HomeMy WebLinkAboutR96-157 amending LUR's revision to Chapter 3 - building resolutionCommissioner moved adoption
of the following Resolution:
BOARD OF COUNTY COMMISSIONERS
COUNTY OF EAGLE, STATE OF COLORADO
RESOLUTION NO. 96 - 11= %
IN RE THE MATTER OF AMENDING THE
EAGLE COUNTY LAND USE REGULATIONS, 1982 AS AMENDED,
TO PROVIDE FOR A REVISION TO
CHAPTER 3,
THE EAGLE COUNTY BUILDING RESOLUTION
WHEREAS, the Board of County Commissioners of the County of
Eagle, State of Colorado, (hereinafter "the Board ") is authorized
pursuant to State - enabling legislation including, but not limited
to Sections 30 -28 -101, et. seq., C.R.S., to plan for and regulate
the use and development of land in the unincorporated territory
of the County of Eagle, State of Colorado, for the purpose of
promoting the health, safety, convenience, order, prosperity, and
welfare of the present and future inhabitants of the County of
Eagle; and,
WHEREAS, the Board has adopted such regulations, which
regulations have been incorporated as into one comprehensive
document entitled "Eagle County Land Use Regulations" (hereinaf-
ter the "L.U.R."), with Chapter 3 of the L.U.R. known as the
Eagle County Building Resolution; and
WHEREAS, Section 30 -28 -133, C.R.S., and Section 1.16 of the
L.U.R. provides for the adoption and amendment of the regulations
by the Board; and
WHEREAS, the Eagle County Department of Community Develop-
ment initiated proposed amendments to Chapter 3, The Eagle County
Building Resolution ( "Chapter 311) of the L.U.R. to provide for
certain revisions to said Chapter 3 and referred such proposed
amendments to the planning commission, referral agencies and to
the Board for their review and comment; and
I
WHEREAS, after public notice in the Eagle Valley Enterprise,
the Eagle County Planning Commission held a public hearing on
December 4, 1996 to consider comments and to make a recommenda-
tion to the Board on the proposed amendments; and
WHEREAS, after public notice of a public meeting published
in the Eagle Valley Enterprise, the Eagle County Board of County
Commissioners held a public hearing on December 10, 1996 to
consider comments and the Planning Commissions' recommendations
on such proposed amendments; and
WHEREAS, having reviewed all of the evidence, testimony, and
statements submitted at the public hearing, as well as the com-
ments and recommendations of the Eagle County Department of
Community Development, the Planning Commission and certain
referral agencies, the Board hereby determines that the proposed
amendments to Chapter 3 of the L.U.R. are necessary and proper
for the protection of the public health, safety, welfare and best
interest of the County of Eagle, State of Colorado.
NOW, THEREFORE, BE IT RESOLVED BY THE BOARD OF COUNTY
COMMISSIONERS OF THE COUNTY OF EAGLE, STATE OF COLORADO:
THAT, Chapter 3 of the Eagle County Land Use Regulations is
hereby amended as set forth on Exhibit "A ", attached hereto and
incorporated herein by this reference.
THAT, the intent of the revised language is to allow for
certain amendments to the Uniform Building Code 1991 and the
Uniform Mechanical Code 1991; to amend the National Electrical
Code from 1993 to 1996; to amend the Uniform Plumbing Code from
1991 to 1994; and to allow for certain amendments to the Eagle
County Building Resolution.
THAT, these amendments to Chapter 3 shall be effective as of
January 1, 1997.
THAT, the Board hereby finds, determines and declares that
this Resolution is necessary for the public health, safety and
welfare of the residents of the County of Eagle, State of
Colorado.
MOVED, READ AND ADOPTED by the Board of County Commissioners
of the County of Eagle, State of Colorado, at its regular meeting
held the day of December, 1996.
'
ATTEST:
Jerk to the Board of G
County Commissioners
COUNTY OF EAGLE, STATE OF
COLORADO, By and Through Its
BOARD OF COUNTY COMMISSIONERS
Georg A. Gates, Chairman
)4�
r
Johnnette Phillips,
Commissioner
Commissioner seconded adoption of the fore-
going resolution. The roll having been called, the vote was as
follows:
Commissioner Gates
Commissioner Phillips
Commissioner Johnson
This Resolution passed by/yA/�� vote of the Board of
County Commissioners of the County of Eagle, State of Colorado.
mta \c- dev \buildres.amd
no file
4
EAGLE COUNTY
BUILDING RESOLUTION
Adopted October 8, 1985
Amended December 30, 1985
Amended March 11, 1986
Amended February 14, 1989
Amended June 23, 1992
Amended January 4, 1994
A
On���
EAGLE COUNTY BUILDING RESOLUTION
TABLE OF CONTENTS
PAGE NO.
3.01
TITLE
1
3.02
APPLICATION
1
3.03
PERMIT REQUIREMENTS
2
3.04
DEFINITIONS
2
3.05
AMENDMENTS TO THE 1991 CODE
9
Amendments and Deletions to the 1991 U.B.C. Appendix
22
Section
Amendments to the National Electrical
Code ±993 1996 Edition
23
Mumbiitq License Required) Amendments to
the 1994 U.P.C,
25
Amendments to the Uniform Mechanical Code 1991 Edition
29
Amendments to the Uniform Fire Cade 1992 Edition
30
3.06
RESPONSIBILITY OF OWNER
33
3.07
GENERAL RESTRICTIONS
33
3.08
PERMITS AND FEES
34
3.09
DOCUMENTS ON THE SITE
40
3.10
POWERS OF THE BUILDING OFFICIAL
41
3.11
APPEALS
41
3.12
PENALTY
44
3.13
WAIVER
45
3.14
REPEAL
45
3.15
SEVERABILITY
45
3.16
EFFECTIVE DATE
45
e '
4
INDEX OF TABLES
Continued
PAGE NO.
