HomeMy WebLinkAbout21234_Haymeadow_BLDG G_PERMIT RESUBMITTAL_ELEC_2023-03-03_StampedABBREVIATIONS DUPLEX RECEPTACLE, MOUNTED +18" O.C. UNO AC = MOUNTED +8" O.C. ABOVE COUNTER EWC = GFI RECEPTACLE FOR WATER COOLER GFI = GROUND FAULT CIRCUIT INTERRUPTER T = TAMPER RESISTANT PER NEC 406.12(A) WP = GFCI WITH WEATHERPROOF IN-USE COVER PER NEC 406.9(B)(1) DUPLEX RECEPTACLE LISTED FOR USE IN COUNTERTOPS, PROTECTED BY UPSTREAM GFCI DUPLEX RECEPTACLE, FLUSH MOUNTED IN FLOOR BOX QUADRUPLEX RECEPTACLE, MOUNTED +18" O.C. UNO AC = MOUNTED +8" O.C. ABOVE COUNTER GFCI = GROUND FAULT CIRCUIT INTERRUPTER T = TAMPER RESISTANT PER NEC 406.12 WP = GFCI WITH WEATHERPROOF IN-USE COVER QUADRUPLEX RECEPTACLE, FLUSH MOUNTED IN FLOOR BOX SPECIAL RECEPTACLE, COORDINATE INSTALLATION WITH EQUIPMENT SUPPLIED ED = ELECTRIC DRYER, PROVIDE 208V/1, 30A-2P 4-WIRE CONNECTION. ER = ELECTRIC RANGE, PROVIDE 208V/1, 50A-2P 4-WIRE CONNECTION. COUNTER-MOUNTED AIR SWITCH FOR GARBAGE DISPOSAL. COORDINATE WITH MILLWORK VENDOR. MOTOR CONNECTION, COORDINATE INSTALLATION WITH EQUIPMENT SUPPLIED G = GARAGE DOOR MOTOR ASSEMBLY WITH INTEGRAL LIGHTING COMPONENT JUNCTION BOX SIZE PER NEC 314, PROVIDE COVER PLATE TO CONCEAL WIRING WITHIN PANELBOARD ELECTRICAL BRANCH CIRCUIT -PROTECTED PER NEC 240.4(D) REQUIREMENTS DISCONNECT SWITCH (F = FUSIBLE) UTILITY COMPANY METER ELECTRICAL SYMBOL LIST A AMP AC ABOVE COUNTER AFC ABOVE FINISHED CEILING AFF ABOVE FINISHED FLOOR AFI ARC FAULT INTERRUPTER AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT AIC AMPS INTERRUPTING CAPACITY AL ALUMINUM AWG AMERICAN WIRE GAUGE AV AUDIO/VISUAL BLDG BUILDING C CONDUIT CATV CABLE TELEVISION SYSTEM CCTV CLOSED CIRCUIT TELEVISION CKT CIRCUIT CL CENTERLINE CU COPPER DWG DRAWING (E)EXISTING EF EXHAUST FAN EMT ELECTRIC METALLIC TUBING EM EMERGENCY EPO EMERGENCY POWER OFF FLA FULL LOAD AMPS GD GARBAGE DISPOSAL GR GROUND GC GENERAL CONTRACTOR GFI/GFCI GROUND FAULT CIRCUIT INTERRUPTER HACR HACR (HEATING, AC & REFRIGERATION) RATED HP HORSE POWER IG ISOLATED GROUND IP INTERNET PROTOCOL JB JUNCTION BOX KCMIL 1000 CIRCULAR MILS KV KILOVOLT KVA KILOVOLT AMPERES KW KILOWATT KWH KILOWATT HOUR LAN LOCAL AREA NETWORK LCP LIGHTING CONTROL PANEL LRA LOCKED ROTOR AMPS LSIGA L(LONG) S (SHORT) I (INSTANTANEOUS) G (GROUND FAULT) A (ARC ENERGY REDUCTION) LTFC LIQUID TIGHT FLEXIBLE CONDUIT MC MECHANICAL CONTRACTOR MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MDP MAIN DISTRIBUTION PANEL MFR MANUFACTURER MLO MAIN LUG ONLY MSB MAIN SWITCH BOARD (N)NEW N.C.NORMALLY CLOSED N.O.NORMALLY OPEN NF NON-FUSED NL NIGHT LIGHT NIC NOT IN CONTRACT P POLE PC PLUMBING CONTRACTOR PH PHASE PPE PERSONAL PROTECTION EQUIPMENT PVC POLYVINYL CHLORIDE CONDUIT QTY QUANTITY RCP REFLECTED CEILING PLAN RLA RUNNING LOAD AMPS RMC RIGID METAL CONDUIT RNC RIGID NON-METALLIC CONDUIT SPDT SINGLE POLE, DOUBLE THROW SPST SINGLE POLE, SINGLE THROW ST SHUNT TRIP TL TWISTLOCK TR TAMPER RESISTANT TYP TYPICAL UL UNDERWRITERS LABORATORIES, INC. UNO UNLESS NOTED OTHERWISE USP UNINTERRUPTIBLE POWER SUPPLY V VOLT W WIRE WP WEATHER PROOF WPI WEATHER PROTECTED IN-USE XFMR TRANSFORMER XP EXPOSION PROOF LABELING REQUIREMENTS ALL ELECTRICAL LABELS SHALL COMPLY WITH LATEST NATIONAL ELECTRICAL CODE REQUIREMENTS. GENERAL LABELING REQUIREMENTS NOTED BELOW MAY NOT BE COMPLETE OR COVER ALL INSTALLATIONS. WIRING DEVICES: PANEL NAME -CIRCUIT NAME PROVIDE BLACK LETTERING ON CLEAR LABEL FOR NORMAL CIRCUITS AND RED LETTERING ON CLEAR LABEL FOR EMERGENCY/STANDBY CIRCUITS. STARTERS / DISCONNECTS / VFDs: EQUIPMENT ID VOLTAGE / PHASE / WIRES INDICATE FUSE SIZE, IF APPLICABLE FED FROM CIRCUIT NAME FEEDING TO CIRCUIT NAME ARC FLASH LABELS PER NFPA-70E & NEC INDICATING: 1. DANGER OR WARNING HEADER 2. INCIDENT ENERGY 3. MINIMUM ARC RATING 4. ARC FLASH BOUNDARY 5. PERSONAL PROTECTIVE EQUIPMENT (PPE) 6. LIMITED APPROACH 7. RESTRICTED APPROACH 8. SHOCK RISK 9. DATE LABEL WAS APPLIED SWITCHBOARDS, TRANSFORMERS, HARMONIC FILTERS, ELECTRICAL PANELS: EQUIPMENT NAME EQUIPMENT RATING FED FROM XXXX VOLTAGE / PHASE / AMPS PRIMARY DISCONNECT LOCATION AND NAME, WHERE APPLICABLE COLORED -CONDUITS AND JUNCTION BOX REQUIREMENTS: RED-COLORED -FIRE ALARM BLUE-COLORED -TEMPERATURE CONTROLS MAXIMUM AVAILABLE FAULT CURRENT: SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKING SHALL INCLUDE THE DATE. THE FAULT CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. POWER M F J LIGHTING ROUND LUMINAIRE (HALF SHADE = UNSWITCHED) -REFER TO LUMINAIRE SCHEDULE ROUND EMERGENCY DOWNLIGHT -REFER TO LUMINAIRE SCHEDULE WALL MOUNTED LUMINAIRE -REFER TO LUMINAIRE SCHEDULE TRACK LIGHTING (# OF HEADS SHOWN) -REFER TO LUMINAIRE SCHEDULE LINEAR FLUORESCENT LUMINAIRE -REFER TO LUMINAIRE SCHEDULE LINEAR FLUORESCENT EMERGENCY LUMINAIRE -REFER TO LUMINAIRE SCHEDULE EXIT SIGN -CEILING MOUNTED (SHADE = FACE, ARROW = DIRECTION), CONNECT AHEAD OF LIGHT SWITCH -REFER TO LUMINAIRE SCHEDULE EXIT SIGN -BACK MOUNTED (SHADE = FACE, ARROW = DIRECTION), CONNECT AHEAD OF LIGHT SWITCH -REFER TO LUMINAIRE SCHEDULE POLE MOUNTED LUMINAIRE (CIRCLE INDICATES POLE, BOXES INDICATE HEADS) -REFER TO LUMINAIRE SCHEDULE TOGGLE SWITCH, MOUNTED +48" O.C. UNO 2 = TWO POLE 3 = THREE WAY 4 = FOUR WAY D = DIMMER (SIZED TO MATCH LOAD SERVED) K = KEYED SWITCH M = MOMENTARY CONTACT SWITCH OC = OCC. SENSOR SWITCH DR = DOOR ACTIVATED P = SWITCH WITH PILOT LIGHT T = TIMER LV = LOW VOLTAGE CB = CIRCUIT BREAKER OCCUPANCY SENSOR -CEILING MOUNTED, DUAL TECHNOLOGY COMMUNICATIONS DUPLEX DATA RECEPTACLE, MOUNTED +18" O.C. UNO AC = MOUNTED +8" O.C. ABOVE COUNTER DUPLEX DATA RECEPTACLE, FLUSH MOUNTED IN FLOOR BOX SIMPLEX TELEPHONE RECEPTACLE, MOUNTED +18" O.C. UNO AC = MOUNTED +8" O.C. ABOVE COUNTER W = MOUNTED +54" O.C. ABOVE FINISHED FLOOR FOR WALL MOUNTING PHONE COMBINATION TEL/DATA RECEPTACLE, FLUSH MOUNTED IN FLOOR BOX -- PROVIDE (1) DATA AND (1) TELEPHONE JACK UNO CABLE TELEVISION OUTLET, COORDINATE MOUNTING HEIGHT WITH OWNER CATV OUTLET. PROVIDE BACKBOX, COAX/CAT 5 CABLE, DEVICE JACK AS DIRECTED BY OWNERS AUTHORIZED REPRESENTATIVE. REFER TO PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. OS TV SHEET LIST FIRE ALARM SYSTEM 1. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE. 2. CONTRACTOR SHALL ENSURE THAT ALL MOUNTING HEIGHTS COMPLY WITH CURRENT ADA REQUIREMENTS. 3. WHERE EVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE OR +12" ABOVE TOP OF DOOR TRIM WHERE DISTANCE TO CEILING IS GREATER THAN 24". 4. ALL ABOVE COUNTER (DESIGNATED BY "AC") SHALL BE MOUNTED 8" ABOVE COUNTER OR MAXIMUM HEIGHT OF 44" TO TOP OF DEVICE. VERIFY HEIGHTS WITH ARCHITECT. 5. FOR CEILINGS BELOW 7'-4", FIRE ALARM STROBE OR HORN/STROBES SHALL BE WALL MOUNTED 6" BELOW FINISHED CEILING. 6. IN LOCATIONS WHERE SIMILAR DEVICES ARE MOUNTED AT THE SAME HEIGHT, DEVICES SHALL BE PROPERLY "GANGED" AND SHALL HAVE A SINGLE COVERPLATE. 7. IN LOCATIONS WHERE DIFFERENT DEVICES ARE MOUNTED AT DIFFERENT HEIGHTS WITHIN FOUR FEET OF ONE ANOTHER, DEVICES SHALL BE MOUNTED SUCH THAT THEY HAVE A COMMON CENTERLINE. IF THERE ARE THREE OR MORE DEVICES, THE CONTRACTOR SHALL REQUEST A DETAIL FROM THE ARCHITECT. NOTES: FINISHED FLOOR18"RECEPTACLEDISCONNECT SWITCHTHE CENTER OF THE OPERATING HANDLE OF THE SWITCH OR CIRCUIT BREAKER CANNOT BE MORE THAN 6'-7" ABOVE THE FLOOR OR PLATFORM WHEN IT IS IN ITS HIGHEST POSITIONPANELBOARDEQUIPMENT POWER FEEDVARIESJ DEVICE MOUNTING REQUIREMENTS FINISHED FLOOREXTERIOR LIGHTDOOR 12"DOOR 12"EXIT 48"MANUAL WALL MOUNTED LIGHTING CONTROLSFINISHED FLOORDOOR CONTACTDOOR VARIESFIRE ALARM DEVICESCOORDINATED W/ ACCESS CONTROLVENDOR18"DATA OUTLETH MOUNTING REQUIREMENTS MUST BE COORDINATED WITH FIRE ALARM DESIGNER F S S S UL LISTED COMBINATION CARBON MONOXIDE/SMOKE ALARM PER IFC 908.7.4.1-PROVIDE HARDWIRED 120V POWER AND BACK-UP BATTERY POWER. WHERE MORE THAN ONE ALARM IS LOCATED IN A SINGLE DWELLING UNIT, LINK OPERATION IN ACCORDANCE WITH 101-9.6.2.9.3. PROVIDE SYSTEM DETECTORS FOR NON-DWELLING UNIT AREA PROTECTION PER LIFE SAFETY SYSTEM DESIGN BY OTHERS -REFER TO GENERAL NOTE 24 THIS SHEET. FIRE ALARM - HORN FIRE ALARM - STROBE FIRE ALARM - HORN AND STROBE FIRE ALARM CONTROL PANEL FIRE ALARM REMOTE ANNUNCIATOR PANEL REMOTE TEST STATION FACP FAA RTS studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E000 ELECTRICAL LEGEND & NOTES KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 G3/3/2023 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E101 ELECTRICAL SITE PLAN KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 