HomeMy WebLinkAbout601 Kings Row Ave - 239121401001 - 0612ISEAGLE COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH
PLJASE-tALL•FOR FINAL
P. U. Box 850 - 550 Broadway
PERMIT MUST BE POSTED
INSPECTION BEFORE COVERTf4G'
Eagle, Colorado
81631
AT INSTALLATION SITE
ANY PORTION OF INSTAL-LEO SYSTEM
328-7311 or Y49-5257 or 927-3823
PERMIT NO.
N
612
OWNER: Mitchell L. Sydoryk
ADDRESS:
P.O. Box
871 - Aspen, CO 81612
SYSTEM LOCATION: Kings Row
Avenue - Missouri Heights
(west
of Red Table Acres)
LICENSED INSTALLER: Joe Zamora
LICENSE NUMBER:
**CONDITIONAL INSTALLATION APPROVAL is hereby granted for the following:
MINIMUM REQUIREMENTS: 1,250 gallon septic tank or aerated treatment unit.
Absorption area or dispersal area computed as follows:
PERCOLATION RATE: one inch in 40 minutes.
Absorption Area per Bedroom * sq. ft. -*per engineer design
No. of Bedrooms 2 x sq. ft. minimum requirement per bedroom
total sq. ft. minimum requirement.
SPECIAL REQUIREMENTS:
DATE: May 3, 1983 INSPECTOR: Erik Edeen-
**CONDITIONS:
1. All installation must comply with all requirements of the County Individual Sewage
Disposal System Regulations, adopted pursuant to authority granted in 25-10-104,
C.R.S. 1973, as amended.
2. This permit is valid only for connection to structures which have fully complied
with County zoning and building requirements. Connection to or use with any
dwelling or structure not approved by the building and zoning departments shall
automatically be a violation of a requirement of the permit and cause for both
legal action and revocation of the permit.
3. Section III, 3.21 requires any person who constructs, alters, or installs an
individual sewage disposal system to be licensed according to the Regulations.
FINAL APPROVAL OF SYSTEM: No system shall be deemed to be in compliance with the Eagle
County Individual Sewage Disposal System Regulations until the installed system is
approved prior to covering any part.
Installed Absorption or Dispersal Area: sq. ft.
Installed Septic Tank: te'Z 1(2 gallons. Degrees: OF 3©6 Feet:
Design Engineer of System: A,j,9,, tK'
Installer of System: -\Dq- '2:C VV\oN Phone:
Septic tank cleanout to within 12" of final grade or
aerated access ports above grade? Yes Y No
Proper materials and assembly? Yes X No
Compliance
with
permit requirements? Yes_
No
Compliance
with
County/State regulations
requirements?
Yes. No
COMMENTS:
-r - - -/
� I `v v...d
1Vt
PE„. IT 1 EE = $150
BOX Ego
EAGLE , COLORACO 81 C 31
FE=-CL."TI TEST FEE = SRO
APPLICATION FOR iNDIV IDUr"L SE:-:I'.GE DISPOSAL SYSTE?-1 PER:'.'.IT
-NAME OF OI NER: M i+c1d L L. Sj,)iat2-,4j<_ d- kn+ALEErj M. Lite!,
ADDRIESS: P'Q•1-3ox Q"7/ P45PF-- C- : gl�Pl�--- PHONE:
NA MI: OF APPLICANT (IF DIFFERENT FROM 01-INER): ��—
ADf,RESS: PHONE:
DESIGN ENGINEER OF SYSTEM (IF APPLICABLE):
ADDRESS: PHONE:
-PERSON RESPONSIBLE FOR INSTALLATION OF SYSTEI1.:
ADDRESS: /1'KX 7S ��t� � ' �I�P�-� PHONE:
PERMIT APPLICATI0'1 IS FOR: (✓) "leer Installation ( ) Alteration ( ) Repair
LOCATION OF PROPOSED FACILITY: County E qo L Lot Size
City or Town, if within City or To;•rn Limits
LEGAL DESCRIPTION: Z.21/,QG; A10, - �i,��5 K�G� Su�LY✓i51a�1A���
STREET (RURAL) ADDRESS: )KjAj65©r�S✓✓�'✓.tsZ. i.