Table
#1 -
Permit Requirements
46
Table
#2 -
Snow Load Requirements
50
Table
#3 -
Building Permit Fees
51
Table
#4 -
Mechanical Permit Fees
54
Table
#5 -
Plumbing Permit Fees
56
Table
#6 -
Electrical Permit Fees
57
Table
#7 -
Elevator Permit Fees
58
Table
#8 -
Enclosure of Factory Built Chimneys
59
Table
#9 -
Construction Sign Board
60
Table
#10-
Permit to Construct Within The Public Way
61
Table
#11-
Design Standards for Driveways
62
13.01 TITLE
T4ip Resolution m4y, bra cited for , a,ll "puxposes, as the Building
Resolution of the Cotinty of Ea91e, ,Col:6rado, X995 1996, as
amended "and , adopted becevb4r , :° 99 , =effective January 1,
1!9,'7. The Board determines and finds that this Resolution is
necessary for the health, safety and welfare of the persons of
Eagle County. Eagle County encompasses mountain terrain located
at moderate to high altitudes and subject to extreme weather
conditions. The application and interpretation of the Uniform
Building Code requirements are subject to, but not limited to,
the consideration of such factors.
3.02 APPLICATION
3.02.01 The Uniform Building Code, Uaifoiia Building Code Standards,
u6iforrn Fire Cade; Uniform Fire Code Standards, Uniform Code for
Abatement of Dangerous Buildings of the International Conference
of Building Officials, 1991 Edition, with Appendices; the Uniform
Mechanical Code of the International Conference of Building
Officials, 1991 Edition, with Appendices; the National Electrical
Code of the National Fire Protection Association, ±993 1996
Edition, with Appendices, with the Uniform Administrative Code
Provision for the National Electrical Code of the International
Conference of Building Officials, 1991 Edition; the Uniform
Plumbing Cade, the Uniform Swimming Pool, Spa, and Hot Tub Code,
and the Uniform Solar Energy Code of the International
Association of Plumbing and Mechanical Officials, 1994 Edition,
National Fire Protection Association, 1994 Edition; Section 13
Installation of Sprinkler Systems, Section 13 -D Sprinkler Systems
ip one and Two Family Dwellings and manufactured Homes, Section
1t-R Sprinkler Systems in Residential Occupancies up to and
including Four Stories in Height, and any and all amendments to
said codes and /or standards as of the date of execution of this
Resolution, are hereby adopted by this reference and incorporated
herein as if set forth in full (hereinafter collectively referred'
to as "code "); and shall apply to all dwellings, buildings and
structures located in the area of the County of Eagle outside of
incorporated towns, hereinafter referred to as the "regulated
area," unless otherwise provided. Said codes and /or standards set
forth in this subsection shall be available from the Building
Official, Department of Community Development, County of Eagle,
500 Broadway, Eagle, Colorado 81631.
1
3.02.02 inhere the requirements or conditions imposed by a provision of
this Resolution or the above - referenced codes and /or standards
differ from the requirements or conditions imposed by a provision
or another law, ordinance, resolution or order having application
in Eagle County, the provision which is more restrictive shall
govern. Not with - standing the foregoing, the most restrictive
provision shall not apply when a provision of an above referenced
code is specifically amended or deleted and so identified within
this resolution and then the terms of this resolution shall
apply.
3.03 PERMIT REQUIREMENTS /REFERENCES
3.03.01 Table 1 entitled "Eagle County Permit Requirements" as set forth
in the Tables included in the text hereof is hereby incorporated
herein by this reference. Table 1 sets forth the projects which
may require permit(s), if any, and identifies the specific type
of permit(s) required and the site inclusion requirements.
Additional permits not identified in Table 1 may also be
required.
3.03.02 It shall be the duty of the person and /or entity of a proposed
project which is not specifically set forth in Table 1 to contact
the Building Official of the Department of Community Development,
County of Eagle, Colorado, for a determination of the type of
permit(s)required, if any, and the site inclusion requirements.
3.04 DEFINITIONS
For the purpose of this Resolution all words, terms and
expressions contained herein shall be interpreted in accordance
with the definitions set out in the 1991 Code, except that:
3.04.01 BUILDING OFFICIAL OR INSPECTOR shall mean the Eagle County Chief
Building Official and the Building Official's duly authorized
deputies, inspectors, staff and other reasonably involved in code
administration and enforcement.
3.04.02 CERTIFICATE OF OCCUPANCY shall mean no building or structure
shall be used or occupied, and no change in the existing
occupancy classification of a building or structure or portion
thereof shall be made until the building official has issued a
Certificate of Occupancy therefor as provided herein.
E
EXCEPTION: Group R, Division 3 and Group M Occupancies.
Issuance of a Certificate of Occupancy shall not be construed as
an approval of a violation of the provisions of this code or of
other ordinances of the jurisdiction. Certificates presuming to
give authority to violate or cancel the provisions of this code
of other ordinances of the jurisdiction shall not be valid.
Certificate of Occupancy for one- and two - family (R -3)
occupancies may be awarded upon special request.
3.04.03 CHIEF OF THE FIRE DEPARTMENT shall mean the head of the fire
protection district having jurisdiction, or his regularly
authorized deputies.
3.04.04 CODE shall mean the 1991 Uniform Building Code, Uniform Fire,
Cide, Uniform Code for Abatement of Dangerous Buildings of the
International Conference of Building Officials, 1991 Edition with
Appendices; Uniform Mechanical Code of the International
Conference of Building Officials, 1991 Edition with Appendices;
tle Uniform Plumbing, Code, the U'nifor Swimming Pool, Spa and not
*b Cade,. and the Uniform Solar „�n!�rgy Code of the International
A *sociation"df Plumbing and Mechanical Officials, 1994 Edition,
4tiona,l Electrical. Code of the Nab loner' . • Eire Protection
Association, 1993 I996'Edition, with Appendices, with the Uniform
A4ministrative Cade Provisions for ,the National. Electrical Cade
of the Internitional Conference of Building Officials,'1991
Edition, National Fire Protection. Association 1994 Edition,
Section 13 Installation of- Sprinkler Systems, Section 13 -D
Sprinkler Systems in One and Two Family Dwellings and
Manufactured Homes, Section 13-R Sprinkler Systems in Residential
Occupancies up to and including Four Stories in Height, and all
amendments to said Codes and /or Standards as of the date of the
execution of this Resolution and as set forth in Section 3.06 of
this Resolution.
3.04.05 COUNTY shall mean the area of Eagle County outside of
incorporated towns, hereinabove referred to as the "regulated
area ".