G3/3/2023 'HP' EM EM X2 TYP. TYP. HP-1 HP-1 HP-1 HP-1 HP-3 LEVEL 2,3 HP-1 TYP. HP-7HP-11HP-11 HP-13 H1 LCP HP-13 TYP. HP-2,4,6 HP-1 H1 HP-5 H1 HP-5 H1 HP-7 H1 HP-7 H1 HP-7 H1 HP-7 H1 HP-11 2 5 4 3 3 4 1 EUH-1 EUH-1 HP-22,24 H1 HP-7 H1 GFI HP-11STORAGE 162 STORAGE 161 STORAGE 160 STORAGE 163 STORAGE 164 STORAGE 165 STORAGE 166 SOLAR INVERTER 169 STORAGE 170 STORAGE 168 MECHANICAL ROOM 167 H1 H1 HP-1 H1 DBP-1 HP-5 H1HP-5 H1HP-5 H1HP-5 H1 HP-5 H1 H1 HP-13 GFI GFI HP-30,32 EUH-3 EUH-1 OC OCOCOCOCOCOCOCOC OC HP-14,16 HP-18,20 HP-26,28 6 OC studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E201 ELECTRICAL LEVEL 1.1 LAYOUT KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 1/4" = 1'-0"1 ELECTRICAL FLOOR PLAN - LEVEL 1.1 XKEYED NOTES: PROVIDE LIGHTING CONTROL PANEL OR LIGHTING RELAY PANEL AND 7- DAY PROGRAMMABLE ASTRONOMICAL TIMECLOCK FOR THE CONTROL OF THE HOUSE LIGHTING FIXTURES. PROPOSED LOCATION OF HOUSE EQUIPMENT PANEL. CONNECT EXIT SIGNS AND EMERGENCY LIGHTING UNITS TO DESIGNATED CIRCUIT, AHEAD OF ALL CONTROLS. PROVIDE LIGHT FIXTURE, TYPE AS INDICATED. SEE HOUSE LIGHT FIXTURE SCHEDULE. CONTINUE TO DEVICES ON SAME CIRCUIT. ROUTE 1-1/4" SPARE CONDUIT FROM EACH OF (11) UNIT PANELS TO INVERTER ROOM AND ROUTE (11) 1-1/4" CONDUITS FROM INVERTER ROOM VERTICALLY TO ROOF FOR FUTURE TIE IN TO PV SYSTEM. PROVIDE PULL STRINGS AND CAP OPEN ENDS OF CONDUIT. REFER TO ONE-LINE AND PANEL SCHEDULES FOR ADDITIONAL INFORMATION. 1. 2. 3. 4. 5. 6. NORTH 1 2 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 G1 G2 G3 G4 G5 G6 X2 G1-1 G2-1 G3-1 G4-1 G5-1 G6-1 G1-3 G2-3 G3-3 G4-3 G5-3 G6-3 G1-5 G2-5 G3-5 G4-5 G5-5 G6-5 TYP. MDP HP-2,4,6 HP-3 HP-3 HP-3 HP-21 TYP. G1-6,8 G2-6,8 G3-6,8 G4-6,8 G5-6,8 G6-6,8 GFI WP HP-30,32 GFI WP HP-21 H7 HP-12H7HP-12 G1-2,4 G2-2,4 G3-2,4 G4-2,4 G5-2,4 G6-2,4 HP-12H1 EUH-2 EUH-2 EUH-2 EUH-2 EUH-2 EUH-2 1 4 6 5 3 3 3 3 3 3 4 4 4 4 4 H1 H1 EUH-3 2 TYP. HP-3 H7 HP-3 H7 FACP HP-15 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E202 ELECTRICAL LEVEL 1.2 LAYOUT KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 XKEYED NOTES: PROPOSED LOCATION OF BUILDING MAIN DISTRIBUTION BOARD. CONNECT EXIT SIGNS AND EMERGENCY LIGHTING UNITS TO DESIGNATED CIRCUIT, AHEAD OF ALL CONTROLS. PROPOSED LOCATON OF GARAGE PANEL. EV CHARGER READY LOCATION TO BE FIELD COORDINATED WITH ARCHITECT AND OWNER. PROVIDE 1"C (3) #8 + #10GND TO PANEL G*. PROVIDE RECEPTACLE FOR POWERED GARAGE DOOR OPENER. PROVIDE LIGHT FIXTURE, TYPE AS INDICATED. SEE HOUSE LIGHT FIXTURE SCHEDULE. 1. 2. 3. 4. 5. 6. 1/4" = 1'-0"1 ELECTRICAL FLOOR PLAN - LEVEL 1.2 NORTH 1 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 HP-3 HP-1 HP-17 1 2 3 TYP. TYP. HP-1 H1 H1 EM HP-3 EM HP-3 TYP. HP-3 H7 X2 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E203 ELECTRICAL LEVEL 2.1 LAYOUT KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 XKEYED NOTES: PROVIDE LIGHT FIXTURE, TYPE AS INDICATED. SEE HOUSE LIGHT FIXTURE SCHEDULE. CONTINUE TO DEVICES ON SAME CIRCUIT. CONNECT EXIT SIGNS AND EMERGENCY LIGHTING UNITS TO DESIGNATED CIRCUIT, AHEAD OF ALL CONTROLS. 1. 2. 3. 1/4" = 1'-0"1 ELECTRICAL FLOOR PLAN - LEVEL 2.1 NORTH 1 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 H1 1 TYP.HP-1 HP-17 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E204 ELECTRICAL LEVEL 2.2 LAYOUT KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 XKEYED NOTES: PROVIDE LIGHT FIXTURE, TYPE AS INDICATED. SEE HOUSE LIGHT FIXTURE SCHEDULE. 1. 1/4" = 1'-0"1 ELECTRICAL FLOOR PLAN - LEVEL 2.2 NORTH 1 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 A 1 3 D 4 6 F B C E 2 5 HP-3 HP-1 HP-1 1 2 TYP. TYP. 3 HP-17 H1 X1 H1EM HP-3 EM HP-3 TYP. studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E205 ELECTRICAL LEVEL 3.1 LAYOUT KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 XKEYED NOTES: PROVIDE LIGHT FIXTURE, TYPE AS INDICATED. SEE HOUSE LIGHT FIXTURE SCHEDULE. CONTINUE TO DEVICES ON SAME CIRCUIT CONNECT EXIT SIGNS AND EMERGENCY LIGHTING UNITS TO DESIGNATED CIRCUIT, AHEAD OF ALL CONTROLS 1. 2. 3. 1/4" = 1'-0"1 ELECTRICAL FLOOR PLAN - LEVEL 3.1 NORTH 1 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 HP-3 H1 1 TYP. HP-3 H1 HP-17 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E206 ELECTRICAL LEVEL 3.2 LAYOUT KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 XKEYED NOTES: PROVIDE LIGHT FIXTURE, TYPE AS INDICATED. SEE HOUSE LIGHT FIXTURE SCHEDULE. 1. 1/4" = 1'-0"1 ELECTRICAL FLOOR PLAN - LEVEL 3.2 NORTH 1 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 TV A A A A A A A A A A A A A A B B B C E 1 2 2 3 4 TYP. 5 6 7 9 10 11 TYP. 12 13 TYP. 14 15 S 16 S 17 18 20 21 21 D 19 TV 22 TYP. EWH-1 VTAC-2 EF-1 30F F A A A A A A A A A AA A A C E 1223 4TYP. 5 6 72 9 10 11 TYP. 12 13 TYP. 14 S 16 S 17 18 20 21 21 EWH-1 19 15 22TYP. TV TV VTAC-1 EF-1 23 30 F F 21 F F studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E401 ELECTRICAL UNIT PLANS KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 1/4" = 1'-0"1 ELECTRICAL UNIT PLAN - 2 BEDROOM TYPE 6 1/4" = 1'-0"2 ELECTRICAL UNIT PLAN - 1 BEDROOM TYPE 2 XKEYED NOTES: PROVIDE DEDICATED 15A 120V BRANCH CIRCUIT AND OUTLET FOR REFRIGERATOR. REFER TO DWELLING UNIT PANEL SCHEDULE FOR ADDITIONAL INFORMATION AND REQUIREMENTS. LOCATE PER EQUIPMENT MFR SPECIFICATIONS. PROVIDE ABOVE-COUNTER DUPLEX GFCI RECEPTACLES FOR SMALL APPLIANCES PER NEC 210.52(B)(3) AND 210.52(C) REQUIREMENTS. INSTALLATION SHALL COMPLY WITH NEC 210.8(A) AND 210.12(A) TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION. PROVIDE 50A 250V 4-WIRE NEMA 14-50R RECEPTACLE FOR RANGE/OVEN OR PER EQUIPMENT MFR SPECIFICATIONS AS DIRECTED BY OWNERS AUTHORIZED REPRESENTATIVE. VERIFY EXACT LOCATION AND REQUIREMENTS PRIOR TO ANY INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS AND DETAILS AND COORDINATE WITH GENERAL CONTRACTOR FOR ALL LUMINAIRES. PROVIDE ALL EQUIPMENT AS DIRECTED FOR A COMPLETE AND OPERABLE INSTALLATION. PROVIDE 30A 250V 4-WIRE NEMA 14-30R RECEPTACLE FOR DRYER UNIT OR PER EQUIPMENT MFR SPECIFICATIONS. COORDINATE WITH OWNERS EQUIPMENT VENDOR TO PROVIDE CONNECTION TO 65VA REMOTE IN-LINE FAN AND CONNECT TO DRYER AS REQUIRED. RE: MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. PROVIDE EXTERIOR OUTLETS PER NEC 210.52(E)(2) & (3) REQUIREMENTS TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION. PROVIDE BELOW-COUNTER SWITCHED RECEPTACLE FOR GARBAGE DISPOSAL. PROVIDE DEDICATED BRANCH CIRCUIT AND SPST AIR SWITCH CONTROLLER, FLUSH IN COUNTER. COORDINATE INSTALLATION AND LOCATION OF ALL DEVICES IN MILLWORK WITH GENERAL CONTRACTOR AND MILLWORK VENDOR PRIOR TO ANY INSTALLATION. PROVIDE CORD AND PLUG IF NOT PROVIDED BY PLUMBING CONTRACTOR. PROVIDE RECEPTACLE LISTED FOR USE IN COUNTERTOPS AS REQUIRED PER NEC 210.52(C)(5) ADJACENT TO SINK. PROVIDE GFCI PROTECTION AS REQUIRED. COORDINATE INSTALLATION WITH MILLWORK VENDOR AND GENERAL CONTRACTOR PRIOR TO ANY INSTALLATION. PROVIDE DEDICATED 20A GFCI BRANCH CIRCUIT FOR DISHWASHER. LOCATE OUTLET UNDER SINK AND LABEL AS DISHWASHER. COORDINATE INSTALLATION WITH PLUMBING CONTRACTOR AND LOCATION OF ALL DEVICES IN MILLWORK PRIOR TO ANY INSTALLATION. PROVIDE GFCI PROTECTION PER NEC 210.8(D). PROVIDE DEDICATED 20A GFCI BRANCH CIRCUIT TO SERVE DWELLING UNIT BATHROOMS PER NEC 210.11(C)(3), 210.8(A)(1) AND 210.52(D) REQUIREMENTS. LOCATE AT SIDEWALL ADJACENT TO MIRROR TO SUIT EACH CONDITION. DO NOT LOCATE IN MIRROR. VERIFY EXACT LOCATION WITH ARCHITECT PRIOR TO ROUGH IN AND LOCATE AS DIRECTED. PROVIDE GENERAL PURPOSE CONVENIENCE OUTLETS THROUGHOUT DWELLING UNITS PER NEC 210.52 REQUIREMENTS, TYPICAL. VERIFY EXACT LOCATION OF ALL DEVICES FOR SPECIAL EQUIPMENT SUCH AS TV'S, ETC. PRIOR TO ROUGH IN AND LOCATE AS DIRECTED. PROVIDE "MEDIA BOX" FOR LOW VOLTAGE SYSTEMS DISTRIBUTION WITHIN DWELLING UNIT. PROVIDE ADDITIONAL 120V RECEPTACLE IF REQUIRED. PROVIDE TELE/DATA CABLING THROUGHOUT DWELLING TO DEVICES AS REQUIRED. PROVIDE FAN-RATED CEILING BOX PER NEC 314.27(C). LOCATED AS DIRECTED BY OWNER'S AUTHORIZED REPRESENTATIVE. PROVIDE 3-WIRE CONNECTION FOR POSSIBLE FAN/CONTROL AS DIRECTED. PROPOSED LOCATION OF DWELLING UNIT PANEL. COORDINATE EXACT LOCATION WITH ARCHITECT AND GENERAL/MECHANICAL CONTRACTORS PRIOR TO ANY INSTALLATION TO AVOID CONFLICTS WITH OTHER SYSTEMS. FINAL LOCATION AND INSTALLATION SHALL PROVIDE ALL WORKING CLEARANCES REQUIRED PER NEC 110.26 REQUIREMENTS. DO NOT LOCATE PANEL IN CLOTHES CLOSET OR RESTROOMS. PROVIDE 120V CONNECTION TO EXHAUST