IS SYSTEM DESIGNED FOR LESS THAN 2,000 GALLONS PER DAY? ( ) Yes ( ) No
BUILDING SERVICE TYPE: (Check applicable category)
(Residential - Single-family dwelling ( ) Residential - Triplex
( ) Residential - Duplex ( ) Residential - Quadplex
1 rnmmerc al - State usage
Persons �—. % Bedrooms
-
WASTE TYPES: (Check all applicable)
( ) Commercial or Institutional (v .) Dwelling ( Garbage Grinder
-( ) Non -domestic wastes ( ) Transient Use (`� ish�rasher
°( ) Other (Automatic Masher
SOURCE AND TYPE OF 14ATER SUPPLY: Wel1 ( ) Spring ( ) Creek or Stream
Give depth of all wells within 200 feet of the system: lV
If supplied.,by community water, give name of supplier: i 42 Iip�f� )
_f
;TYPE OF 7Septic
IDUAL SEWAGE •DISPOSAL SYSTEM PROPOSED:
( Tank. ( ) Aeration Plant ( ) Chemical Toilet
i .Y alal 1. Pf lYy .i ) t,. ��ir. .��1•���� iUi i:. 1. *=•.f�_1 �iltif vLaV.t_' i.•Ji= -
( ) Pit Privy ( ) Incineration Toilet ( ) Recycling, Other Use
( ) Greywater ( ) Other
WILL EFFLUEIT BE DISCHARGED DIRECTLY INTO WATERS OF THE STATE? ( ) Yes (%_,,�'No
'`.Signature QJ� Cate
*
INFORMATION BELO!-/ TO BE FILLED OUT BY ENVIRnNME�lTAL HEALTH OFFICER
GROUND CONDITIONS: Percent nround Slope:
Depth to Bedrock (per 8' Profile Hole):
SOIL PERCOLATION TEST RESULTS:
FINAL DISPOSAL BY: ( )
Depth to Groun-'-Ovrater Table:
Minutes per inch in Hole No. 1
Minutes per inch in Hole No. 2
!1i nutes per inch in Hole No. 3
Absorption Trench, Bed or Pit ( ) Evanotransoiration
Above Ground Dispersal; ( ) Sand Filter
Underground Dispersal' ( ) ,!aste'.ihter Pond
O t"e r
i 1
ROUTE FORM
EAGLE COUNTY ENVIRONMENTAL HEALTH OFFICE
Name
-U3 g3 8�
Date Routed >
Application No.
Location
Please review the attached Individual Sewage Disposal System Permit Application and return
it with this completed form to the Environmental Health Office.