3
3.04.06 FACTORY -BUILT HOUSING UNIT shall mean any structure or component
thereof, designed primarily for residential occupancy,- either
permanent or temporary which is wholly or in substantial part
made, fabricated, formed or assembled in a manufacturing facility
intended for assembly and installation, on a permanent foundation
at a building site and which carries a Colorado Division of
Housing "Factory -Built Unit Certification ".
3.04.07 FINAL INSPECTION shall mean a final inspection and final approval
of all buildings and structures when deemed complete and ready
for occupancy and use. A final inspection approval for one- and
two - family dwelling units may be granted only if, but not limited
to, the following components of a project are complete and within
the U.B.C. Codes, and approved by the Eagle County Building
Official.
1. Kitchen complete and operative.
2. All bathrooms complete and operative as per the
approved plans.
3. All smoke detectors installed per U.B.C. 1210 and
operative.
4. The following life safety items are fully installed:
a. Address Numbers.
b. Handrails.
C. Guardrails.
d. Decks.
e. Stairs.
f. Separation between the garage and house complete,
with a self - closing, tight fitting, 20 minute fire
protection rated door (must latch).
5. Furnace /Boiler operable.
6. Final Electrical approval.
7. Final Mechanical and Plumbing approval.
8. Fire department review and approval of Commercial or
Multi - Family projects where required.
9. All required permits are issued.
10. Culvert under the driveway installed per County
specifications (located on the approved drawing), and
the on -site drainage improvements are cleaned to allow
water to flow freely.
11. Positive drainage away from the structure at all
locations.
4
12. The exterior of the building shall be completed,
including roof assembly and parking areas, as per
approved plans.
13. Sufficient roadway access for emergency vehicles.
3.04.08 HEALTH OFFICER shall mean the Eagle County Health Officer as
appointed by the Eagle County Board of Health. For the purpose
of administering the Individual Sewage Disposal System
Regulations (Chapter IV Eagle County Land Use Regulations), the
Environmental Health Officer has been designated as his duly
authorized representative.
3.04.09 MANUFACTURED HOUSING (MOBILE HOME) shall mean a factory - assembled
structure or structures equipped with the necessary service
connections and made so as to be readily moveable as a unit or
units on its (their) own running gear and designed to be used as
a dwelling unit(s) without permanent foundation. ANSI A119 -1:(1)
(1) The phrase "without a permanent foundation" indicates that
the support system is constructed with the intent that the
mobile home placed thereon will be moved from time to time
at the convenience of the owner. (American National
Standards Institute (ANSI) Article A119.1: Standard for
Mobile Homes, National Fire Protection Association (NFPA
Edition No. 501A, 1990) Section 1 -2.]
3.04.10 LOFT shall mean any story or floor area in a building which is
open to the floor directly below, but which does not qualify as a
mezzanine due to its failure to comply with one or more of the
items specified for mezzanine floors in Section 1717. At least
one side of the loft shall be at least 50% open to the room
below. Lofts may be habitable space or non - habitable space.
(Habitable lofts in residential occupancies shall be considered
as sleeping rooms or bedrooms).
3.04.11 LOT shall mean any legal parcel of land created in compliance
with the Eagle County Land Use Regulations on record in the
office of the Eagle County Clerk and Recorder.
3.04.12 ROAD OR STREET shall mean a way or right -of -way reserved for
public or private use (other than an alley) which also provides
primary vehicular and pedestrian access to adjacent properties;
it may also be used for drainage or utility access to adjacent
properties, and may include the terms: avenue, drive, highway,
k,
lane, place, road or other similar designation.
3.04.13 SIGN shall mean any letters, figures, design, symbol, trademark,
illuminating device, or other device intended to attract
attention to any place, subject, person, firm, corporation,
public performance, article, machine or merchandise whatsoever,
and painted, printed, constructed or displayed in any manner
whatsoever.
3.04.14 SITE shall mean any parcel or area of land having an area
sufficient to satisfy the provisions of the Eagle County Land Use
Regulations.
3.04.15 TEMPORARY CERTIFICATE OF OCCUPANCY for one- and two - family
dwelling units (R -3 occupancies) shall mean a Temporary
Certificate of Occupancy that may be issued when, but not limited
to, the following components of a project are complete and
approved by the Eagle County Building Official.
1. Kitchen operative.
2. One bathroom operative as per the approved plans.
3. All smoke detectors installed per U.B.C. 1210 and
operative.
4. The following life safety items are fully installed:
a. Address Numbers.
b. Handrails.
C. Guardrails.
d. Decks.
e. Stairs.
f. Separation between the garage and house complete,
with a self- closing, tight fitting, 20 minute fire
protection rated door (must latch).
5. Furnace /Boiler is operable.
6. Final Electrical approval.
7. Final Mechanical and Plumbing approval.
8. Culvert under the driveway installed per County
specifications (located on the approved drawing), and
the on -site drainage improvements are cleaned to allow
water to flow freely.
9. Positive drainage away from the structure at all
locations.
10. The permit holder and owner /buyer /occupant shall enter
into a Temporary Certificate of Occupancy request
agreement wherein they agree that all required
corrections as stated by the Building Official are
completed within the required 30 day timeline -. The
agreement shall be presented to the Building Official
prior to the issuance of any Temporary Certificate of
Occupancy.
11. Sufficient roadway access for emergency vehicles.
The Temporary Certificate of Occupancy agreement shall be
submitted and approved by the Building Official.
The Temporary Certificate of Occupancy for one- and two - family
dwellings shall have a time period of up to, but not more than,
30 days from date of issuance.
The Temporary Certificate shall be posted in a conspicuous place
on the premises until final approval for occupancy is complete.
3.04.16 TEMPORARY CERTIFICATE OF OCCUPANCY for Commercial or Multi -
Family, 3 or more units (A, B, E, H, I & R -1 occupancies) shall
mean a Temporary Certificate of Occupancy that may be issued
when, but not limited to, the following components of a project
are complete and approved by the Eagle County Building Official.
1. Kitchen operative.
2. One bathroom operative.
3. All smoke detectors installed per U.B.C. 1210 and
operative.