FAN. COORDINATE EXACT REQUIREMENTS WITH MECHANICAL CONTRACTOR PRIOR TO ANY INSTALLATION. PROVIDE ALL EQUIPMENT FOR A COMPLETE AND OPERABLE INSTALLATION. PROVIDE SEPARATE CONTROL SW ITCH AS DIRECTED BY OWNERS AUTHORIZED REPRESENTATIVE. PROVIDE 120V CONNECTION AND INSTALL UL 217 SMOKE DETECTOR(S) PER IBC 907.2.11.2 REQUIREMENTS. INTERCONNECT MULTIPLE ALARMS AS REQUIRED PER IBC 907.2.11.5. INSTALLATION TO BE TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION (IAHJ). PROVIDE COMBINATION SMOKE/CO DETECTOR IF ACCEPTABLE TO IAHJ. PROVIDE DEDICATED 20A 120V BRANCH CIRCUIT TO COMBO MICROWAVE / RECIRC VENT, TYPICAL ALL NON-ADA UNITS. COORDINATE EXACT LOCATION AND ALL EQUIPMENT REQUIREMENTS WITH MECHANICAL CONTRACTOR PRIOR TO ANY INSTALLATION. PROVIDE ALL EQUIPMENT FOR A COMPLETE AND OPERABLE INSTALLATION. PROVIDE DEDICATED 20A 120V BRANCH CIRCUIT FOR LAUNDRY EQUIPMENT PER NEC 210.11(C)(2) AND 210.52(F) REQUIREMENTS. VERIFY EXACT LOCATION PRIOR TO ROUGH IN AND LOCATE AS DIRECTED. VERIFY EXACT LOCATION AND REQUIREMENTS WITH MECHANICAL CONTRACTOR PRIOR TO ANY INSTALLATION. REFER TO GENERAL NOTES ABOVE FOR ADDITIONAL REQUIREMENTS. REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION AND REQUIREMENTS. STUB OUT 1/2" CONDUIT ABOVE CEILING FROM ENTRY DOOR/FRAME ASSEMBLY FOR ACCESS CONTROL/DOOR STRIKE (BY OTHERS). UNDERCOUNTER LED LIGHTS, TYPE F. PROVIDE STEP DOWN TRANSFORMER AS REQUIRED. COORDINATE WITH ARCHITECT/OWNER FOR SWITCH LOCATION. REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION AND REQUIREMENTS. VERIFY TELE/DATA (CATV) DEVICE LOCATIONS WITH OWNER'S AUTHORIZED REPRESENTATIVE PRIOR TO ROUGH IN. LOCATE AND PROVIDE ALL EQUIPMENT ASDIRECTED FOR A COMPLETE AND OPERATION INSTALLATION. PROVIDE DUPLEX RECEPTACLE ADJACENT TO ALL TELE/DATA AND CATV DEVICES, TYPICAL. DO NOT INSTALL ANY LOW VOLTAGE SYSTEMS BASED ON THIS UNIT PLAN. PROVIDE 250V 30A 2PST DISCONNECT SWITCH TO EWH PER EQUIPMENT MFR NAMEPLATE AND FINAL WP FLEXIBLE CONNECTION TO MECHANICAL EQUIPMENT INDICATED. VERIFY WITH MECHANICAL OR PLUMBING CONTRACTOR EXACT LOCATION PRIOR TO ANY INSTALLATION AND LOCATE AS REQUIRED. BASIS OF DESIGN: PROGRESS P2501-09 IN BRUSHED NICKEL WITH LIGHT KIT. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. GENERAL NOTES: ELECTRICAL CONTRACTOR (EC) SHALL BE COMPLETELY RESPONSIBLE TO PROVIDE AND PROPERLY LOCATE ALL REQUIRED RECEPTACLES IN DWELLING UNITS AS REQUIRED TO COMPLY WITH NEC 210.52 REQUIREMENTS WITHOUT EXCEPTION. RECEPTACLE SPACING IN LIVING, DINING, BEDROOM, HALLWAYS, ETC. SHALL HAVE A RECEPTACLE NO GREATER THAN 6 FEET FROM ANY POINT ALONG THE WALL, FOR WALLS GREATER THAN 24 INCHES. KITCHEN RECEPTACLE SPACING AT COUNTERTOPS, ISLANDS, ETC. SHALL HAVE A RECEPTACLE NO MORE THAN 24 INCHES FROM ANY POINT ALONG WALL FOR WALLS GREATER THAN 12 INCHES. PROVIDE AFCI PROTECTION PER NEC 210.12(A). RECEPTACLES SHALL BE TAMPER- RESISTANT PER NEC 406.12(A)(1) REQUIREMENTS. GFCI PROTECTION SHALL BE PROVIDED FOR ALL DEVICES AND/OR CIRCUITS PER NEC 210.8. GFCI PROTECTION SHALL BE PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS PER 2017 NEC 210.8(D) REQUIREMENTS. CONTRACTOR SHALL PROVIDE ALL GENERAL-USE CONVENIENCE RECEPTACLES AS REQUIRED IN ALL DWELLING UNITS PER NEC 210.52 REQUIREMENTS WHETHER INDICATED ON THE DRAWINGS OR NOT. NOT EVERY REQUIRED OUTLET MAY BE SHOWN CORRECTLY LOCATED ON THE DWELLING UNIT LAYOUTS PROVIDED. CONTRACTOR SHALL INCLUDE ALL FLOOR OUTLETS AS MAY BE REQUIRED PER NEC 210.52(A)(2) WHETHER INDICATED ON THE DRAWINGS OR NOT IF REQUIRED TO MEET MINIMUM CODE REQUIREMENTS BY THE IAHJ. PROVIDE WP GFCI RECEPTACLE AT ALL DWELLING UNIT BALCONIES PER NEC 210.52(E)(3) REQUIREMENTS. DWELLING UNIT LAYOUTS ARE PROVIDED FOR GENERAL REQUIREMENTS AND INFORMATION ONLY AND ARE NOT SPECIFIC INSTALLATION DRAWINGS INDICATING EXACT LOCATION OF ALL DEVICES OR EQUIPMENT OR DETAILING EVERY INSTALLATION REQUIREMENT TO MEET ALL APPLICABLE CODES AND ADOPTED AMENDMENTS TO THE SATISFACTION OF THE IAHJ. IT SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO INCLUDE ALL LABOR AND MATERIALS IN BASE BID PROPOSAL FOR ALL ITEMS REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION TO THE SATISFACTION OF THE IAHJ. NO RFI'S OR CHANGE ORDERS WILL EVEN BE CONSIDERED, REVIEWED OR APPROVED FOR ANY REQUIRED ADDITIONAL ITEMS AS NOTED ABOVE AS MAY BE REQUIRED BY THE IAHJ DURING ROUGH AND/OR FINAL INSPECTION. IT IS EXPECTED THAT THE ELECTRICAL CONTRACTOR HAS PROVIDED THE REQUIRED FUNCTION AS A LICENSED ELECTRICAL CONTRACTOR WHILE PREPARING A CONSTRUCTION ESTIMATE AND BID PROPOSAL THAT ACCOUNTS FOR AND INCLUDES ALL SCOPE OF WORK REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION ACCEPTABLE TO THE IAHJ IN ACCORDANCE WITH NEC 210.52 REQUIREMENTS. PROVIDE AND INSTALL WP GFCI MAINTENANCE RECEPTACLES PER NEC 210.63 AT ALL GROUND MOUNTED AND/OR ROOF MOUNTED HACR EQUIPMENT WHETHER INDICATED ON THE DRAWINGS OR NOT. PROVIDE DEDICATED 20A 120V BRANCH CIRCUIT FROM NEAREST AVAILABLE HOUSE PANEL IF NO BRANCH CIRCUIT IS INDICATED ON THE DRAWINGS. PROVIDE 10AWG THWN CU CONDUCTORS FOR CIRCUITS IN EXCESS OF 75' IN LENGTH AND 8AWG THHN CU CONDUCTORS FOR CIRCUITS IN EXCESS OF 125' IN LENGTH, TYPICAL FOR ALL BUILDINGS. COORDINATE ALL INTERIOR AND EXTERIOR RECEPTACLE/LUMINAIRE INSTALLATIONS IN/ON EXTERIOR LOAD-BEARING PARTITIONS WITH GENERAL CONTRACTOR TO ENSURE THERE ARE NO CONFLICTS WITH STUD PACKS OR SHEAR WALL SYSTEMS. DO NOT MODIFY ANY STRUCTURAL ELEMENT WITHOUT PRIOR WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD. ALL BACKBOXES REQUIRED FOR DEVICES/LUMINAIRES SHALL BE RECESS MOUNTED. COORDINATE FUR-OUT OF WALL OR PROVIDE FLOOR MOUNTED RECEPTACLE AS NECESSARY FOR INTERIOR OUTLETS. FINAL INSTALLATION SHALL BE ACCEPTABLE THE IAHJ AND OAR. DO NOT SUBMIT AN RFI FOR THESE CONDITIONS OR REQUEST SPECIFIC INSTALLATION DETAILS UNLESS DESIGN DIRECTION IS ABSOLUTELY REQUIRED TO RESOLVE THE CONDITION. CONTRACTORS SHALL BE RESPONSIBLE TO FIELD COORDINATE ALL OCCURENCES AND SHALL BE RESPSONSIBLE FOR ALL INSTALLATION MEANS AND METHODS FOR A COMPLETE AND OPERABLE INSTALLATION TO SUIT THE APPLICATION. LOCATE ALL ELECTRICAL EQUIPMENT TO PROVIDE ALL REQUIRED WORKING CLEARANCES PER NEC 110.26 REQUIREMENTS TO THE SATISFACTION OF THE IAHJ. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS/CONTRACTORS FOR EXACT LOCATIONS OF ALL EQUIPMENT. VERIFY POINT OF SERVICE AND ROUTE FEEDER/BRANCH CIRCUIT WIRING AS REQUIRED TO SUIT FIELD CONDITIONS. ROUTE ALL WIRING OUT OF PUBLIC VIEW AS MUCH AS POSSIBLE. REFER TO ARCHITECTURAL OR INTERIOR DESIGNER REFLECTED CEILING PLANS (RCP) FOR EXACT LOCATION OF ALL LUMINAIRES. IF NO RCP IS PROVIDED, LOCATE ALL LUMINAIRES TO BEST ILLUMINATE THE SPACE AND CENTERED IN AVAILABLE SPACE COORDINATED WITH ALL OTHER CEILING ITEMS SUCH AS MECHANICAL EQUIPMENT OR LIFE SAFETY SYSTEM DEVICES. COORDINATE ALL LOCATIONS WITH OAR DURING BOX WALK PRIOR TO ANY WIRING INSTALLATION TO ENSURE ACCEPTABLE INSTALLATION PRIOR TO INSTALLATION OF ANY WIRING. ALL EQUIPMENT EXPOSED TO WEATHER SHALL BE NEMA 3R RATED TO SUIT THE APPLICATION. THE ELECTRICAL CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR DETERMINING AND PROVIDING ALL PROPER WIRING MEANS AND METHODS FOR ALL BUILDING TYPES, CONDITIONS/APPLICATIONS, COORDINATION OF ROUTING AND INSTALLATION OF ALL FEEDERS AND INSTALLATION OF ALL EQUPMENT PER ALL APPLICABLE CODES WITH ALL OTHER TRADES PRIOR TO ANY INSTALLATION TO THE SATISFACTION OF THE IAHJ. WHERE WIRING MEANS OR METHODS ARE INDICATED ON THESE DRAWINGS THEY ARE MINIMUM REQUIREMENTS ONLY AND THE ELECTRICAL CONTRACTOR SHALL CONFIRM ACCEPTABLE INSTALLATION METHODS AND MATERIALS WITH THE IAHJ PRIOR TO ANY INSTALLATION, TYPICAL. VERIFY ALL DEVICE TYPE, COLOR AND MATCHING COVER PLATE COLOR WITH OAR AND/OR ARCHITECT. DEVICE ORIENTATION SHALL BE VERTICAL UNLESS OTHERWISE INDICATED OR DIRECTED BY OAR/ARCHITECT. VERIFY EXACT REQUIREMENTS PRIOR TO ANY INSTALLATION AND INSTALL ALL EQUIPMENT AS DIRECTED. PROVIDE APPROVED CO DETECTOR OR APPROVED COMBINATION SMOKE/CO DETECTOR IN ALL DWELLING UNITS WHERE REQUIRED TO THE SATISFACTION OF THE IAHJ. ALL EQUIPMENT PROVIDED SHALL HAVE 120V PRIMARY POWER WITH BATTERY BACKUP PER APPLICABLE CODE REQUIREMENTS. IT IS FULLY EXPECTED AND REQUIRED THAT THE EC SHALL BE RESPONSIBLE TO THOROUGHLY COORDINATE WITH ARCHITECTURAL PLANS, INTERIOR ELEVATIONS, ALL APPLIANCE INSTALLATION MANUALS AND FINAL APPROVED MILLWORK VENDOR SHOP DRAWINGS TO VERIFY ALL REQUIREMENTS FOR ELECTRICAL CONNECTIONS AND EXACT LOCATIONS WITHIN MILLWORK PRIOR TO ANY INSTALLATION. PROVIDE ALL BACKBOXES, OULETS, SUPPORTS, ETC. AS REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION. NOTES ON DRAWINGS HAVE BEEN PROVIDED TO ALERT CONTRACTOR TO VARIOUS ITEMS/ISSUES BUT SHALL NOT BE CONSTRUED AS BEING COMPLETE IN ANY WAY. ENGINEER ASSUMES NO LIABILITY FOR OUTLET/CONNECTION TYPE/DEVICE LOCATIONS, ETC. FOR ANY DEVICE OR CONNECTION INSTALLED WITHIN DWELLING UNITS. