005 High Head Effluent Pump
30 GPM, 1/2HP
115/230V 1Ø 60Hz, 200V 3Ø 60Hz
Legend
System Curve:
Pump Curve:
Pump Optimal Range:
Operating Point:
Design Point:
5020 County Road 154
Glenwood Springs, CO 81601
phone: (970) 945-7988
fax: (970) 945-8454
email: kaglenwood@kumarusa.com
www.kumarusa.com Office Locations: Denver (HQ), Parker, Colorado Springs, Fort Collins, Glenwood Springs, and Summit County, Colorado
SUBSOIL STUDY
FOR FOUNDATION DESIGN
PROPOSED RESIDENCE
LOT 7, BLOCK 2, FILING 36, CORDILLERA
1142 SUMMIT TRAIL
EAGLE COUNTY, COLORADO
PROJECT NO. 20-7-595
DECEMBER 31, 2020
PREPARED FOR:
TOM GRANT
2413 ROBERT BROWNING
AUSTIN, TEXAS 78723
(tgrant@empirecommunities.com)
Kumar & Associates, Inc. ® Project No. 20-7-595
TABLE OF CONTENTS
PURPOSE AND SCOPE OF STUDY ....................................................................................... - 1 -
PROPOSED CONSTRUCTION ................................................................................................ - 1 -
SITE CONDITIONS ................................................................................................................... - 1 -
FIELD EXPLORATION ............................................................................................................ - 2 -
SUBSURFACE CONDITIONS ................................................................................................. - 2 -
FOUNDATION BEARING CONDITIONS .............................................................................. - 3 -
DESIGN RECOMMENDATIONS ............................................................................................ - 3 -
FOUNDATIONS .................................................................................................................... - 3 -
FOUNDATION AND RETAINING WALLS ....................................................................... - 4 -
FLOOR SLABS ...................................................................................................................... - 5 -
UNDERDRAIN SYSTEM ..................................................................................................... - 6 -
SURFACE DRAINAGE ......................................................................................................... - 6 -
LIMITATIONS ........................................................................................................................... - 7 -
FIGURE 1 - LOCATION OF EXPLORATORY BORINGS
FIGURE 2 - LOGS OF EXPLORATORY BORINGS
FIGURE 3 - LEGEND AND NOTES
FIGURES 4 and 5- SWELL-CONSOLIDATION TEST RESULTS
TABLE 1- SUMMARY OF LABORATORY TEST RESULTS
Kumar & Associates, Inc. ® Project No. 20-7-595
PURPOSE AND SCOPE OF STUDY
This report presents the results of a subsoil study for a proposed residence to be located on Lot 7,
Block 2, Filing 36, Cordillera, Eagle County, Colorado. The project site is shown on Figure 1.
The purpose of the study was to develop recommendations for the foundation design. The study
was conducted in accordance with our agreement for geotechnical engineering services to Tom
Grant dated October 8, 2020.
A field exploration program consisting of exploratory borings was conducted to obtain
information on the subsurface conditions. Samples of the subsoils and bedrock obtained during
the field exploration were tested in the laboratory to determine their classification,
compressibility or swell and other engineering characteristics. The results of the field
exploration and laboratory testing were analyzed to develop recommendations for foundation
types, depths and allowable pressures for the proposed building foundation. This report
summarizes the data obtained during this study and presents our conclusions, design
recommendations and other geotechnical engineering considerations based on the proposed
construction and the subsurface conditions encountered.
PROPOSED CONSTRUCTION
The proposed residence will be a one or two story structure possibly over a walkout basement
level with attached garage and located generally as shown on Figure 1. Ground floors could be
structural over crawlspace or slab-on-grade. Grading for the structure is assumed to be relatively
minor with cut depths between about 2 to 10 feet. We assume relatively light foundation
loadings, typical of the proposed type of construction.
If building loadings, location or grading plans change significantly from those described above,
we should be notified to re-evaluate the recommendations contained in this report.
SITE CONDITIONS
The subject site was vacant at the time of our field exploration. The ground surface is relatively
flat in the uphill, northwest part of the building envelope sloping moderately steep down to the
southeast at a grade of about 20 percent. Vegetation consists of sagebrush, oak brush, grass and
weeds.