4. The following life safety items are fully installed:
a. Address Numbers.
b. Handrails.
C. Guardrails.
d. Decks.
e. Stairs.
f. Separation between the garage and house complete,
with a self - closing, tight fitting, 20 minute fire
protection rated door (must latch).
5. Furnace /Boiler is operable.
6. Final Electrical approval.
7. Final Mechanical and Plumbing approval.
8. Fire department review and approval of Commercial and
Multi - Family projects where required.
9. Culvert under the driveway installed per County
specifications (located on the approved drawing), and
the on -site drainage improvements are cleaned to allow
IVA
water to flow freely.
10. Positive drainage away from the structure at all
locations.
11. Commercial or Multi - family Residential (3 or more
dwelling units) projects shall be required to have a
completed core and shell inspection. The exterior of
said buildings shall be required to be completed,
including roof assembly. The interior of said
buildings shall have all exit corridors, ramps,
stairways, smoke proof enclosures, horizontal exits,
exit passageways, courts, yard and entry ways completed
in all occupied areas. Separate adequate parking shall
be required for the public in said buildings.
12. Where the landscaping, revegetation, drainage or
culvert installation, required under Section 2.07.01
(4) of these Land Use Regulations for the purposes of
preventing land erosion, improper drainage, damage to
properties and unsightliness in residential zones
containing multi family dwellings and in all portions
of lots in CL, CG, I, and PUD Zone Districts, is not
complete, or where Public Improvements are required
under Section 2.20 of the Eagle County Land Use
Regulations, a Temporary Certificate of Occupancy may
be awarded upon submittal and approval of a property
executed Construction Improvement Agreement.
If the improvements required for issuance of a final
Certificate of Occupancy have not been completed within
one year of the date of issuance of the Temporary
Certificate of Occupancy, the County may arrange such
completion using the collateral. Should compliance be
attained any time prior to the expiration of one year,
the collateral will be returned to the permittee upon
issuance of the Final Certificate of Occupancy.
13. Sufficient roadway access for emergency vehicles.
Required improvements collateralized under a
subdivision improvements agreement to which the County
is a party may not be required to be further
collateralized under this sub - section.
The Temporary Certificate of Occupancy agreement shall be
submitted and approved by the Building Official.
The Temporary Certificate of Occupancy for Commercial or
E:
Multi - Family dwellings shall have a time period of up to,
but not more than, one year from date of issuance,- where a
project does not have a Construction Improvement Agreement.
The Temporary Certificate shall be posted in a conspicuous
place on the premises until final approval for occupancy
complete.
3.04.17 WORK shall mean the construction, demolition, alteration, repair,
moving or change in the class of occupancy of any building,
equipment or structure, and shall include the installation,
construction, alteration or repair of any private or subsurface
sewage - disposal system, and the placement and use of a mobile
home as a living unit elsewhere than in an approved mobile -home
park as defined in the Eagle County Land Use Regulations, Section
2.08.
3.05 AMENDMENTS TO THE 1991 CODE
3.05.01 WHERE the requirements or conditions imposed by a provision of
this Resolution differ from the requirements or conditions
imposed by the 1991 Code, the most restrictive shall govern.
3.05.02 THE UNIFORM BUILDING CODE, 1991 EDITION IS SPECIFICALLY AMENDED
AS FOLLOWS:
A. Amendment of Section 202(a) the first sentence of the first
paragraph is changed to read: The Building Official is
hereby authorized and directed to enforce all of the
provisions of this Code; however, a guarantee that all
buildings and structures have been constructed in accordance
with all provisions of this Code is neither intended nor
implied.
B. Amendment of Section 301(b) item 1 "Permits ": One story
detached buildings used as tool and storage sheds,
playhouses and similar uses, provided the projected roof
area does not exceed 120 square feet and the height of said
buildings does not exceed 10 feet at peak of roof.
These buildings must specifically not be intended or used
for human habitation. Amendment of Section 301(b)7: Decks
not more than 30 inches above grade and not more than 20
square feet, will not require a Building Permit.
4
C. Amendment of Section 303(a) "Issuance" to add the - following
paragraph:
A building permit will not be issued in the Eagle County
jurisdiction until all construction drawings, applications,
and permit fees are submitted and approved. Notwithstanding
the foregoing, a footing and foundation permit may be issued
prior to the receipt of other permit information, if
adequate structural, site plan, flood plain and geological
hazard information is provided.
D. Amendment of Section 303(d): No permit shall be extended
more than once; is hereby deleted.
E. Amendment to Section 304(b) "Valuationff - to add the
following sentence:
The valuation for building permits in Eagle County shall be
based on the average cost figures per square foot shown in
the Building Valuation Data Chart published bi- monthly in
the Building Standards Magazine of the International
Conference of Building Officials.
F. Amendment of Section 305(b) "Inspection Record Cards" to add
the following sentence:
Inspection Record Cards shall be posted as described in
Table No.8, included in the text hereof and incorporated
herein by this reference.
It shall be the responsibility of the permittee to display
the Building Permit card on the job site throughout the
construction process for inspectors signatures.
For occupancy approval, Temporary Certificate of Occupancy
or Certificate of Occupancy approval to occur, this card
must be fully signed and returned to the Eagle County
Building Deg= tiftel Division.
If this card becomes lost or unreadable, there will be a
$20.00 fee to update or replace the card.
G. Amendment of Section 306(a) "Special Inspection" to add the
10
following sentences:
LOG HOMES: A third party inspection by a certified log
inspection agency shall be required of all structural log
type buildings. A letter of certification from said agency
shall be required at time of framing inspection.
ELEVATORS: Elevators installed in all structures shall
require a third party plan review and inspection by a
certified elevator inspection agency.
H. Amendment of Section 503(d) "Fire Ratings for Occupancy
Separations" to add the following paragraph:
1. Single family residences having primary and secondary
units within.
2. Insulation placed in occupancy separations
shall not contain combustible materials.
3. A one hour fire resistive assembly shall be required
for separation of individual tenant finishes of Group B
Division 2 Occupancies located under a common roof
assembly.