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED COORDINATION WITH KITCHEN EQUIPMENT/APPLIANCE VENDORS AND SHOP DRAWINGS, ALL MILLWORK SHOP DRAWINGS/CONTRACTOR AND OAR TO ENSURE ALL EQUIPMENT IS PROPERLY ACCOUNTED FOR AND CORRECTLY LOCATED PRIOR TO ANY INSTALLATION TO AVOID ANY CONFLICTS DURING ACTUAL INSTALLATION. EC SHALL SCHEDULE A "BOX WALK" WITH OAR AFTER ALL OUTLET BOXES HAVE BEEN INSTALLED, BUT PRIOR TO INSTALLING ANY WIRING TO VERIFY EXACT LOCATION OF ALL DEVICES. ONCE OAR CONFIRMS APPROVAL OF ALL LOCATIONS, ROUGH WIRING MAY OCCUR. ANY ROUGH WIRING INSTALLED PRIOR TO BOX WALK AND OAR APPROVAL SHALL BE AT CONTRACTORS SOLE RISK AND SHALL BE RELOCATED OR RECONFIGURED AT CONTRACTORS SOLE EXPENSE IF INSTALLED WIRING DOES NOT MEET PROJECT REQUIREMENTS AS DETERMINED BY OAR. IT IS FULLY EXPECTED AND REQUIRED THAT THE EC SELECTED AND AWARDED THE CONTRACT FOR THIS PROJECT WILL HAVE PREVIOUSLY PERFORMED MANY PROJECTS SIMILAR TO THIS PROJECT'S SIZE AND SCOPE AND THEREFORE IS FULLY PREPARED AND ABLE TO UNDERSTAND THE REQUIRED SCOPE OF WORK AND IN FACT HAS INCLUDED ALL THE NECESSARY COORDINATION, PRE-PLANNING AND ADDITIONAL SCOPE OF WORK THAT IS REQUIRED TO SUCCESSFULLY COMPLETE A PROJECT OF THIS SIZE AND SCOPE WITHOUT UNNECESSARY RFI'S, QUESTIONS OR NEED FOR SPECIFIC ADDITIONAL DIRECTION FROM THE DESIGN TEAM ON COMPLETING THE PROJECT. PROJECT EXECUTION BY THE ELECTRICAL CONTRACTOR SHALL INCLUDE THE PROPER LAYOUT AND INSTALLATION OF ALL REQUIRED BRANCH CIRCUITING PER 2017 NEC ARTICLE 210 AS AMENDED BY THE CITY OF LONE TREE PER SEC. 18-7-40. THE OWNER EXPECTS THIS LEVEL OF EXPERIENCE AND COMPETENCE SHALL RESULT IN A PROJECT WITHOUT UNDUE RFI'S AND CHANGE ORDERS FOR "MISSING ITEMS" THAT MAY NOT BE EXPLICITLY INDICATED ON THE DRAWINGS, BUT ARE NECESSARY FOR A COMPLETE AND OPERABLE INSTALLATION. REFER TO GENERAL NOTES ABOVE FOR ADDITIONAL EXPECTATIONS AND REQUIREMENTS TO BE INCLUDED IN THE CONTRACTORS BASE SCOPE OF WORK AND SPECIFIC CONTRACT REQUIREMENTS. PER 2018 IECC R404.1; NOT LESS THAN 90% OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH-EFFICACY LAMPS. CONTRACTOR SHALL PROVIDE ALL DOCUMENTATION TO IAHJ AS MAY BE REQUIRED FOR CERTIFICATION AND APPROVAL FOR OCCUPANCY. ELECTRICAL CONTRACTOR (EC) SHALL FULLY COORDINATE WITH OWNERS LOW VOLTAGE DESIGN CONSULTANT (LVDC) TO INCLUDE ALL SCOPE ELEMENTS FOR ALL LOW VOLTAGE SYSTEMS TO AND WITHIN ALL DWELLING UNITS. EC SHALL OBTAIN FINAL APPROVED LVDC DELEGATED DESIGN DRAWINGS AND SHALL INCLUDE ALL SCOPE ITEMS AS REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION. VERIFY EXACT LOCATION AND DEVICE TYPES WITH LVDC DRAWINGS AND OAR PRIOR TO ANY INSTALLATION. LV DEVICE LOCATIONS INDICATED HEREON ARE FOR REFERENCE USE ONLY AND ARE NOT TO BE USED FOR DETERMINING INSTALLATION REQUIREMENTS OR REQUIRED SCOPE OF WORK. EC SHALL PROVIDE SEPARATE LINE ITEM PRICING AS DIRECTED BY OAR FOR ALL LOW VOLTAGE SCOPE AS PART OF BASE BID PROPOSAL FOR A COMPLETE AND OPERABLE INSTALLATION. REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION FOR EQUIPMENT INSTALLATION AND CONNECTION REQUIREMENTS. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 1 1 1 2 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 A A A A A A A A A A A A A A AA A E B B B C G A 1 TYP.S S S 3 2 2 4 5 6 7 9 10 TYP.11 12 13 TYP. 14 15 10 16 17 18 20 19 EWH-1 3 3 TV TV TV 15 21 21 D D D TYP.22 VTAC-2 EF-1 EF-13023 F F A A A A A A A A AA A AA B B B C G E 16 TYP. S 2 1 2 3 4 5 6 7 8 9 10 A TYP.11 12 13 TYP. 14 S 17 GFI 18 GFI 20 A A A LIVING/ DINING ROOM 24 KITCHEN 28 W.I.C 148 FOYER 31 M.BEDROOM 10 M.BATH 32 MECH 33 BATH 13 BEDROOM 9 A AC GFI S 19TVTV TV 19 GWH-1 15 15 21 21 A D D D 22 TYP. F F 19 VTAC-2 TV A AA 11TYP. 13 TYP. S A A A A TV 22 TYP. E 6 A A 14 20 EWH-1 305 1 3 2 2 17 21 21 A A B B B 7 9 S 16 F F 15 EF-1 10 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E402 ELECTRICAL UNIT PLANS KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 1/4" = 1'-0"1 ELECTRICAL UNIT PLAN - 2 BEDROOM TYPE 5 XKEYED NOTES: PROVIDE DEDICATED 15A 120V BRANCH CIRCUIT AND OUTLET FOR REFRIGERATOR. REFER TO DWELLING UNIT PANEL SCHEDULE FOR ADDITIONAL INFORMATION AND REQUIREMENTS. LOCATE PER EQUIPMENT MFR SPECIFICATIONS. PROVIDE ABOVE-COUNTER DUPLEX GFCI RECEPTACLES FOR SMALL APPLIANCES PER NEC 210.52(B)(3) AND 210.52(C) REQUIREMENTS. INSTALLATION SHALL COMPLY WITH NEC 210.8(A) AND 210.12(A) TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION. PROVIDE 50A 250V 4-WIRE NEMA 14-50R RECEPTACLE FOR RANGE/OVEN OR PER EQUIPMENT MFR SPECIFICATIONS AS DIRECTED BY OWNERS AUTHORIZED REPRESENTATIVE. VERIFY EXACT LOCATION AND REQUIREMENTS PRIOR TO ANY INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS AND DETAILS AND COORDINATE WITH GENERAL CONTRACTOR FOR ALL LUMINAIRES. PROVIDE ALL EQUIPMENT AS DIRECTED FOR A COMPLETE AND OPERABLE INSTALLATION. PROVIDE 30A 250V 4-WIRE NEMA 14-30R RECEPTACLE FOR DRYER UNIT OR PER EQUIPMENT MFR SPECIFICATIONS. COORDINATE WITH OWNERS EQUIPMENT VENDOR TO PROVIDE CONNECTION TO 65VA REMOTE IN-LINE FAN AND CONNECT TO DRYER AS REQUIRED. RE: MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. PROVIDE EXTERIOR OUTLETS PER NEC 210.52(E)(2) & (3) REQUIREMENTS TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION. PROVIDE BELOW-COUNTER SWITCHED RECEPTACLE FOR GARBAGE DISPOSAL. PROVIDE DEDICATED BRANCH CIRCUIT AND SPST AIR SWITCH CONTROLLER, FLUSH IN COUNTER. COORDINATE INSTALLATION AND LOCATION OF ALL DEVICES IN MILLWORK WITH GENERAL CONTRACTOR AND MILLWORK VENDOR PRIOR TO ANY INSTALLATION. PROVIDE CORD AND PLUG IF NOT PROVIDED BY PLUMBING CONTRACTOR. PROVIDE RECEPTACLE LISTED FOR USE IN COUNTERTOPS AS REQUIRED PER NEC 210.52(C)(5) ADJACENT TO SINK. PROVIDE GFCI PROTECTION AS REQUIRED. COORDINATE INSTALLATION WITH MILLWORK VENDOR AND GENERAL CONTRACTOR PRIOR TO ANY INSTALLATION. PROVIDE DEDICATED 20A GFCI BRANCH CIRCUIT FOR DISHWASHER. LOCATE OUTLET UNDER SINK AND LABEL AS DISHWASHER. COORDINATE INSTALLATION WITH PLUMBING CONTRACTOR AND LOCATION OF ALL DEVICES IN MILLWORK PRIOR TO ANY INSTALLATION. PROVIDE GFCI PROTECTION PER NEC 210.8(D). PROVIDE DEDICATED 20A GFCI BRANCH CIRCUIT TO SERVE DWELLING UNIT BATHROOMS PER NEC 210.11(C)(3), 210.8(A)(1) AND 210.52(D) REQUIREMENTS. LOCATE AT SIDEWALL ADJACENT TO MIRROR TO SUIT EACH CONDITION. DO NOT LOCATE IN MIRROR. VERIFY EXACT LOCATION WITH ARCHITECT PRIOR TO ROUGH IN AND LOCATE AS DIRECTED. PROVIDE GENERAL PURPOSE CONVENIENCE OUTLETS THROUGHOUT DWELLING UNITS PER NEC 210.52 REQUIREMENTS, TYPICAL. VERIFY EXACT LOCATION OF ALL DEVICES FOR SPECIAL EQUIPMENT SUCH AS TV'S, ETC. PRIOR TO ROUGH IN AND LOCATE AS DIRECTED. PROVIDE "MEDIA BOX" FOR LOW VOLTAGE SYSTEMS DISTRIBUTION WITHIN DWELLING UNIT. PROVIDE ADDITIONAL 120V RECEPTACLE IF REQUIRED. PROVIDE TELE/DATA CABLING THROUGHOUT DWELLING TO DEVICES AS REQUIRED. PROVIDE FAN-RATED CEILING BOX PER NEC 314.27(C). LOCATED AS DIRECTED BY OWNER'S AUTHORIZED REPRESENTATIVE. PROVIDE 3-WIRE CONNECTION FOR POSSIBLE FAN/CONTROL AS DIRECTED. PROPOSED LOCATION OF DWELLING UNIT PANEL. COORDINATE EXACT LOCATION WITH ARCHITECT AND GENERAL/MECHANICAL CONTRACTORS PRIOR TO ANY INSTALLATION TO AVOID CONFLICTS WITH OTHER SYSTEMS. FINAL LOCATION AND INSTALLATION SHALL PROVIDE ALL WORKING CLEARANCES REQUIRED PER NEC 110.26 REQUIREMENTS. DO NOT LOCATE PANEL IN CLOTHES CLOSET OR RESTROOMS. PROVIDE 120V CONNECTION TO EXHAUST FAN. COORDINATE EXACT REQUIREMENTS WITH MECHANICAL CONTRACTOR PRIOR TO ANY INSTALLATION. PROVIDE ALL EQUIPMENT FOR A COMPLETE AND OPERABLE INSTALLATION. PROVIDE SEPARATE CONTROL SWITCH AS DIRECTED BY OWNERS AUTHORIZED REPRESENTATIVE. PROVIDE 120V CONNECTION AND INSTALL UL 217 SMOKE DETECTOR(S) PER IBC 907.2.11.2 REQUIREMENTS. INTERCONNECT MULTIPLE ALARMS AS REQUIRED PER IBC 907.2.11.5. INSTALLATION TO BE TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION (IAHJ). PROVIDE COMBINATION SMOKE/CO DETECTOR IF ACCEPTABLE TO IAHJ. PROVIDE DEDICATED 20A 120V BRANCH CIRCUIT TO COMBO MICROWAVE / RECIRC VENT, TYPICAL ALL NON-ADA