- 2 -
Kumar & Associates, Inc. ® Project No. 20-7-595
FIELD EXPLORATION
The field exploration for the project was conducted on October 20, 2020. Two exploratory
borings were drilled at the locations shown on Figure 1 to evaluate the subsurface conditions.
The borings were advanced with 4 inch diameter continuous flight augers powered by a truck-
mounted CME-45B drill rig. The borings were logged by a representative of Kumar &
Associates, Inc.
Samples of the subsoils were taken with 1⅜ inch and 2 inch I.D. spoon samplers. The samplers
were driven into the subsoils at various depths with blows from a 140 pound hammer falling 30
inches. This test is similar to the standard penetration test described by ASTM Method D-1586.
The penetration resistance values are an indication of the relative density or consistency of the
subsoils and hardness of the bedrock. Depths at which the samples were taken and the
penetration resistance values are shown on the Logs of Exploratory Borings, Figure 2. The
samples were returned to our laboratory for review by the project engineer and testing.
SUBSURFACE CONDITIONS
Graphic logs of the subsurface conditions encountered at the site are shown on Figure 2. The
subsoils consist of about ½ to 2 feet of topsoil overlying loose to medium dense sand and clay to
between 1 and 4 feet deep underlain by weathered sandstone in Boring 1 and clayey basalt and
ash in Boring 2 to between 10 to 12 feet in depth. Basalt rock was encountered below the
sandstone and ash to the maximum explored depth of 31 feet.
Laboratory testing performed on samples obtained from the borings included natural moisture
content and gradation analyses. Results of swell-consolidation testing performed on a relatively
undisturbed drive sample of the clay, presented on Figure 4, indicate low to moderate
compressibility under existing moisture conditions and light loading and a moderate expansion
potential wetted. Results of swell-consolidation testing performed on a relatively undisturbed
drive sample of the weathered basalt and ash, presented on Figure 5, indicate low to moderate
compressibility under conditions of loading and wetting. The laboratory testing is summarized
in Table 1.
No free water was encountered in the borings at the time of drilling and the subsoils and rock
were slightly moist to moist.
- 3 -
Kumar & Associates, Inc. ® Project No. 20-7-595
FOUNDATION BEARING CONDITIONS
The upper clay soils encountered in the borings possess a swell potential when wetted. The
underlying weathered sandstone and weathered basalt rock possess a moderate bearing capacity
and typically low settlement potential. At assumed excavation depths, we expect the subgrade
will consist of sandstone and basalt/ash rock.
Spread footings bearing on the sandstone and basalt/ash rock should be feasible for foundation
support of the proposed building with a risk of movement due to variable bearing conditions
across the different materials. The effects of differential movement can be limited by heavily
reinforcing the foundation. The foundation excavation should be evaluated for expansive soils
which should be removed from below foundation and slab areas and replaced with compacted
structural fill.
DESIGN RECOMMENDATIONS
FOUNDATIONS
Considering the subsurface conditions encountered in the exploratory borings and the nature of
the proposed construction, we recommend the building be founded with spread footings bearing
on the sandstone and basalt/ash rock below expansive clay soils.
The design and construction criteria presented below should be observed for a spread footing
foundation system.
1) Footings placed on the undisturbed sandstone and basalt/ash should be designed
for an allowable bearing pressure of 2,500 psf. Based on experience, we expect
settlement of footings designed and constructed as discussed in this section will
be about 1 inch or less.
2) The footings should have a minimum width of 16 inches for continuous walls and
2 feet for isolated pads.
3) Exterior footings and footings beneath unheated areas should be provided with
adequate soil cover above their bearing elevation for frost protection. Placement
of foundations at least 42 inches below exterior grade is typically used in this
area.
- 4 -
Kumar & Associates, Inc. ® Project No. 20-7-595
4) Continuous foundation walls should be heavily reinforced top and bottom to span
local anomalies, such as across material transitions, by assuming an unsupported
length of at least 12 feet. Foundation walls acting as retaining structures should
also be designed to resist lateral earth pressures as discussed in the "Foundation
and Retaining Walls" section of this report.