IM Amendment to add Section 514 'Fire Alarm Systemsff as
follows:
a. WNW REQU3:RZD. An approved manual, automatic, or
manual and automatic fire alarm system shall be
provided in accordance with this section. Installation
of fire alarm systems shall be in accordance with this
article. The regulations contained in this article
require the installation of electrically supervised
fire alarm systems.
All fire alarm systems required by the Eagle county
Building Resolution or the Uniform Building Code shall,
be monitored as required by occupancy, When automatic
fire - extinguishing systems are required by the Vniform
Fire Code, or by the Uniform Building Code, such
systems shall be connected to the building fire alarm
system, and shall annunciate upon activation of the
fire alarm /fire protection system.
11
For the purposes of this article, .area, separation walls
shall not define separate-buildings. The number of
stories in occkipav&ies othei,, =than R-3 shall mean all
habitable ',l.evel.s of.. a� ,st ructure including but not
limited.to. basements, garden levels, mezzanines, lofts,
and floors
b. SYSTEM %AYWT AXD OPZR T:EOX .
manual Fire Alarm faxes. when a manual fire alarm
system is required, manual fire alarm boxes shall be
distributed throughout so .they. are readily accessible,
unobstructed, and are located in the normal path of
exit travel from the area and as follows
S. At every exit from every Level.
2. Additional fire alarm boxes shall be located so
that travel. distance , to .the nearest box does not
exceed 200 feet.
Control Mnits, Annunciator Panel and Access Keys. The
alarm control unit, remote annunciator panel and access
kegs to all fire alarm equipment shall be installed and
maintained in a location approved by the Chief of the
Fire Department. Where required, the location of an
operated initiating device shall be visibly indicated
by building, floor, type of devise, or other approved
subdivision by annunciation, printout, or other
approved means. The visible indication shall not be
canceled by the operation of an audible alarm silencing
means.
,Alarm Initiation and Signal. When actuated, fire
alarm -- initiating devices shall activate an alarm signal
which is audible throughout the building or in
designated portions of the building when approved by
the Chief of the Fire Department.
XXCUPTION: Signal- station detectors in dwelling
units, rooms used for sleeping purposes in hotel and
lodging douses, and patient sleeping roams in hospitals
and nursing homes. All devices must comply with the
A.D.A. requirements where applicable
12
Ala= Signal. The alarm 'signal shall be keyed to' one
half to' one I second,, one' second-,-off- for three
cycles, immediately after= which, , when 'a voice alarm is
requirede''a voice, announcement shall be :broadcast. The
alarm signal shall be repeated fog ,Ithe duration that
the ,fare alarm syst6i,ii',activated.
ZXC39PTION.* This alarm signal is not required for:
1. Group A occupancy having a fire alarm signal, in
accordance with teqti
approved plans and specifications.
Instructions. When required by the Chief of the Fire
Department, operating, testing and maintenance
instructions and..t`as- built drawings and equipment
specifications :shall be provided at an approved
location.
J. Amendment to Section 'S09 rcup A, Divissonl,2,2.1 and 3
Occupancies. Section 6Q .is amended to'read as
follows:
An approved fire alarm system shall be installed as set
forth in the Fire Code amendments for in Croup A, Divisions
1, 2, 2.1 and 3 Occupancies.
K. Amendment to Section 809 9`UX Ar_AIMS. Section 809 is amended
to read as follows:
Group E Occupancies shall be provided with fire alarm
systems. Group E Division 1 Occupancies and Group E,
Division 3 Occupancies baving,an occupant load of 50 or more
shall be provided with an approved monitored manual and
automatic fire alarm system. When automatic sprinkler
systems or smoke detectors provided in accordance with this
section are installed, such systems or detectors shall be
connected to the building fire alarm system.
L. Amendment to Section 909 FIRS ALARMS. Section 909 is
amended to read as follows
Group H Occupancies shall be provided with a fire alarm
system where the floor area exceeds 5,000 square feet on any
or all floors. The fire alarm system shall be bath manual
and automatic.
Organic Coatings. Organic coating manufacturing uses shall
be provided with a manual fire alarm system.
Group H, Division 6 Occupancies. Group H, Division b
Occupancies shall be provided with a manual fire alarm
system.
Rooms used for storage, dispensing, use and handling of
hazardous materials. When required by the 'Uniform Fire Code,
14
rooms-or areas used for storagei"dimpensing,, use or handling
0 f - hi Ohl y , toxi c,:,,6*iim,
,pressed solid
oxidizers•, !and plais 1, - 17, ltl` 6 ` IV'br4anip peroxides •
shall, bo- provided' viitli a' . maaivaI:_aiid, automatic smoke-
detectionValaxii system.
to Socti, 10,0.9 a last paragraph
as follows:
Divlision 3 bacupancies.
General. Group, ;s Division,3 6o4%AOailcies_ shall be provided •
with a manual. and automatic fire,"AlArm system ,installed.for
alertin4'the staff.
System zuitiati6a. Actuation bf,'anautomatic fire-
extinguishing system,'a or a heat:
detector shall initiate an approved fire alarm signal v&ich
automatically, notifies staff. systems shall not
be used.
manual fir* Alarm Boma.
1. General, manual fire alarm boxed need not be located
in accordance with Section 1807 wheia they are ,provided
at staff-attended locations having direct supervision
over areas where-manual fire alarm boxes have been
omitted.
2. Locking of Manual Fire Alarm Boxes. Manual fire alarm
boxed are allowed to be locked in area's occupied be
detainees, provided the staff members are present
within the subject area and have keys readily available
to operate the manual fire alarm boxes.
Smoke Detection. An approved automatic smoke-detection
system shall be installed throughout resident housing areas,
including sleeping areas and contiguous day rooms, group
activity spaces and other common spaces normally accessible
to residents.
X=XPTX0X-. Other approved smoke-detection arrangements
providing equivalent protection, such as placing detectors
09.1
in exhaust ducts from cells or behind protective grills, are
allowed when necessary to prevent damage or tampering.
Zoning and A=Unciation. Alarm -and trouble signals shall be
annunciated at an approved constantly attended location.
Such signals shall indicate -the, =,zone I or origin. Separate
zones shay, be p' rovided ' for , irid viduil fire-protection
systems, buildings, flours,',cell.'complexes and sections of
floors coMartmented I>y smoke-- atops-, partitions.