UNITS. COORDINATE EXACT LOCATION AND ALL EQUIPMENT REQUIREMENTS WITH MECHANICAL CONTRACTOR PRIOR TO ANY INSTALLATION. PROVIDE ALL EQUIPMENT FOR A COMPLETE AND OPERABLE INSTALLATION. PROVIDE DEDICATED 20A 120V BRANCH CIRCUIT FOR LAUNDRY EQUIPMENT PER NEC 210.11(C)(2) AND 210.52(F) REQUIREMENTS. VERIFY EXACT LOCATION PRIOR TO ROUGH IN AND LOCATE AS DIRECTED. VERIFY EXACT LOCATION AND REQUIREMENTS WITH MECHANICAL CONTRACTOR PRIOR TO ANY INSTALLATION. REFER TO GENERAL NOTES ABOVE FOR ADDITIONAL REQUIREMENTS. REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION AND REQUIREMENTS. STUB OUT 1/2" CONDUIT ABOVE CEILING FROM ENTRY DOOR/FRAME ASSEMBLY FOR ACCESS CONTROL/DOOR STRIKE (BY OTHERS). UNDERCOUNTER LED LIGHTS, TYPE F. PROVIDE STEP DOWN TRANSFORMER AS REQUIRED. COORDINATE WITH ARCHITECT/OWNER FOR SWITCH LOCATION. REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION AND REQUIREMENTS. VERIFY TELE/DATA (CATV) DEVICE LOCATIONS WITH OWNER'S AUTHORIZED REPRESENTATIVE PRIOR TO ROUGH IN. LOCATE AND PROVIDE ALL EQUIPMENT ASDIRECTED FOR A COMPLETE AND OPERATION INSTALLATION. PROVIDE DUPLEX RECEPTACLE ADJACENT TO ALL TELE/DATA AND CATV DEVICES, TYPICAL. DO NOT INSTALL ANY LOW VOLTAGE SYSTEMS BASED ON THIS UNIT PLAN. PROVIDE 250V 30A 2PST DISCONNECT SWITCH TO EWH PER EQUIPMENT MFR NAMEPLATE AND FINAL WP FLEXIBLE CONNECTION TO MECHANICAL EQUIPMENT INDICATED. VERIFY WITH MECHANICAL OR PLUMBING CONTRACTOR EXACT LOCATION PRIOR TO ANY INSTALLATION AND LOCATE AS REQUIRED. BASIS OF DESIGN: PROGRESS P2501-09 IN BRUSHED NICKEL WITH LIGHT KIT. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. GENERAL NOTES: REFER TO GENERAL NOTES ON SHEET E401.1. 1/4" = 1'-0"2 ELECTRICAL UNIT PLAN - 2 BEDROOM TYPE 4 1 1 1 1/4" = 1'-0"3 ELECTRICAL UNIT PLAN - 1 BEDROOM TYPE 1 2 2 2 1 ABCO COMMENTS 02/02/2023 2 VE CHANGES 03/03/23G3/3/2023 ONE-LINE DIAGRAM GENERAL NOTES: 1. ALL SERVICE EQUIPMENT SHALL BE INSTALLED PER NEC REQUIREMENTS AND UTILITY PROVIDER'S SERVICE STANDARDS. 2. ALL DISTRIBUTION EQUIPMENT AND OVERCURRENT DEVICES INDICATED SHALL BE NEW AND IDENTIFIED AS A UL LISTED SERIES TESTED COMBINATION WITH UPSTREAM FUSE PER NEC 240.86(B) WHERE REQUIRED FOR SCCR RATING INDICATED. PROVIDE ALL EQUIPMENT LABELING PER NEC 110.22(C). PROVIDE SUBMITTAL DATA FOR REVIEW AND APPROVAL BY ARCHITECT/ENGINEER PRIOR TO ORDERING OR PURCHASING ANY EQUIPMENT. 3. UTILITY SERVICE EQUIPMENT SHALL BE SHALL BE GROUNDED AND BONDED IN ACCORDANCE WITH NEC 250.80 AND 250.84 REQUIREMENTS. 4. ALL SERVICE EQUIPMENT SHALL BE GROUNDED AND BONDED IN ACCORDANCE WITH NEC 250.24 AND 250.92 REQUIREMENTS. 5. CONTRACTOR'S SERVICE EQUIPMENT VENDOR SHALL PROVIDE ALL REQUIRED ARC FLASH SYSTEM ANALYSIS, DOCUMENTATION AND EQUIPMENT LABELING PER NEC 110.16, 110.21, 110.22 AND 240.87 REQUIREMENTS TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION. 6. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL NEW ELECTRICAL SERVICE INSTALLATION REQUIREMENTS WITH UTILITY AUTHORIZED SERVICE REPRESENTATIVE. COORDINATE EXACT LOCATION OF ALL SITE UTILITIES AND EQUIPMENT WITH FINAL APPROVED UTILITY SERVICE PLAN. PROVIDE INSTALLATION OF ALL RACEWAY SYSTEMS AND EQUIPMENT AS REQUIRED FOR NEW SERVICE TO BUILDING PER UTILITY SERVICE STANDARDS AND FINAL APPROVED SERVICE PLAN. 7. ALL SITEWORK AND UNDERGROUND CONDUIT SHALL BE PER UTILITY PROVIDER'S GUIDE FOR CUSTOMER INSTALLED UNDERGROUND CONDUITS AND VAULTS PRIMARY INSTALLATION AND LATEST ELECTRIC SERVICE CONSTRUCTION STANDARDS (ESCS). VERIFY EXACT REQUIREMENTS PRIOR TO BID. 8. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH SERVING UTILITIES FOR ALL LOW VOLTAGE SYSTEM SERVICES TO THE BUILDING INCLUDING, BUT NOT LIMITED TO, TELEPHONE, CATV, SECURITY SYSTEMS, ETC. PROVIDE ALL RACEWAYS AND STRUCTURES AS REQUIRED BY SERVING UTILITY COMPANIES FOR RESPECTIVE SYSTEMS IN BASE BID PROPOSAL. 9. CONTRACTOR SHALL SUBMIT FOR REVIEW AND APPROVAL EQUIPMENT SHOP DRAWINGS FOR ALL SERVICE ENTRANCE EQUIPMENT, DISTRIBUTION EQUIPMENT, PANELBOARDS, OR OTHER RELATED EQUIPMENT. 10. ALL ELECTRICAL SERVICE AND DISTRIBUTION EQUIPMENT EXPOSED TO WEATHER SHALL BE NEMA 3R RATED WEATHERPROOF. 11. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING APPLICABLE WIRING MEANS AND METHODS TO SUIT SPECIFIC FIELD CONDITIONS TO SUIT THE INTENDED APPLICATION. PROVIDE ALL RACEWAYS AND EQUIPMENT PER APPLICABLE CODE REQUIREMENTS. WHERE RACEWAY TYPES ARE INDICATED HEREON, THEY ARE FOR REFERENCE USE ONLY AND DO NOT NECESSARILY INDICATE THE SPECIFIC RACEWAY TYPE REQUIRED FOR THE SPECIFIC APPLICATION IN ALL AREAS. 12. PROVIDE SUPPORT FOR ALL CONDUCTORS IN VERTICAL RACEWAYS AS REQUIRED PER NEC 300.19 TO THE SATISFACTION OF THE INSPECTING AUTHORITY HAVING JURISDICTION. DETAIL NOTES: COORDINATE WITH OWNERS AUTHORIZED REPRESENTATIVE AND OBTAIN SERVING UTILITY COMPANY (HOLY CROSS ELECTRIC) TO PROVIDE ELECTRONIC SUBMETERING AS PART OF BASE BID PROPOSAL FOR ALL DWELLING UNITS. INCLUDE ALL EQUIPMENT AND INSTALLATION REQUIRED FOR A COMPLETE AND OPERABLE ELECTRONIC SUBMETERING SOLUTION. SYSTEM TO BE CAPABLE OF METERING AND ASSOCIATING MULTIPLE FEEDERS AND BRANCH CIRCUITS TO A SINGLE UNIT. PROVIDE CIRCUIT BREAKER AND BRANCH CIRCUIT SHOWN TO REMOTE ELECTRONIC SUBMETERING EQUIPMENT. COORDINATE WITH OWNERS ELECTRONIC SUBMETERING VENDOR EXACT EQUIREMENTS AND EQUIPMENT LOCATIONS PRIOR TO ANY INSTALLATION. REFER TO GENERAL NOTE 25 ON E0.00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS, TYPICAL. PROVIDE 18AWG UL1015, 600V 221F/105C, TWISTED PAIR BLACK AND WHITE CONDUCTORS FOR CT WIRING FROM CT'S AT "MDP" TO REMOTE MMU. COORDINATE WITH OWNERS ELECTRONIC SUBMETERING VENDOR EXACT REQUIREMENTS AND EQUIPMENT LOCATIONS PRIOR TO ANY INSTALLATION. PROVIDE RACEWAY SYSTEM(S) AS REQUIRED TO SUIT THE SPECIFIC INSTALLATION REQUIREMENTS PER EQUIPMENT MFR SPECIFICATIONS AS DIRECTED BY OWNERS ELECTRONIC SUBMETERING VENDOR. PROVIDE ARC-ENERGY REDUCTION PER NEC 240.87 REQUIREMENTS. ROUTE SPARE 1-1/4" CONDUIT FROM EACH TENANT PANEL TO INVERTER ROOM ON THE 1ST FLOOR. ROUTE A 1-1/4" CONDUIT FOR EACH UNIT FROM INVERTER ROOM TO ROOF AND STUB OUT 1' ABOVE ROOF LEVEL. PROVIDE PULL STRINGS AND CAP OFF ENDS FOR EACH CONDUIT. THESE CONDUITS ARE FOR FUTURE USE WITH ROOF MOUNTED PV SYSTEMS. (ASSUMED) 300kVA 208/120V/3Φ TRANSFORMER BY HOLY CROSS ELECTRIC 2 LEVEL 1 1600/3 200/3 60/3 225/2 "MDP", 1600A, 208/120V, 3Φ, 4W, NEMA 3R, 65kAIC 4 3 4 HOUSE PANEL "HP" MCB WATER PIPE UFER GROUND ROD UTILITY METER N G LEVEL 2 LEVEL 3 ESM TENANT PANEL (x3) MLO X 1. 2. 3. 4. 5. 4 "MMU"1 2 3 60/2 3 GARAGE PANEL (x6) MLO 3 8[(4-1000kcmil) 3-1/2"C] 6[(4-400kcmil) 3-1/2"C] (4#4;#8GND) 1-1/4"C (4-250kcmil;#4GND) 3"C 1 FEEDER SCHEDULE 2 3 4 NOTE: ALL CONDUCTORS SHOWN ARE ALUMINUM UNLESS OTHERWISE NOTED. SECONDARY CONNECTION CABINET 4000A 1 #6 Cu GEC #4 Cu GEC#3/0 Cu GEC 225/2 4 TENANT PANEL (x4) MLO 3 X X - Isc=56,202 Isc=41,534 - X Isc=21,519 - X X - Isc=6,031 X - Isc=18,793 (WORST CASE)(WORST CASE) 225/2 4 TENANT PANEL (x4) MLO 3 TO BLDG F UM1-3 XFMR VAULT ROOF INVERTER ROOM 5 X - Isc=57,400 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E602 ELECTRICAL ONE-LINE DIAGRAM KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 1 BUILDING G - ELECTRICAL ONE-LINE DIAGRAM ALL CALCULATIONS BASED ON BUSSMAN POINT-TO-POINT METHOD FOR 3 PHASE CIRCUITS. ** FOR INFINITE BUS USE 100,000,000 * MULTIPLY THE TOTAL MOTOR LOAD CURRENT BY 4 1. Transformer short circuit rating based on information received from Holy Cross Metering Guidebook, Table II. Unit Panel (Worst Case) 45 Al 250 kcmil 1 2 208 12862 41534 18793 Garage Panel (Worst Case) 40 Al #4 1 2 208 2350 41534 6031 PANEL 'HP' 50 Al 250 kcmil 1 2 208 18593 41534 21519 SWBD 'MDP' 110 Al 400 kcmil 6 2 208 145776 56202 41534 TERMINATION CABINET 10 Al 600 kcmil 8 2 208 224264 57400 56202 LOCATION FT. Cu SIZE PH. NON=2 L-L " C " Isc Isc FAULT LEN. Al/ NO./ MAG=1 VOLT. CIRCUIT BEGINNI... FAULT CKT COND... COND... CKT FEEDERS 500kVA XFMR secondary 500 12470 208 1.41 1388 100000... 33400 0 57400 LOCATION KVA L-L L-L %Z FLA Isc** Isc CONTRIB. Isc FAULT TRANS. VOLT. VOLT. XFMR SEC. PRI. SEC. *MOTOR CONTRIB. PRI. SEC. XFMR. XFMR. TOTAL TRANSFORMERS LOCATION:Eagle Vail DATE:3/3/2023 PROJECT:Haymeadow PROJ. NO.:21234 SHORT CIRCUIT CALCULATIONS 2 2 2 2 VE CHANGES 03/03/23G3/3/2023 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E604 ELECTRICAL SCHEDULES KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 LUMINAIRE SCHEDULE GENERAL NOTES 1 LUMINAIRES INDICATED ABOVE WERE USED AS A BASIS OF DESIGN; ALTERNATE MANUFACTURERS WILL BE CONSIDERED WITH ARCHITECT'S AND OWNER'S APPROVAL. 