5) Topsoil, expansive clay and any loose disturbed soils and rock should be removed
and the footing bearing level extended down to the undisturbed natural soils or
rock. The exposed soils in footing area should then be moistened and compacted.
If water seepage is encountered, the footing areas should be dewatered before
concrete placement. Structural fill should be a non-expansive granular material
such as CDOT Class 6 road base compacted to at least 98% of standard Proctor
density at near optimum moisture content.
6) A representative of the geotechnical engineer should observe all footing
excavations prior to concrete placement to evaluate bearing conditions.
FOUNDATION AND RETAINING WALLS
Foundation walls and retaining structures which are laterally supported and can be expected to
undergo only a slight amount of deflection should be designed for a lateral earth pressure
computed on the basis of an equivalent fluid unit weight of at least 50 pcf for backfill consisting
of the on-site predominantly granular soils. Cantilevered retaining structures which are separate
from the residence and can be expected to deflect sufficiently to mobilize the full active earth
pressure condition should be designed for a lateral earth pressure computed on the basis of an
equivalent fluid unit weight of at least 40 pcf for backfill consisting of the on-site predominantly
granular soils. The backfill should not contain topsoil or oversized (plus 6-inch) rocks.
All foundation and retaining structures should be designed for appropriate hydrostatic and
surcharge pressures such as adjacent footings, traffic, construction materials and equipment. The
pressures recommended above assume drained conditions behind the walls and a horizontal
backfill surface. The buildup of water behind a wall or an upward sloping backfill surface will
increase the lateral pressure imposed on a foundation wall or retaining structure. An underdrain
should be provided to prevent hydrostatic pressure buildup behind walls.
- 5 -
Kumar & Associates, Inc. ® Project No. 20-7-595
Backfill should be placed in uniform lifts and compacted to at least 90% of the maximum
standard Proctor density at a moisture content near optimum. Backfill placed in pavement and
walkway areas should be compacted to at least 95% of the maximum standard Proctor density.
Care should be taken not to overcompact the backfill or use large equipment near the wall, since
this could cause excessive lateral pressure on the wall. Some settlement of deep foundation wall
backfill should be expected, even if the material is placed correctly, and could result in distress to
facilities constructed on the backfill.
The lateral resistance of foundation or retaining wall footings will be a combination of the
sliding resistance of the footing on the foundation materials and passive earth pressure against
the side of the footing. Resistance to sliding at the bottoms of the footings can be calculated
based on a coefficient of friction of 0.45. Passive pressure of compacted backfill against the
sides of the footings can be calculated using an equivalent fluid unit weight of 375 pcf. The
coefficient of friction and passive pressure values recommended above assume ultimate soil
strength. Suitable factors of safety should be included in the design to limit the strain which will
occur at the ultimate strength, particularly in the case of passive resistance. Fill placed against
the sides of the footings to resist lateral loads should be a granular material compacted to at least
95% of the maximum standard Proctor density at a moisture content near optimum.
FLOOR SLABS
The on-site clay soils possess an expansion potential and slab heave could occur if the clay
subgrade soils become wetted. Exposed clay subgrade should be evaluated for expansion
potential and removed as needed and replaced with compacted structural fill. Crawlspace
construction could also be used to avoid slabs bearing on expansive soils.
To reduce the effects of some differential movement, floor slabs should be separated from all
bearing walls and columns with expansion joints which allow unrestrained vertical movement.
Floor slab control joints should be used to reduce damage due to shrinkage cracking. The
requirements for joint spacing and slab reinforcement should be established by the designer
based on experience and the intended slab use. A minimum 4 inch layer of free-draining gravel
should be placed beneath basement level slabs to facilitate drainage. This material should
consist of minus 2-inch aggregate with at least 50% retained on the No. 4 sieve and less than 2%
passing the No. 200 sieve.
- 6 -
Kumar & Associates, Inc. ® Project No. 20-7-595
All fill materials for support of floor slabs should be compacted to at least 95% of maximum
standard Proctor density at a moisture content near optimum. Required fill should consist of
granular soils devoid of vegetation, topsoil and oversized rock.
We recommend vapor retarders conform to at least the minimum requirements of ASTM E1745
Class C material. Certain floor types are more sensitive to water vapor transmission than others.