-:E N. Amendment to Section 1204 "Access and Rxit Facilities and
Emargency,Xacapes" to add the following paragraph:
Escape and rescue windows with a finished sill height below
the adjacent ground elevation shall have a window well.
Window wells at escape or rescue windows shall campy with
the following.,
1. The clear horizontal dimensions shall allow the window
to be fully opened and provide a minimum accessible net
clear opening of 9 square feet, with a minimum
dimension of 36 inches.
2. window wells with a vertical depth of more than 44
inches shall be equipped with an approved permanently
affixed ladder or stairs that are accessible with the
window in the fully open position. The ladder or
stairs shall not encroach into the required dimensions
of the window well by more than 6 inches.
0. Amendment to Section 1211. Section 1211 ,,Fire Alarm
Systems,w to amend the .first. paragraph:
Group R Occupancies shall be protected with fire alarm
systems in accordance with this section. Group R, Division
1 Occupancies shall be provided with a manual and automatic
Eire alarm system in apartment houses three or more stories
in height or containing 12 or more dwelling units, in hotels
three or more stories in height or containing 20 or more
guest roam, and in congregate residences three or more
stories in height or having an occupant load of 20 or mare.
16
in any mixed occupancy building - containing any Group R,
Division I or" Division, 3 - OccU0,6ncy,, any, automatic and manual
fire alarm system shall be pio41'ded,ihroughout.
For the purpose of this article, area separation walls shall
not, define 'separate building q,'.itn,d_e tli,4,number of stories in
occupancies other" than Group 'R;,, Division 3 shall mean all
habitable 14vels'of -,a,'structiire including, , but not limited
to basements', garden levels, zi� zzaniii6s . . .... lofts, and floors.
rj=PT3:ON :
1. Manual fire alarm systeqp,need not be provided in
buildings not over two'storiles in height when all
individual, dwelling units'an4_,66ntiguous attic and
crawl spaces are separate from'each other and
public or common areas by at least one-hour fire -
resistive occupancy separiL-t1ioln's. -and each
individual dwelling unit or'
,guest room has an exit
directly to a public way, exit court or yard.
2. A separate fire alarm system need not be provided
in"buildings which are protected throughout by an
approved'monitored fire 6prinkler's'ystem
conforming with the Building Code and having a
local alarm to notify all occupants.
Smoke Detectors. Smoke detectors shall be required in
all common areas and interior corridors serving as a
required exit for an occupant load of 10 or more,
Heat Detectors. Heat detectors shall be provided in
common areas such as recreational rooms, laundry rooms,
furnace rooms, and similar areas in accordance with
U.F.C. Standard 14-1 and 14-2.
Visual Signaling Devices. Guest rooms for persons with
hearing impairments shall be provided with-Visual and
audible alarm-indicating appliances, activated by both
the 4n-room smoke detector and the building fire alarm
system.
Single-Station Smoke Detectors. Approved single-
station smoke detectors shall be installed in dwelling
OIN
units, congregate residences and hotel or lodging house
guest roomy in actor& .with;"tt4e,Building Code.
Single - station smoke detectors, shall not be connected
to a`fine alarm system.
VTTOX; Connection of-such detectors for
annunciation only.
Amendment of Section 1212 "Heating" to add the following
sentence: Heat loss calculations shall be required for all
dwelling units, the minimum design criteria shall be 70
degree temperature inside and -20 degree temperature
outside.
Minimum insulation requirements for Group R Division 1 &3
occupancies shall be as follows: R -11 for exterior walls and
R -19 for ceilings and roofs exposed to the outside.
Insulation installed for exterior walls and exterior
ceiling's shall be required to have a minimum 4 mil vapor
barrier or equivalent.
iff Q. Amendment to Section 1213 "Special Hazards" the exception is
hereby deleted and the following sentences are added:
Residential buildings containing a boiler, central heating
plant, or hot water supply boiler _h. of where the
largest piece of fuel - equipment exceeds 400,000 Btu per hour
input, the room where the boiler is located shall be
required to be separated by one -hour fire resistive
construction.
-h R. Amendment to Section 1706 "Shaft Enclosures" to add the
following subsection:
Factory built chimneys shall be enclosed with materials
suitable for construction of a one hour fire resistive wall.
Firestops can be omitted in chases which are protected on
all sides. Eagle County requirements for enclosure of
factory built chimneys shall be as set forth in Table 7,
included in the text hereof and incorporated herein by this
reference.
S. Amendment to Section 1807 (a) %OcoW to add the following
paragraph:
flu
Group B office buildingsand Group R, Division 1
Occupancies, each having floors- used for human occupancy
located "more,, than 751,feet',,aboVe"t;#ik lowest level of fire
aepa-it]meht,'ac6ess ',, Oali,be, provid4d'vift-h'an automatic fire
alarm" sys , tem and a communii6atii6n,-system in accordance with
this sectl"Ori.
t Amendment to Section 1867" (d) ." wSmoke-Detection Systems," I to
add the "folltwing paragraph:
(d) Auto matte rire Ala= System. Smoke detectors shall be
provided in accordance with Section JB07. Smoke
detectors 'shall be .connected ,,to an automatic fire alarm
system. The activation,of,any'detector required by,
Section 1807 shall vp'dr4te "the energency, voice alarm-
signaling system and shall placelinto operation all
equipment,necessary I to." prevent the recirculation of
smoke. Smoke detectors siball'be"llocated as follows.-
1. in every mechanical equipment, electrical, transformer,
telephone equipment, elevator machine or similar room,
and in elevator lobbies. Elevator lobby detectors
shall be connected to an alarm verification zone or be
listed as a releasing device;
2. In the main return-air and exhaust plenum of each HVAc
system. Such detectors shall be located in a
serviceable area downstream of the last duct inlet;
3. At each connection to a vertical duct or riser serving
two or more stories from.a return-air duct or plenum of
an HVAC system. in Group R, Division 1 Occupancies, an
approved smoke detector is allowed to be used in each
return-air riser carrying not more than 5,000 cubic
feet per minute and serving not more than 10 air-inlet
openings; and
4. For Group R, Division 1 Occupancies, in all interior
corri dors serving as a required exit for an occupant of
10 or more.