2 CATALOG NUMBERS INDICATE BASIC LUMINAIRE TYPES REQUIRED FOR THIS PROJECT. CONTRACTOR SHALL BE RESPONSIBLE TO INCLUDE ALL ACCESSORIES AND HARDWARE REQUIRED FOR FINAL INSTALLATION. 3 ELECTRICAL CONTRACTORS SHALL BE RESPONSIBLE FOR VERIFYING LUMINAIRE LOCATIONS AND MOUNTING REQUIREMENTS PRIOR TO PURCHASE. INCLUDE ALL MOUNTING HARDWARE AS REQUIRED FOR A COMPLETE INSTALLATION. 4 FINAL FINISH OF ALL FIXTURES SHALL BE APPROVED IN WRITING BY ARCHITECT. 5 MOUNTING HEIGHTS SHALL BE COORDINATED WITH ARCHITECT'S ELEVATIONS. 6 THE FIXTURE SCHEDULE DOES NOT NECESSARILY LIST ALL ACCESSORIES AND HARDWARE NECESSARY FOR THE COMPLETE INSTALLATION, NOR DOES IT DETAIL THE CEILING CONSTRUCTION TO BE ENCOUNTERED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROPERLY DETERMINE AND PROVIDE CORR 7 FIXTURES AND TRACKS SHALL BE MOUNTED TO / FROM STRUCTURE IN A MANNER RECOMMENDED BY THE MANUFACTURER WITHOUT COMPROMISING THE INTEGRITY OF THE STRUCTURE. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MATERIALS REQUIRED TO INSURE A SAFE AND PROPER INSTALLATION. 8 REMOTE TRANSFORMERS, POWER SUPPLIES, OR DRIVERS SHALL BE LOCATED IN NEARBY ACCESSIBLE, CONCEALED-FROM-VIEW LOCATION WITH MANUFACTURER'S RECOMMENDED VENTILATION. CONTRACTOR SHALL SUPPLY MANUFACTURER'S TRANSFORMERS, POWER SUPPLIES, OR DRIVERS OF PROPER CAPACITY FOR A COMPLETE INSTALLATION. LIGHTING FOR EXTERIOR APPLICATIONS SHALL COMPLY WITH IECC C405.2.5 AND MEET ALL OF THE FOLLOWING REQUIREMENTS: 1. LIGHTING SHALL BE CONTROLLED BY A DEVICE THAT AUTOMATICALLY TURNS OFF THE LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE. 2. ALL BUILDING FACADE AND LANDSCAPE LIGHTING SHALL BE AUTOMATICALLY CONTROLLED AS A FUNCTION OF DUSK/DAWN AND A SET BUSINESS OPENING AND CLOSING TIME, OR BETWEEN TIMES ESTABLISHED BY THE AUTHORITY HAVING JURISDICTION. 3. LIGHTING NOT SPECIFIED IN 2. SHALL BE CONTROLLED BY A DEVICE THAT AUTOMATICALLY REDUCES THE CONNECTED LIGHTING POWER BY AT LEAST 30% FOR AT LEAST ONE OF THE FOLLOWING CONDITIONS: A. FROM 12 MIDNIGHT OR WITHIN ONE (1) HOUR OF THE END OF BUSINESS OPERATIONS, WHICHEVER IS LATER, UNTIL 6A.M. OR BUSINESS OPENING, WHICHEVER IS EARLIER. B. DURING ANY PERIOD WHEN NO ACTIVITY HAS BEEN DETECTED FOR A TIME OF NO LONGER THAN 15 MINUTES. ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST TEN HOURS. EXCEPTIONS: 1. LIGHTING FOR COVERED VEHICLE ENTRANCES OR EXITS FROM BUILDINGS OR PARKING STRUCTURES WHERE REQUIRED FOR SAFETY, SECURITY, OR EYE ADAPTATION 2. LIGHTING THAT IS INTEGRAL TO SIGNAGE AND INSTALLED IN THE SIGNAGE BY THE MANUFACTURER EXTERIOR LIGHTINGINTERIOR LIGHTING LIGHTING FOR INTERIOR APPLICATIONS SHALL COMPLY WITH IECC C405.2 AND MEET ALL OF THE FOLLOWING REQUIREMENTS: 1. OFFICES 2. AUTOMATIC CONTROLS IN CORRIDORS SHALL HAVE THE FOLLOWING: A. CONTROLLED TO AUTOMATICALLY TO TURN THE LIGHT 'ON' TO 50 PERCENT POWER UPON DIGITAL TIMECLOCK SETPOINT, 1- HOUR BEFORE BUSINESS HOURS a. OCCUPANT TO MANUALLY TURN 'ON' THE REMAINDER OF THE LIGHTING b. OCCUPANT MANUAL CONTROLS TO BE FULLY CONTINUOUSLY DIMMABLE B. LIGHT FIXTURES SHALL AUTOMATICALLY TURN 'OFF' 1-HOUR AFTER END OF BUSINESS HOURS a. OCCUPANT TO MANUALLY TURN 'OFF' LIGHT FIXTURES 3. AUTOMATIC CONTROLS IN JANITOR CLOSETS, BATHROOMS, AND STORAGE ROOMS SHALL HAVE THE FOLLOWING: A. AUTOMATICALLY TURN 'ON' THE LIGHT FIXTURES WHEN OCCUPANTS ENTER THE SPACE B. MANUAL 'ON' OVERRIDE AT ENTRANCE DOOR C. LIGHT FIXTURES SHALL AUTOMATICALLY TURN 'OFF' WITHIN 20-MINUTES OF ALL OCCUPANTS LEAVING THE SPACE 4. AUTOMATIC CONTROLS IN THE OPEN AREA WAREHOUSE SHALL HAVE THE FOLLOWING: A. AUTOMATICALLY TURN 'ON' TO 50 PERCENT POWER WHEN OCCUPANTS ENTER THE SPACE B. MANUAL 'ON' CONTROL AT EACH ENTRANCE DOOR C. LIGHT FIXTURES SHALL AUTOMATICALLY TURN 'OFF' WITHIN 30-MINUTES OF ALL OCCUPANTS LEAVING THE SPACE 5. MECHANICAL, ELECTRICAL, AND WATER ENTRY ROOMS A. AUTOMATIC CONTROLS NOT REQUIRED FOR OCCUPANT SAFETY. OCCUPANT TO MANUALLY TURN 'ON' AND MANUALLY TURN 'OFF' THE LIGHT FIXTURES • LIGHTING CONTROLS SHALL BE PROVIDED BY LUTRON, LEVITON, GREENGATE, WATTSTOPPER, OR EQUIVALENT MANUFACTURER AS APPROVED BY OWNER AND ENGINEER. PROVIDE MANUFACTURER'S SHOP DRAWINGS TO ARCHITECT FOR REVIEW PRIOR TO PURCHASING. • CONTROL SWITCHES, SENSORS, ETC. SHALL BE LOW-VOLTAGE OR WIRELESS WHENEVER PRACTICAL. INCLUDE ALL ACCESSORIES, RELAY PACKS, CAT-# CABLING, ETC. AS REQUIRED FOR A COMPLETE INSTALLATION. • MANUAL DIMMING CONTROLS SHALL BE CAPABLE OF DIMMING LIGHTS TO 0% (OFF) SETTING. DIMMING COMPATIBILITIES BETWEEN THE LUMINAIRES AND CONTROLS TO BE COORDINATED BY THE CONTRACTOR TO ENSURE PROPER OPERATION. LUMINAIRES MUST BE ABLE TO DIM TO THE LEVEL INDICATED ON THE LUMINAIRE SCHEDULE. • REMOTE LIGHTING CONTROL DEVICES (TIMECLOCKS, ETC.) SHALL BE CENTRALLY LOCATED IN ELECTRICAL ROOM, UNLESS INDICATED OTHERWISE ON PLANS. COORDINATE AND CONFIRM WITH OWNER PRIOR TO ROUGH-IN. • ALL SWITCHES AND SENSORS SHALL BE LABELED TO IDENTIFY THE AREA CONTROLLED. • ELECTRICAL CONTRACTOR SHALL LOCATE SENSORS AS PROVIDED BY MANUFACTURER PER APPROVED SHOP DRAWINGS. CONTROL LOCATIONS INDICATED ON THE DRAWINGS ARE FOR REFERENCE PURPOSES ONLY AND WILL BE ALTERED AS NECESSARY FOR CORRECT OPERATION BY MANUFACTURER. • PROJECT TO HAVE FUNCTIONAL PERFORMANCE TESTING OF ALL LIGHTING SYSTEMS AND PROVIDE OWNER WITH REPORT OF DOCUMENTED PERFORMANCE WITHIN 90 DAYS OF RECEIPT OF CERTIFICATE OF OCCUPANCY. TESTING SHALL INCLUDE SYSTEM COMMISSIONING AS REQUIRED BY IECC C408. • DAYLIGHT RESPONSIVE CONTROLS SHALL BE PROVIDED WHERE REQUIRED PER IECC C405.2.3 REQUIREMENTS. LIGHTS AND SENSORS IN THESE AREAS MUST BE INDEPENDENTLY CONTROLLED AND BE CAPABLE OF DIMMING FROM 10%-100%. • PROGRAMMING, FACTORY START-UP AND TRAINING TO END-USER STAFF SHALL BE BY LIGHTING CONTROLS MANUFACTURER OR AUTHERIZED REPRESENTATIVE. CONTRACTOR SHALL INCLUDE AT LEAST ONE FOLLOW-UP VISITS WITH LIGHITNG CONTROL REPRESENTATIVE FOR FOLLOW-UP TRAINING OR ANY ADDITIONAL PROGRAMMING WITH OWNER IN BASE BID PROPOSAL. • COMPLETE LIGHTING CONTROLS SYSTEM SHALL BE AS SIMPLIFIED AS ALLOWED BY IECC C405.2. STAND-ALONE AND SINGLE ROOM CONTROLS IS PREFERED OVER CENTRAL CONTROL PANELS. DESIGN ALTERNATES AS ALLOWED BY CODE TO SIMPLIFY THE DESIGN SHALL BE CONSIDERED AND REVIEWED BY THE ENGINEER WHERE PROPOSED BY CONTROLS MANUFACTURER OR CONTRACTOR. GENERAL REQUIREMENTS LIGHTING CONTROLS REQUIREMENTS LUMINAIRE SCHEDULE - ALTERNATE LIGHT FIXTURES AND CONTROLS 1 THE CONTRACTOR SHALL BE REQUIRED TO PAY FOR ANY INCURRED HOURS REQUIRED TO UPDATE THE PERMIT OR CONSTRUCTION DOCUMENTS DUE TO ALTERNATE FIXTURES OR CONTROLS BY THE ENGINEER OF RECORD. 2 THE CONTRACTOR SHALL BE REQUIRED TO PAY FOR ANY INCURRED HOURS REQUIRED FOR THE ENGINEER OF RECORD TO REVIEW ALTERNATE LIGHT FIXTURES OR CONTROLS. 3 UPDATES SHALL BE BILLED AT AN HOURLY RATE OF $150/HR OR AS PREVIOUSLY AGREED TO RATES IN THE CONTRACT DOCUMENTS. LUMINAIRE SCHEDULE NOTES: ALL LUMINAIRES, LAMPS/DRIVERS, ACCESSORIES SHALL BE PROVIDED BY CONTRACTOR AS PART OF BASE BID SCOPE. HC620D010-HM60525-830 G 6" LED SHOWER LIGHT HALO RECESSED 120V 21 3000K 80 2228 - WET LISTED LED-T24P-1-1-WTFUNDERCOUNTER LED STRIP... WAC LIGHTING SURFACE 120V 3 3000K - - - PROVIDE REQUIRED STEP-DOWN TRANSFORMER\POWER... HS71003-125EEXTERIOR WALL SCONCE HOMESTYLE LIGHTING WALL 120V 14 3000K - 1440 - WET LISTED, INSTALL 14W A19 LED LAMP P2708-09 D BATHROOM VANITY LIGHT PROGRESS LIGHTING WALL 120V 42 3000K - 4320 - INSTALL (3) 14W A19 LED LAMPS P500149-143 C DINING RM LED PENDANT PROGRESS LIGHTING PENDANT 120V 14 3000K - 1440 - INSTALL 14W A19 LED LAMP PD-26611-SN B 4" ROUND LED PENDANT WAC LIGHTING PENDANT 120V 15 3000K 90 858 ELV, 10% HC620D010-HM60525-830 A 6" LED DOWNLIGHT HALO RECESSED 120V 21 3000K 80 2228 - CATALOG NUMBER TYPE DESCRIPTION MANUFACTURER & MOUNTING VOLTAGE WATTAGE CCT CRI LUMENS DIMMING REMARKS UNIT LUMINAIRE SCHEDULE LUMINAIRE SCHEDULE NOTES: ALL LUMINAIRES, LAMPS/DRIVERS, ACCESSORIES SHALL BE PROVIDED BY CONTRACTOR AS PART OF BASE BID SCOPE. 