PLANNING: Complies with - . YES - NO REVIEWED BY DATE
Subdivision Regulations:
Zoning`Regulations:
Recommend Approval:
-
COMMENTS:
BUILDING.: Complies with -
Building Permit Applied For:
Building Permit Issued:
Recommend Approval:
YES
NO
REVIEWED BY
DATE
COMMENTS:
ENGINEER: with -
Roa s.�
Grading:
Drainage:
Recommend Annroval:
YES
NO
REVIEWED BY
DATE
- --_
_
- `—
COMMENTS:
ENVIRONMENTAL HEALTH:
Complies with -
Floodplain Permit Necessary:
I.S.D.S. Regs. Compliance:
Recommend Approval:
YES
NO
REVIEWED BY
DATE
1�
COMMENTS:
E
LOAN INSPECTION FORM
LOCATION:
REQUESTOR:-
5
TO:
DILL to
� * �'c � 9c 9c � 9c 4c 3c 4c � 9c 9c it •�c 4e ' 9t �e 9c �'t •3c it it 9c � * it 9c * � * * * �
ISDS rERMIT #
INSPECTION INFpORMATION:
/so
INSPECTION DONE BY: � Z5
SlCL 47crf
DATE:
To: First Colorado Mortgage
P.O. Box 1378
Aspen, CO 81612
Attn : Bonnie in account with
EAGLE COUNTY DEPARTMENT OF COMMUNITY DEVELOPMENT
P. 0. BOX 179
EAGLE, COLORADO 81631
DATE
AMOUNT
08/20/86 Loan Inspection Fee for property located at 25.00
0601 Kings Row / Lot 10, Kings Row Subdivision
TOTAL AMOUNT DUE 25.00
Guideline Technical Specifications
Scope of Work: These technical specification guidelines are directed
towards construction of individual sewage disposal systems. All
building sewer installations as designed shall meet the 1972 revised
Colorado Technical plumbing code. The disposal system can be located
to suit individual dwelling locations and shall meet the requirements
of the county regulations.
Septic Tank
General: The septic tank shall have a minimum of two.(2) compartments
with two (2) twenty (20) inch diameter access holes or manholes, one
each located in inlet and outlet chambers. The size and shape may
vary, however minimum dimensions and capacities shown in the drawing
and as specified by county regulations shall be met. The invert of
the inlet shall be at least three (3) inches above the invert of the
outlet. A baffle or tee shall be provided to divert the influent
downward and shall penetrate at least six (6) inches below the liquid
level and at a level not below that allowed for the outlet device. The
outlet shall have a baffle or tee extending to a minimum of fourteen
(14) inches below the invert of the outlet invert and one (1) inch
below the tank cover. The outlet shall be distinctly marked on the
exterior of the tank. No septic tank shall be located within the
horizontal distances from the various facilities listed below and
on the drawing.
50 feet from springs, wells or suction lines
10 feet from potable water supply line, dwelling, property lines,
dry gulches
50 feet from cistern, lakes, water course or stream
-2-
Material/Construction: The septic tank shall be constructed of water
tight material. Precast reinforced concrete septic tanks are acceptable
by the county. However, metal or coated metal tanks are not acceptable.
Cement for a concrete tank shall be Portland Type II, sulfate resistant.
The tank shall be reinforced with welded wire mesh of not less than 10
gauge with 6" x 6" spacing or heavier. The walls and floor of the tank
shall be a minimum of four (4) inches thick. The top cover of the
tank shall also be four (4) inches thick minimum and reinforced in
the same manner, and including #4 rebar eight (8) inches from each side
and thirty (30) inches crossways from each end as well as on inside
of the access holes.
Installation: The tank shall be installed on a solid base and must
be level. The finished grade shall be within twelve (12) inches from
the manholes. Roof drains, surface and subsurface drains or cistern
overflows can not be diverted into the tank or around any part of the
disposal system. The discharge line from the building sewer to the
septic tank shall be laid to a grade as shown in the drawing.: Sewer
pipe connections to and from the septic tank shall be of cast iron
and bends shall be limited to 450 ells or longsweep quarterbends. The
inlet and outlet shall be grouted and sealed with waterproof material.
Backfilling around a septic tank must be conducted in a manner to
prevent any settlement and avoid undue strain on the tank and the pipes
entering and leaving the tank.
-3-
Distribution Box
General: The distribution box is installed to collect liquid effluent
from the septic tank and to distribute it evenly into the next phase
of the disposal systems. The distribution box shall have one (1)
inlet and seven (7) outlets. All outlet inverts shall be at the same
level and at least one (1) inch below the invert of the inlet and
three (3) inches to six (6) inches above the floor of the box.
Material: A precast, reinforced, concrete box will be acceptable.
Cement for the concrete shall be Type II Portland, sulfate resistant.