M U. Amendment of Section 2305(d) "Snow Loads" This section is
hereby deleted and replaced with the following:
19
Snow load requirements for Eagle County shall be as set
forth in Table 2, entitled "Eagle County Snow Load
Requirements ", included in the text hereof and incorporated
here in by this reference. *For snow loads on mobile homes,
refer to page 50.
N V. Amendment of Section 2905(f) "Drainage" to add the following
paragraphs:
Positive drainage away from the exterior of all foundation
walls must be maintained. In those locations where the
foundation is subjected to a high water table, or where
surface or ground water drainage will present a problem,
additional precautions may be required.
Foundation Drains - Where foundation or footing drains are
required or provided voluntarily, they shall be connected to
a positive outfall or approved drywell. Direct the flow
from , outfall ref ,v derdrai
Q Y.Regarding Chapter 31 of the Uniform Building Code: Eagle
County does not purport to review, interpret or apply in any
manner the provisions set forth in 36 THE Part 1191,
Americans With Disabilities Act (ADA); Chapter 31 of the
1991 Uniform Building Code is advisory only. Compliance
with Chapter 31 of the Uniform Building Code and the ADA is
the sole responsibility of the property owner and /or his /her
agents and representatives.
R Z.Amendment to Section 3703(f) "Height and Termination" to add
the following sentences:
"Solid fuel chimney caps shall not be constructed in a way
that prevents accessibility for cleaning ".
Where solid fuel and /or gas burning appliance flue vents are
terminated within 24 inches horizontally of each other said
flue vents are to be offset 10 inches vertically.
-S AA.Amendment of Section 3705(a) °Factory Built Chimneys and
Fireplaces" to add the following sentences:
Factory built chimneys shall be supported at intervals not
to exceed 10 feet by wall straps or equivalent.
Outside combustion air shall be required to the fireplace
both gas -fired and wood burning, to be terminated inside the
firebox wall. Ducts for said combustion air shall be a
minimum of 26 gauge galvanized metal when located in a fire
resistive shaft.
Pursuant to Eagle County Land Use Regulations Section
2.07.11 Wood Burning Control:
No building or mechanical permits will be issued for the
installation of a wood burning device unless the device is a
new technology device as defined in Eagle County Land Use
Regulations Section 2.07.11. or is otherwise exempt.
B . Amendment of Section 38€ 3 "Sprinkler System ,Supervision
AlarmsO to add the following sentences:
When an automatic sprinkler system is required, all valves
controlling the water supply for automatic systems and
21
water -flow alarm and trouble si
1Z II.Uniform Building Code Appendix Chapter 26 - "Protection of
Residential Concrete Exposed to Freezing and Thawing" is
hereby deleted.
AhJJ.Uniform Building Code Appendix 35 - "Sound Transmission
Control" is hereby deleted.
5BM Uniform Building Code Appendix 38 - "Basement Pipes inlets"
is hereby deleted.
eeLL . tin orm Building Code Appendix < 1. � "Elevatosrs" : Amendment
to fee schedule - A fee for each permit shall be paid to the
Northwest Colorado Council of 'Governments
See table 71for';fee requirements by Northwest Colorado
Council .of Govm nments.
For permit applications and to;schedulo inspections, contact
Elevator inspection. Program a.t j,R1 i) 468 -0295 Ext. 108.
The. Annual Certificate of inspection and fees will be
administered by the Certified Elevator Inspection agency.
Section 5110(b) Exception is hereby deleted.
DDMM.Uniform Building Code Appendix Chapter 70 -
"Excavation and Grading" Section 7015(a) "Final
Reports ". Add a new subsection #4 to read:
Where drainage improvements are required, the work is to be
completed per approved plans and ready for inspection at the
time of the Temporary Certificate of Occupancy inspection.
It will be the general contractor's responsibility to
maintain positive drainage on the site during all phases of
construction, including protection of any drainage along the
Public Roadway.
3.05.03 THE NATIONAL ELECTRICAL CODE, ±993 1996, EDITION IS
SPECIFICALLY AMENDED AS FOLLOWS:
A. Amendment of Article 220 -4 (b) to add the
following sentence to the first paragraph:
There shall be no more than four (4) duplex receptacles on
23
the small appliance branch circuit.
B. Amendment of Articles 210 -21, 220 -3, 220 -4 to add
the following sentence to the first paragraph:
Only eight (8) outlets will be installed on 15 amp
circuits; or ten (10) outlets on 20 amp circuits
for lighting branch circuits including receptacles.
C. Amendment of Article 305 -1 "Temporary Wiring - Scope" to add
a new subsection (e):
Permanent services on buildings which are energized
for construction work will be considered as
temporary service equipment until such time as the
final inspection is completed.
D. Amendment to the N.E.C. 1993 Article 210 -8 to add the
following sentence: All G.F.C.I. protection shall be
resetable in rooms where protection is required
including outside receptacles.
E. Amendment to Article 680 -70 Hydromassage Tubs to add
the following sentence:
All G.F.C.I. protection shall be located with in the same
room. It is to be installed 5 feet + off of finished floor
and 5 feet from hydromassage bathtub. The cord is not to
exceed 3 feet from motor to receptacle installed near the
access door protected by the resetable G.F.C.I. mounted on
the wall. (The resetable G.F.C.I. is not to be installed
under the tub). A 15" x 201, minimum access is required for
hydro massage tub motors.
3.05.04 THE UNIFORM ADMINISTRATIVE CODE PROVISIONS FOR THE NATIONAL
ELECTRICAL CODE, ±993- 1996 EDITION IS SPECIFICALLY AMENDED
AS FOLLOWS:
A. Table 3B - "Fee Schedule" is hereby amended. Current
schedule of Electrical Permit fees is contained in Table #6.
B. Electrical License Rectuired:
Pursuant to 12 -23 -105 C.R.S. only qualified licensed
electricians may install "Electrical Work" as defined in
24
12 -23 -101 (1.7) by Colorado State Electrical Board 1988
Edition.
Notwithstanding the foregoing provision, an Electrical
License will not be required provided all conditions of
Section 12 -23- 111(2) C.R.S. have been satisfied.