90-MINUTE BACKUP BATT. SQ-LED-W-SD EM EMERGENCY LIGHT MULE WALL 120-277V - - - - - 90-MINUTE BACKUP BATT. HCXUGW03L SPECIFIC INSTALLATION REQUIREMENTS, TYPICAL FOR ALL... X2 EXIT SIGN & EM LIGHT COMBO DUAL LITE UNIVERSAL 120-277V - - - - - PROVIDE ALL MOUNTING HARDWARE/ACCESSORIES AS... EVE U G W E I SPECIFIC INSTALLATION REQUIREMENTS, TYPICAL FOR ALL... X1 EXIT SIGN DUAL LITE UNIVERSAL 120-277V - - - - - PROVIDE ALL MOUNTING HARDWARE/ACCESSORIES AS... HS71003-125 H7 WALL SCONCE HOMESTYLE LIGHTING WALL 120V 14 3000K - - - WET LISTED, INSTALL 14W A19 LED LAMP FVS8 M 4 2 LO OS1 H5 4' LINEAR SURFACE LED FAIL-SAFE WALL 120-277V 45.5 3000K 80+ 5675 - FVS4W M 2 1 LO 30 P187 WALL H4 2' LINEAR SURFACE LED FAIL-SAFE SURFACE 120-277V 12.3 3000K 80+ 1230 - FVS4 M 2 1 LO 30 P187 CEILING H3 2' LINEAR SURFACE LED FAIL-SAFE SURFACE 120-277V 12.3 3000K 80+ 1230 - FSV8 M 2 LD4 2 STD 30 P187 CEILING H2 2' LINEAR SURFACE LED FAIL-SAFE SURFACE 120-277V 33.5 3000K 80+ 3718 - SLD606 8 30 WH H1 6" LED DOWNLIGHT HALO RECESSED 120-277V 12.2 3000K 80 760 0-10V, 5% CATALOG NUMBER TYPE DESCRIPTION MANUFACTURER & MOUNTING VOLTAGE WATTAGE CCT CRI LUMENS DIMMING REMARKS HOUSE LUMINAIRE SCHEDULE G3/3/2023 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E605 ELECTRICAL LOAD CALCULATIONS KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 ***Unit Panel Rating 225A at 120/208V, 1Ø, 3W*** Minimum Service Ampacity at 120/208V, 1Ø, 3W:207 *-Table 220.42 (First 3000VA @ 100%, remainder @ 35%) Net Calculated Load:42958 Sub-Total: 34819 (1) VTAC Unit 13977 13977 25% Largest Motor 174 (1) Domestic Circ. Pump 168 168 (1) Electric Water Heater @ 125% 6000 7500 (1) Clothes Dryer (Table 220.54) 5000 5000 (1) Electric Oven/Cooktop (Table 220.55) 8000 8000 Equipment Sub-Total: 3498 (1) Refrigerator 950 712.5 (1) Microwave 1650 1237.5 (1) Dishwasher 1200 900 (1) Garbage Disposal 864 648 Fixed Appliances (220.53) Demand*: 4641 Sub-Total: 7689 (1) Laundry Circuits, 1500W (220.52(B))1500 (2) Small Appliance Circuits, 1500W (220.52(A)) 3000 1063 Sq. Ft. @ 3VA 3189 General Lighting Load @ 3VA/Sq. Ft. 220.14 (J)NEC 220.42 Basic* New Single Family Dwelling - 2BR-Largest Unit Main Panel Description of Load 2020 NEC 220 RESIDENTIAL ELECTRICAL LOAD CALCULATION Haymeadow - 2BR-Type1 Unit (Largest) ***Main Distribution Panel Rating 1600A at 120/208V, 3Ø, 4W*** Minimum Service Ampacity at 120/208V, 3Ø, 4W:1259 * First 3kW @ 100%, remainder up to 120kW @ 35%, above 120kW @ 25% - Table 220.42 Net Calculated Load: 453673 House Loads 36000 Sub-Total: 74460 (6) Misc. Garage Loads 226 1356 (6) Garage Door Openers 864 5184 (6) Electric Unit Heaters 3000 18000 (6) EV Charging Stations @ 125% 8320 49920 Garage Panels Sub-Total: 274757 (9) VTAC-2 Units 13977 125793 (2) VTAC-1 Units 10046 20092 25% Largest Motor 174 (11) Domestic Circ. Pump 168 1848 (8) Electric Water Heater EWH-2 6000 60000 (3) Electric Water Heater EWH-1 4000 15000 (11) Electric Clothes Dryer (Table 220.54) 5000 25850 (11) Electric Range/Oven (Table 220.55) 8000 26000 Equipment Sub-Total: 38478 (11) Refrigerator 950 7838 (11) Microwave 1650 13612.5 (11) Dishwasher 1200 9900 (11) Garbage Disposal 864 7128 Fixed Appliances (220.53) Demand*: 29978 Sub-Total: 80079 (11) Laundry Circuits, 1500W (220.52(B))16500 (22) Small Appliance Circuits, 1500W (220.52(A))33000 10193 Sq. Ft. @ 3VA 30579 General Lighting Load @ 3VA/Sq. Ft. NEC 220.14 (J)NEC 220.42 Basic* Total Unit SF: 10193 (4) 2BR-Type4 Unit 906 SF 3624 (4) 2BR-Type5 Unit 1063 SF 4252 (1) 2BR-Type6 Unit 1063 SF 1063 (1) 1BR-Type2 Unit 580 SF 580 (1) 1BR-Type1 Unit 674 SF 674 Unit SF Breakdown Area, SF Building (11 Units) Description of Load 2020 NEC 220 RESIDENTIAL ELECTRICAL LOAD CALCULATION Haymeadow - 11 Unit Building Ampacity at 120/208V, 3Ø, 4W:2473 * First 3kW @ 100%, remainder up to 120kW @ 35%, above 120kW @ 25% - Table 220.42 Net Calculated Load (VA): 890751 (2) House Panel 36000 72000 House Loads Sub-Total: 148920 (12) Misc. Garage Loads 226 2712 (12) Electric Unit Heaters 3000 36000 (12) Garage Door Openers 864 10368 (12) EV Charging Stations @ 125% 6656 99840 Garage Panels Sub-Total: 538885 (18) VTAC-2 Units 13977 251586 (4) VTAC-1 Units 10046 40184 25% Largest Motor 1819 (22) Domestic Circ Pump 168 3696 (22) Electric Water Heater 6000 165000 (22) Electric Clothes Dryer (Table 220.54) 5000 39600 (22) Electric Range/Oven (Table 220.55) 8000 37000 Equipment Sub-Total: 76956 (22) Refrigerator 950 15675 (22) Microwave 1650 27225 (22) Dishwasher 1200 19800 (22) Garbage Disposal 864 14256 Fixed Appliances (220.53) Demand*: 53990 Sub-Total: 160158 (22) Laundry Circuits, 1500W (220.52(B))33000 (44) Small Appliance Circuits, 1500W (220.52(A))66000 20386 Sq. Ft. @ 3VA 61158 General Lighting Load @ 3VA/Sq. Ft. NEC 220.14 (J)NEC 220.42 Basic* Total Unit SF: 20386 (8) 2BR-Type6 Unit 906 SF 7248 (8) 2BR-Type5 Unit 1063 SF 8504 (2) 2BR-Type6 Unit 1063 SF 2126 (2) 1BR-Type2 Unit 580 SF 1160 (2) 1BR-Type1 Unit 674 SF 1348 Unit SF Breakdown Area,... Electrical Load for Electrical Service (Bldgs A, B) Description of Load 2020 NEC 220 RESIDENTIAL ELECTRICAL LOAD CALCULATION Haymeadow - Electrical Service (Bldgs A, B) Ampacity at 120/208V, 3Ø, 4W:2473 * First 3kW @ 100%, remainder up to 120kW @ 35%, above 120kW @ 25% - Table 220.42 Net Calculated Load (VA): 890751 (2) House Panel 36000 72000 House Loads Sub-Total: 148920 (12) Misc. Garage Loads 226 2712 (12) Electric Unit Heaters 3000 36000 (12) Garage Door Openers 864 10368 (12) EV Charging Stations @ 125% 6656 99840 Garage Panels Sub-Total: 538885 (18) VTAC-2 Units 13977 251586 (4) VTAC-1 Units 10046 40184 25% Largest Motor 1819 (22) Domestic Circ Pump 168 3696 (22) Electric Water Heater 6000 165000 (22) Electric Clothes Dryer (Table 220.54) 5000 39600 (22) Electric Range/Oven (Table 220.55) 8000 37000 Equipment Sub-Total: 76956 (22) Refrigerator 950 15675 (22) Microwave 1650 27225 (22) Dishwasher 1200 19800 (22) Garbage Disposal 864 14256 Fixed Appliances (220.53) Demand*: 53990 Sub-Total: 160158 (22) Laundry Circuits, 1500W (220.52(B))33000 (44) Small Appliance Circuits, 1500W (220.52(A))66000 20386 Sq. Ft. @ 3VA 61158 General Lighting Load @ 3VA/Sq. Ft. NEC 220.14 (J)NEC 220.42 Basic* Total Unit SF: 20386 (8) 2BR-Type6 Unit 906 SF 7248 (8) 2BR-Type5 Unit 1063 SF 8504 (2) 2BR-Type6 Unit 1063 SF 2126 (2) 1BR-Type2 Unit 580 SF 1160 (2) 1BR-Type1 Unit 674 SF 1348 Unit SF Breakdown Area,... Electrical Load for Electrical Service (Bldgs F, G) Description of Load 2020 NEC 220 RESIDENTIAL ELECTRICAL LOAD CALCULATION Haymeadow - Electrical Service (Bldgs F, G) 2 2 VE CHANGES 03/03/23G3/3/2023 studio DRAWN BY: CHECKED BY: DATE: REVISION: COPYRIGHT 2023 This document is an instrument of service, and as such remains the property of the Architect. Permission for use of this document is limited and can be extended only by written agreement with EVstudio, LLC. Denver, CO Evergreen, CO 303.670.7242 inspections@evstudio.com design@evstudio.com www.evstudio.com Contact: E606 ELECTRICAL PANEL SCHEDULES KH CT 21234 PERMIT SET 11/16/2022HAYMEADOW CONDOSBUILDING A91 MT. HOPE CIRCLEEAGLE, COLORADOShane Donalson shane.donalson@evstudio.com 303.670.7242 PANEL:TYPICAL GARAGE PANEL G* ISSUE DATE:11.14.2022 FEEDER DEMAND AMPS 50.7 BY:CT FEEDER DEMAND KVA 12.2 2. CONTROL WIRING FOR HVAC EQUIPMENT BY MECHANICAL CONTRACTOR - NIC CONN.KVA (CODE 4)0.0 TIMECLOCK OFF OPERATION.CONN.KVA (CODE 3)0.2 1. ROUTE EXTERIOR LIGHTS THROUGH PHOTOCELL/TIMECLOCK FOR PHOTOCELL ON/CONN.KVA (CODE 2)3.6 NOTES:CONN.KVA (CODE 1)6.7 TOTAL 5474 5008 CONNECTED KVA 10.5 19 20 1 SPARE ///////// 0 SPARE 1 20 20 17 20 1 SPARE 0 ///////// SPARE 1 20 18 15 20 1 SPARE ///////// 0 SPARE 1 20 16 13 20 1 SPARE 0 ///////// SPARE 1 20 14 11 20 1 SPARE ///////// 0 SPARE 1 20 12 9 20 1 SPARE 0 ///////// SPARE 1 20 10 7 20 1 SPARE ///////// 1500 1500 --- --- --- 2 8 5 2 20 1 DOOR OPENER 600 2100 ///////// 1500 EUH-2 2 20 2 6 3 3 20 1 RECEPTS 180 ///////// 3508 3328 --- --- --- 1 4 1 1 20 1 LIGHTING 46 3374 ///////// 3328 EV CHARGING STATION 2 40 1 2 NO. CODE TRIP POLE DESCRIPTION MISC REC LITE VA A B VA LITE REC MISC DESCRIPTION POLE TRIP CODE NO. CKT CB LOAD DESIGNATION LOAD PHASES LOAD LOAD DESIGNATION CB CKT AIC RATING:10,000 MAINS:MLO 4=(KITCHEN EQUIPMENT NEC 220.56) PANEL:TYPICAL GARAGE PANEL G*BUS (AMPS):100 3=(RECEPTACLES NEC 220.44) JOB:Haymeadow PHASE & WIRE:1PH 3W 2=(NON-CONTINUOUS LOAD NEC 220.14) DATE:11/15/2022 PANEL VOLTAGE:120/240 CKT CODE: 1=(CONTINUOUS LOAD NEC 210.19(A) MIN 20A CKTS 1.33 MIN 15A CKTS 1.77 AMPACITY: 26.58 LOAD @3VA/SF: 3189 UNIT SF: 1063 (Largest Unit, Worst-case Typical) Minimum Number Branch Circuits Required PANEL:Typical Dwelling Unit (2BR) ISSUE DATE:3.3.23 FEEDER DEMAND AMPS See Dwelling Unit Load Calculations BY:CT FEEDER DEMAND KVA BASED ON SQUARE D HOMELINE LOADCENTER 3-TIER