Reinforcement shall be 10 gauge 6" x 6" welded wire mesh or heavier.
Concrete shall achieve a 28 day strength of 3000 psi.
Installation: The distribution box shall be installed on solid ground
and must be level. Backfill around the box shall be carried out in a
manner to prevent box misalignment and eliminate any voids. Granular
backfilling under the box is recommended.
Evapo-transpiration (E.T.) Bed With or Without Subsurface Sand Filters
General: The effluent from a septic tank is collected into a distri-
bution box and discharged into an E.T. bed through four (4) inch diameter
perforated PVC lines or into the subsurface sand filter and finally
carried into an E.T. bed as shown in the drawing. In case of a disposal
system through subsurface sand filtration, an additional distribution
box is required. Construction of the evapo-transpiration system shall
be performed as per the drawings and specifications herein. Evapo-
transpiration and.subsurface sand filter beds shall not be located
within the distances from various facilities as listed below and on
the drawings.
-4-
rAOTT .T'PV
DISTANCE IN FEET FROM:
E.T. BED SAND FILTER BED
Springs, wells or suction lines
75
75
Potable water supply line
10
25
Cistern
15
15
Dwelling or occupied building
15
15
Property line
10
10
Subsoil drains
10
10
Lakes, watercourse, stream
25
75
Dry gulches
15
15
Evapo-transpiration beds: The effluent from a septic tank shall be
carried into -the distiibution box through four (4) inch cast iron pipe.
In order to achieve an excavation and fill balance, the bed may b'e laid
perpendicular to general slope of the ground. Twelve (12) inches of
washed gravel, 3/4" to 2 1/2", shall be placed in the excavation and
distribution lines shall be laid to a slope as shown in the drawing.
All pipes must be covered with gravel to a depth of at least four (4)
inches. The remainder of the excavation shall be filled with fine
grained soils and capped with top soil. The finished grade shall be
crowned to eliminate infiltration of surface runoff into the bed. Four
(4) inch PVC air vent pipes shall be placed vertically and must extend
six (6) inches above finished grade. Each vent will be capped, with
air vent holes in the surface extension. The subsurface sand filter
bed, where applicable, shall be uniform, coarse, clean and shall have
the following gradation:
SIEVE SIZE
PERCENT PASSING
#4 100
#10 30 - 80
#20 0 - 5
#60 0
y 1.
ME
Gravel for the sand filter bed shall pass through a 2 1/2" sieve and
retained on a 3/4" sieve. Prior to laying distribution lines, the
sand shall be thoroughly flooded and settled. Four (4) inch PVC
perforated distribution lines shall be laid to a grade shown in the
drawing and be capped at the ends.
Vegetation
To provide favorable transpiration, after the topsoil is placed and
finished, seeding and mulching shall be done over the finished grade.
Seeding shall be of a meadow grass or lucern grass although rye or wheat
will be acceptable.
r _,
EAGLE COUNTY
551 Broadway
Eagle, Colorado 81631
(303) 328 7311
August 20, 1986
First Colorado Mortgage
P.O. Box 1378
Aspen, Colorado 81612
Attn: Bonnie
RE: Loan Inspection for property located at 0601 Kings
Row / Lot 10, Kings Row Subdivision
Dear Bonnie:
All loan inspections are completed under the authority of the
Eagle County Building Resolution, Section 3.09.03-A(7), adopted
by the Eagle County Commissioners on October 8, 1985.
An onsite inspection of the sewage disposal system on August 19,
1986 revealed that the system appears to be functioning properly
with no apparent problems. This septic system was permitted and
finalized on August 2, 1983 under Permit #612.
Enclosed is an invoice in
the amount of $25.00, the fee
for this
loan inspection.
If you have any questions
concerning this inspection, please
contact this office.
Sincerely,
Sid Fox
Asst. Environmental Health
Officer
EAGLE COUNTY
/gP
Enc.