For floor slabs bearing on angular gravel or where flooring system sensitive to water vapor
transmission are utilized, we recommend a vapor barrier be utilized conforming to the minimum
requirements of ASTM E1745 Class A material. The vapor retarder should be installed in
accordance with the manufacturers’ recommendations and ASTM E1643.
UNDERDRAIN SYSTEM
Although free water was not encountered during our exploration, it has been our experience in
the area and where clay soils are present that local perched groundwater can develop during
times of heavy precipitation or seasonal runoff. Frozen ground during spring runoff can create a
perched condition. We recommend below-grade construction, such as retaining walls,
crawlspace and basement areas, be protected from wetting and hydrostatic pressure buildup by
an underdrain system.
The drains should consist of drainpipe placed in the bottom of the wall backfill surrounded above
the invert level with free-draining granular material. The drain should be placed at each level of
excavation and at least 1 foot below lowest adjacent finish grade and sloped at a minimum 1% to
a suitable gravity outlet. If rigid PVC drain-pipe is used, which we recommend, the pipe slope
can be reduced to a minimum ½%. Free-draining granular material used in the underdrain
system should contain less than 2% passing the No. 200 sieve, less than 50% passing the No. 4
sieve and have a maximum size of 2 inches. The drain gravel backfill should be at least 1½ feet
deep and covered with filter fabric such as Mirafi 140N or 160N.
SURFACE DRAINAGE
The following drainage precautions should be observed during construction and maintained at all
times after the residence has been completed:
1) Inundation of the foundation excavations and underslab areas should be avoided
during construction.
- 7 -
Kumar & Associates, Inc. ® Project No. 20-7-595
2) Exterior backfill should be adjusted to near optimum moisture and compacted to
at least 95% of the maximum standard Proctor density in pavement and slab areas
and to at least 90% of the maximum standard Proctor density in landscape areas.
3) The ground surface surrounding the exterior of the building should be sloped to
drain away from the foundation in all directions. We recommend a minimum
slope of 12 inches in the first 10 feet in unpaved areas and a minimum slope of
3 inches in the first 10 feet in paved areas. Free-draining wall backfill should be
covered with filter fabric and capped with about 2 feet of the on-site finer graded
soils to reduce surface water infiltration.
4) Roof downspouts and drains should discharge well beyond the limits of all
backfill.
5) Landscaping which requires regular heavy irrigation should be located at least
5 feet from foundation walls.
LIMITATIONS
This study has been conducted in accordance with generally accepted geotechnical engineering
principles and practices in this area at this time. We make no warranty either express or implied.
The conclusions and recommendations submitted in this report are based upon the data obtained
from the exploratory borings drilled at the locations indicated on Figure 1, the proposed type of
construction and our experience in the area. Our services do not include determining the
presence, prevention or possibility of mold or other biological contaminants (MOBC) developing
in the future. If the client is concerned about MOBC, then a professional in this special field of
practice should be consulted. Our findings include interpolation and extrapolation of the
subsurface conditions identified at the exploratory borings and variations in the subsurface
conditions may not become evident until excavation is performed. If conditions encountered
during construction appear different from those described in this report, we should be notified so
that re-evaluation of the recommendations may be made.
This report has been prepared for the exclusive use by our client for design purposes. We are not
responsible for technical interpretations by others of our information. As the project evolves, we
should provide continued consultation and field services during construction to review and
TABLE 1
SUMMARY OF LABORATORY TEST RESULTS
Project No. 20-7-595
SAMPLE LOCATION NATURAL MOISTURE CONTENT
NATURAL DRY DENSITY
GRADATION
PERCENT PASSING NO. 200 SIEVE
ATTERBERG LIMITS UNCONFINED COMPRESSIVE STRENGTH SOIL TYPE BORING DEPTH GRAVEL SAND LIQUID LIMIT PLASTIC INDEX (%) (%)
(ft) (%) (pcf) (%) (%) (psf)
1 1 5.6 121 Weathered Sandstone
7 12.6 112 Weathered Sandstone
2 4 14.6 100 43 Clay with Basalt Fragments
7 24.7 102 Weathered Ash