SERIES RATED SYSTEM - LABEL PER NEC 240.86B PROVIDE ALL CIRCUIT BREAKERS AS APPROVED BY THE AHJ. ** - PROVIDE 20A2P BREAKER FOR UNITS WITH EWH-1 (4000W), 2BR TYPE 6 * - PROVIDE GFCI DEVICES IN KITCHEN PER NEC 210.8(A)(6 AND NEC 406.11 REQUIREMENTS responsible to perform all work in accordance with 2020 NEC requirements. GFCI - GROUND-FAULT CIRCUIT INTERRUPTER PER NEC 210.8(A)(1). (MAY BE LOCAL GFCI DEVICES)with 2020 NEC 210 and NEC 210.52 requirements. Contractor shall be AFCI - ARC-FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKER PER 2017 NEC 210.12(B)Note: All branch circuiting and devices installed shall be in compliance NOTES:>>ALL DEVICES INSTALLED SHALL COMPLY WITH 2017 NEC 406.11 REQUIREMENTS<<See Dwelling Unit Load Calculations TOTAL 22035 23396 CONNECTED KVA 45.4 29 AFCI 15 1 SPARE 0 ///////// SPARE 1 15 AFCI 30 27 AFCI 15 1 SPARE ///////// 3000 3000 --- --- --- 28 25 AFCI 15 1 SPARE 3000 ///////// 3000 EWH-2 2 30 **26 23 --- --- (FUTURE)///////// 4503 4503 --- --- --- AFCI 24 21 100 2 PV SYSTEM CONNECTION 4503 ///////// 4503 1 VTAC UNIT (HEATER CKT) 2 45 AFCI 22 19 AFCI 15 1 SPARE ///////// 2486 2486 --- --- --- 20 17 AFCI 15 1 SPARE 2486 ///////// 2486 1 VTAC UNIT 2 35 18 15 15 1 DCP-1 168 ///////// 4168 4000 PROVIDE 4-WIRE CONNECTION --- ---16 13 AFCI 15 1 REFRIGERATOR 1 696 4696 ///////// 4000 1 ELEC RANGE OVEN 2 50 14 11 AFCI 20 1 MICROWAVE 1 1800 ///////// 4300 2500 PROVIDE 4-WIRE CONNECTION --- --- 12 9 *20 1 SMALL APPLIANCE 2 1500 4000 ///////// 2500 1 CLOTHES DRYER 2 30 10 7 *20 1 SMALL APPLIANCE 2 1500 ///////// 3000 1500 1 LAUNDRY CIRCUIT 1 20 GFCI 8 5 AFCI 15 1 GENERAL LIGHTING 1075 2275 ///////// 1200 1 DISHWASHER 1 20 GFCI 6 3 AFCI 15 1 GENERAL LIGHTING 1075 ///////// 1939 864 1 GARBAGE DISPOSAL 1 20 GFCI 4 1 AFCI 15 1 GENERAL LIGHTING 1075 1075 ///////// 1 BATHROOM CIRCUIT 1 20 GFCI 2 NO. CODE TRIP POLE DESCRIPTION MISC REC LITE VA A B VA LITE REC MISC DESCRIPTION POLE TRIP CODE NO. CKT CB LOAD DESIGNATION LOAD PHASES LOAD LOAD DESIGNATION CB CKT AIC RATING:22,000 MAINS:MLO ** - COMPLY WITH NEC 210.7(B) REQUIREMENTS PANEL:Typical Dwelling Unit (2BR)BUS (AMPS):125 * - GFCI DEVICES PER 210.8(B)(6) & NEC 406.11 JOB:Haymeadow PHASE & WIRE:1PH 3W GFCI= SEE NOTES BELOW DATE:3/3/2023 PANEL...120/208 CKT CODE: AFCI= SEE NOTES BELOW REMAINDER IN EXCESS OF 10KVA+ALLOWABLE DEMAND FOR COMMERCIAL COOKING EQUIPMENT (IF APPLICABLE) PER NEC 220.56 REQUIREMENTS. * - FEEDER DEMAND KVA INDICATED IS THE SUM OF CONN.KVA (CODE 1)X125%+100% OF CONN.KVA (CODE 2)+100% OF FIRST 10KVA OF GENERAL-USE RECEPTACLES PER NEC 220.44 AND 50% OF PANEL:HP ISSUE DATE:6.13.22 FEEDER DEMAND AMPS 88.0 BY:CT FEEDER DEMAND KVA*31.7 CONN.KVA (CODE 4)0.0 NEC 220.56 CONN.KVA (CODE 3)2.2 NEC 220.44 CONN.KVA (CODE 2)19.8 100 NOTES:98.7 85.1 49.6 CONN.KVA (CODE 1 )7.8 125 TOTAL 11849 10216 5953 CONNECTED KVA 28.0 DEMAND %/NEC REF. 41 20 1 SPARE ///////// ///////// 0 SPARE 1 20 42 39 20 1 SPARE ///////// 0 ///////// SPARE 1 20 40 37 20 1 SPARE 0 ///////// ///////// SPARE 1 20 38 35 20 1 SPARE ///////// ///////// 0 SPARE 1 20 36 33 20 1 SPARE ///////// 0 ///////// SPARE 1 20 34 31 1 --- --- ---375 1875 ///////// ///////// 1500 --- --- --- 2 32 29 1 20 2 LTG - SITE 375 ///////// ///////// 1875 1500 EUH-3 - LVL 1 STAIRWELL 2 20 2 30 27 1 --- --- ---3328 ///////// 4828 ///////// 1500 --- --- --- 2 28 25 1 40 2 EV Charging Station 3328 4828 ///////// /////////1500 EUH-3 - LVL 1 CORRIDOR 2 20 2 26 23 20 1 SPARE ///////// ///////// 1000 1000 --- --- --- 2 24 21 3 20 1 Recepts - Exterior 360 ///////// 1360 ///////// 1000 EUH-1 - ROOM 160 2 20 2 22 19 20 1 SPARE 1000 ///////// ///////// 1000 --- --- --- 2 20 17 3 20 1 Rcpts - Lev 2,3 corr 720 ///////// ///////// 1000 EUH-1 - ROOM 169 2 20 2 18 15 2 20 1 Fire Alarm Circuit 500 ///////// 1500 ///////// 1000 --- --- --- 2 16 13 3 20 1 Rcpts - Lev 1 W corr,stor,mech 540 1540 ///////// ///////// 1000 EUH-1 - ROOM 167 2 20 2 14 11 3 20 1 Rcpts - Lev 1 E corr,stor,mech 540 ///////// ///////// 568 28 LTG - EXTERIOR, BLDG MNTD 1 20 1 12 9 20 1 SPARE ///////// 0 ///////// SPARE 1 20 10 7 1 20 1 Lights-Utility-Storage Level 1 E. 72 72 ////////////////// SPARE 1 20 8 5 1 20 1 Lights-Utility-Storage Level 1 W. 84 ///////// ///////// 2510 2426 -- -- -- 2 6 3 1 20 1 Lights- Level 1,2,3 stairs 102 ///////// 2528 ///////// 2426 -- -- -- 2 4 1 1 20 1 Lights- Level 1,2,3 corridor 108 2534 ///////// ///////// 2426 DBP-1 - ROOM 167 3 30 2 2 NO. CODE TRIP POLE DESCRIPTION MISC REC LITE VA A B C VA LITE REC MISC DESCRIPTION POLE TRIP CODE NO. CKT CB LOAD DESIGNATION LOAD PHASES LOAD LOAD DESIGNATION CB CKT AIC RATING:42,000 MAINS:200/3 4=(KITCHEN EQUIPMENT NEC 220.56) PANEL:HP BUS (AMPS):200 3=(RECEPTACLES NEC 220.44) JOB:Haymeadow PHASE AND WIRE:3PH,4W 2=(NON-CONTINUOUS LOAD NEC 220.14) DATE:3/3/2023 PANEL VOLTAGE:208/120V CKT CODE: 1=(CONTINUOUS LOAD NEC 210.19(A) NOTE: CONDUCTORS SHOWN ARE COPPER UNLESS NOTED OTHERWISE. DBP-1 BOOSTER PUMP 30A3P 20.2 7,277 208 3 30A3P W/30A FUSES (3#10;#10GND) 3/4"C DCP-1 DOMESTIC RECIRC. PUMP 15A1P 1.4 168 120 1 MOTOR RATED SWITCH (2#12;#12GND) 3/4"C EUH-2 & 3 ELECTRIC UNIT HEATER 20A2P 14.4 3,000 208 1 - (3#12;#12GND) 3/4"C DISCONNECT IS INCLUDED WITH UNIT EUH-1 ELECTRIC UNIT HEATER 20A2P 9.6 2,000 208 1 - (3#12;#12GND) 3/4"C DISCONNECT IS INCLUDED WITH UNIT VTAC-2 CKT 2 VERTICAL TERMINAL HEAT PUMP (HEATING CKT) 45A2P 43.3 9,006 208 1 60A2P FUSED DISC. (3#6;#10GND) 3/4"C FUSE PER MANUFACTURER REQUIREMENTS. VTAC-2 CKT 1 VERTICAL TERMINAL HEAT PUMP 35A2P 23.9 4,971 208 1 60A2P FUSED DISC. (3#8;#10GND) 3/4"C FUSE PER MANUFACTURER REQUIREMENTS. VTAC-1 VERTICAL TERMINAL HEAT PUMP 50A2P 48.3 10,046 208 1 60A2P FUSED DISC. (3#6;#10GND) 3/4"C FUSE PER MANUFACTURER REQUIREMENTS. EF-1 EXHAUST FAN 20A1P 0.1 8 120 1 MOTOR RATED SWITCH (2#12;#12GND) 3/4"C KEY ITEM CB AMPS WATTS VOLT PH. DISCONNECT FEEDER NOTES EQUIPMENT SCHEDULE MIN 20A CKTS 0.84 MIN 15A CKTS 1.12 AMPACITY: 16.85 LOAD @3VA/SF: 2022 UNIT SF: 674 (Largest Unit, Worst-case Typical) Minimum Number Branch Circuits Required PANEL:Typical Dwelling Unit (1BR) ISSUE DATE:3.3.23 FEEDER DEMAND AMPS See Dwelling Unit Load Calculations BY:CT FEEDER DEMAND KVA BASED ON SQUARE D HOMELINE LOADCENTER 3-TIER SERIES RATED SYSTEM - LABEL PER NEC 240.86B PROVIDE ALL CIRCUIT BREAKERS AS APPROVED BY THE AHJ. * - PROVIDE GFCI DEVICES IN KITCHEN PER NEC 210.8(A)(6 AND NEC 406.11 REQUIREMENTS responsible to perform all work in accordance with 2020 NEC requirements. GFCI - GROUND-FAULT CIRCUIT INTERRUPTER PER NEC 210.8(A)(1). (MAY BE LOCAL GFCI DEVICES)with 2020 NEC 210 and NEC 210.52 requirements. Contractor shall be AFCI - ARC-FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKER PER 2017 NEC 210.12(B)Note: All branch circuiting and devices installed shall be in compliance NOTES:>>ALL DEVICES INSTALLED SHALL COMPLY WITH 2017 NEC 406.11 REQUIREMENTS<<See Dwelling Unit Load Calculations TOTAL 21871 24083 CONNECTED KVA 46.0 29 AFCI 15 1 SPARE 0 ///////// SPARE 1 15 AFCI 30 27 AFCI 15 1 SPARE ///////// 2000 2000 --- --- --- 28 25 AFCI 15 1 SPARE 2000 ///////// 2000 EWH-1 2 20 26 23 --- --- (FUTURE)///////// 4503 4503 SPARE --- --- AFCI 24 21 100 2 PV SYSTEM CONNECTION 4503 ///////// 4503 1 SPARE 2 45 AFCI 22 19 AFCI 15 1 SPARE ///////// 5023 5023 --- --- --- 20 17 AFCI 15 1 SPARE 5023 ///////// 5023 1 VTAC UNIT 2 50 18 15 15 1 DCP-1 168 ///////// 4168 4000 PROVIDE 4-WIRE CONNECTION --- ---16 13 AFCI 15 1 REFRIGERATOR 1 696 4696 ///////// 4000 1 ELEC RANGE OVEN 2 50 14 11 AFCI 20 1 MICROWAVE 1 1800 ///////// 4300 2500 PROVIDE 4-WIRE CONNECTION --- --- 12 9 *20 1 SMALL APPLIANCE 2 1500 4000 ///////// 2500 1 CLOTHES DRYER 2 30 10 7 *20 1 SMALL APPLIANCE 2 1500 ///////// 3000 1500 1 LAUNDRY CIRCUIT 1 20 GFCI 8 5 AFCI 15 1 GENERAL LIGHTING 225 1425 ///////// 1200 1 DISHWASHER 1 20 GFCI 6 3 AFCI 15 1 GENERAL LIGHTING 225 ///////// 1089 864 1 GARBAGE DISPOSAL 1 20 GFCI 4 1 AFCI 15 1 GENERAL LIGHTING 225 225 ///////// 1 BATHROOM CIRCUIT 1 20 GFCI 2 NO. CODE TRIP POLE DESCRIPTION MISC REC LITE VA A B VA LITE REC MISC DESCRIPTION POLE TRIP CODE NO. CKT CB LOAD DESIGNATION LOAD PHASES LOAD LOAD DESIGNATION CB CKT AIC RATING:22,000 MAINS:MLO ** - COMPLY WITH NEC 210.7(B) REQUIREMENTS PANEL:Typical Dwelling Unit (1BR)BUS (AMPS):125 * - GFCI DEVICES PER 210.8(B)(6) & NEC 406.11 JOB:Haymeadow PHASE & WIRE:1PH 3W GFCI= SEE NOTES BELOW DATE:3/3/2023 PANEL...120/208 CKT CODE: AFCI= SEE NOTES BELOW 2 2 VE CHANGES 03/03/23G3/3/2023