_ t
Y.
u ti
; V
.." .. 1. ._.,
_ t. ..
y ➢
Board of County Commissioners Assessor
Clerk and Recorder Sheriff
Treasurer
P.O. Box 850 P.O. Box 449
P.O. Box 537 P.O. Box 359
P.O. Box 479
Eagle, Colorado 81631 ` Eagle, Colorado 81631
Eagle, Colorado 81631 Eagle, Colorado 81631,
Eagle, Colorado 81631
u
.rt.[�ii.%xt1;u43...Y.udAIN�.fniSi+rrSa.'E�p`+d`e ieeFF sY. ...�bF�.'..�� .r ;. ;__'
,
_ _.. ::' a-. _, .._ fr.^'. �•)'..
.. ...- ., .<av ...
EAGLE COUNTY memorandum
To:
Mr. Mitchell L. Sydoryk
Subject:
Enclosed ISDS Permit #612
From: Environmental Health Office
File No.:
Date: August 4, 1983
This is to inform you that your ISDS Permit #612 has been finalized and signed
off by Richard Pylman on August 2, 1983.
I am enclosing a copy of this permit for your records.
-- Lorraine Funke, Secretary
Environmental Health Office
Eagle County
Enc.
PERCOLATION TEST FEE: $50
I.S.D.S. APP. #
LEGAL DESCRIPTION:
RURAL ADDRESS:
TYPE OF DWELLING:
# OF BEDROOMS:
DATE OF PERCOLATION TEST: TYPE OF SOIL: C la
TEST HOLES PRESOAKED? Yes No
WATER DEPTH
INCHES OF FALL
_-
___I��-1--■
ME
IMEMMINIM!
ME
WOMEN
1111MEN
IMEMEN
WOMEN
PERCOLATION RATE:
RECOMMENDED MINIMUM SEPTIC TANK SIZE:
RECOMMENDED MINIMUM LEACH FIELD SIZE: %o� �i�t�s���✓,
RECOMMENDED MINIMUM SQUARE FOOTAGE PER BEDROOM:
Site has been reviewed and tested for percolation rate.
Date Environmental -Health icer
COMMENTS:
/ee
EAGLE COUNTY memorandum
To: Subject:
Mitchell L. Sydoryk Enclosed - ISDS Permit #612
From: File No.: Date:
Environmental Health Office May 5, 1983
Enclosed is your ISDS Permit #612 for property located on Kings Row Avenue.
The information on the permit application indicates that the system will be
agent (Joe Zamora) installed. Therefore, he will be responsible for the installation
of the system.
This green copy of the ISDS Permit must be posted on the installation site. The
owner/agent must call our office for final inspection before covering any portion
of the installed system. We can be reached at 328-7311, est. 23E
927-3823.
If you have any questions, please contact our office.
-- Lorraine Funke, Secretary
Environmental Health Office
Eagle County
/if
Enc.
;=
a06 NAME,
0612
Kings
Sydoryk Missouri Heights
Row Avenue
5k,lUlS, i't ftW'I;`�
I�
/z"
B
BILL
DATE STARTED I DATE COMPLETED
ka% )ten Svinry VC
P&6ss ; WN0 k,hgs Rove Ap, � , �X0 aces
#! z_N c- 2)q -- o [-00
PERMIT # 612 /
OWNER: . Sydoryk C:,�-°�� e. s,V
P.O. Box 871 - Aspen, CO 81612
>01090q/
LOCATION: Kings Row Avenue - Missouri Heights (West of
Red Table Acres) L-0 10 3,SR0XVe&
INSTALLER: Joe Zamora - AIC Inc. (Engineer Designed)
SIZE OF TANK: 1250 gallons Degrees 300 NE - Feet: 25'
DWELLING: Residential Single Family -- 2 bedrooms
PERC RATE: one inch/40 minutes - per engineer design
Finalized: 8-02-83
By: Richard Pylman
DER