3.05.05 PLUMBING LICENSE REQUIRED
Pursuant to 12 -58 -115, C.R.S., only qualified licensed
plumbers may install "Plumbing Systems" as defined in ±±Elj
202'.0 of the Uniform Plumbing Code, ±99± 1994 Edition.
3.05.06 The Uniform Plumbing Code Section 3-0-4 103.4.1 ' east of-
Permrt-" "APOZZit FO+' go, Schedtz±e of Fees" is hereby amended.
Current schedule of Plumbing Permit Fees is contained in
Table 5.
A. Amendment of Section 3 63 --(k) 603.3-.4 - Heat Exchangers, and
other assemblies or methods of construction using potable
water shall be of listed construction and materials. The
sections in contact with potable water shall be of material
and weights suitable for potable water as set forth in this
chapter.
e B. Appendix I entitled "Private Sewage Disposal Systems" is
hereby deleted.
f) C. Amendment of Section )- 807.4 - No domestic dishwashing
machine shall be directly connected to a drainage system or
food waste disposer without the use of an approved
dishwasher airgap fitting on the discharge side of the
dishwashing machine. Listed airgaps shall be installed with
the flood level (FL) marking at or above the flood level of
the sink or drain board, whichever is higher, or separately
trapped with the airbreak located on the stand pipe.
25
ft D. Amendment of Section 5$fr 906.1 - Vent terminations on metal
roofs shall be within 3 feet of the ridge or be provided
with an alternate means of protection.
E. Amendment of Section frig- 911 - "Horizontal and Vertical Wet
Venting" (d) - Single bathroom groups - a single bathroom
group of fixtures may be installed with the drain from an
individually vented lavatory or lavatories serving as a wet
vent for a bathtub, shower compartment, or floor drain and
for a water closet provided the requirements listed below
are met: (1) Not more than four fixture units drain into a
minimum 2 inch diameter wet vent. Kitchen sinks,
dishwashers, or automatic clothes washer connections are not
permitted. (2) The horizontal branch drain connects to the
stack at the same level as the water closet drain; or it
may connect to 'the upper half of the horizontal portion of
the water closet bend at an angle not greater than 45
degrees from the direction of flow. (3) Trap arm sizes and
lengths shall conform to tables 4 -1, 4 -3, and 7 -1.
. - - -
1 aw,
Amendments of Section 1008.0- 1008.5 - "SAND INTERCEPTORS"
WHERE REQUIRED:
1. Wherever a drain discharges through an oil interceptor,
it must first discharge through a sand interceptor.
Multiple floor drains may discharge into one sand
interceptor.
2. whenever the discharge of a floor drain may contain
solids or semisolids that would be harmful to a
drainage system, or tend to choke the system, the
discharge must be through a sand interceptor.
M
wcoxamamoN JMDzlZir, - Sand in�:erdeptors ~shall 'be built of
bjick or concrete and ,be watertight*',,, -The jnterceptor ,shall have
aq interior, brick ,or, concrete ,baffl,,O_ftr
"_the full :separation cf
tfie, interceptor izito-t:46,, sections. ""the outlet pipe shall be the
same size as the,inlletsize ofl,the_qil,interceptor, the minimum
b4ing 3 inchesir and the, baft 1 1 e must'bave, .two - opens ngs of the
same diameter as the "Cutlet' pipe "aaid,,ki�,',ihd;iaine'invert, as the
outlet pipe. These ' openin4s laust ,,
be,:stAggered so that there
cannot be a straight line of.,,fl0w`b6t*4en any inlet pipe and the,
outlet pipe. The invert of the inlet pipes must be no lower than
the invert -of tbaloutlet pipe.
The sand interceptor shall have a minimum dimension of 2 feet
square for the net free opening of and a
minimum depth under 'the invert of,the outlet pipe of 2 feet.
For each 5 gallons per minute flowor1 fraction ,thereof over ,20
gallons per minute, the area of inlet
section.is to be'increa-sed by I'square foot. The outlet section
shall have at all times a minimum area of ,50 percent of the inlet
section. The outlet section must be d6vered,by a solid removable
cover set flush with the finished floor, and the inlet section
shall have an open grating set flush,with the finished floor and
suitable for the traffic in the area , in which it is located.
'"ALTERNATED - Alternate designs for construction or baffling of
sand interceptors complying with the intent of this code may be
submitted to the Building official for approval.
IRDISCWMGZ,w - When a sand interceptor is used by itself without
also discharging through an oil interceptor, the outlet pipe must
be turned down inside the interceptor under the water level to
provide a 6-inch water seal. A cleanout shall be installed to
provide access to the outlet line.
VIOXL Am LIQUIDS SEPARATOR" WHERE REQUIRED-GENERAL: -
All commercial storage or repair garages; gasoline stations with
grease racks, grease pits or wash racks; all motor vehicle
laundries and all factories which have oily and/or flammable
wastes-as a result of manufacturing, storage, maintenance, repair
or testing processes shall be provided with all necessary floor
4ains, sand interceptors, catch basins and oil interceptors
properly vented through the roof on the sewer side of the
27
diameter with a full -size cleanput to.grade and the gent pipe not
less than 2- inches.
%%C0MBIKRTI0X ,t)2L RIRD SAND I1111FURCZMR0 -- A. combination oil and
sand interceptor maybe installed when the design is approved in
writing:by the Building Official.
"D881w0n" OVEM"L RZQ 0 r' I'CNI TSB' z - Oil separators shall have a
depth of not less than 2-feet below , the„ invert of the discharge
drain: The outlet opening r�f,,, the, s�:parator shall, have not less
than an 18 -inch water'seal.
"MOTOR VERICLS GA.RAQB8,0 , - _„ On . each floor of garages where not more
than three motor vehicles are serviced and stored, separators
shah, have a minimum capacity of 6,cubic feet, and 1 cubic foot
capacity shall be added 'for each. vehicle up to 10 vehicles.
Above 14'vehicles, the Building Official .shall determine the size
of the separator required.
`OSSR"V"ICS STRTXONS AND .R,XPA3:R SRAS00 , - Where , vehicles are serviced
only and�not stored, separator capacity shall be based on a net
capacity of 1 cubic font for each 100, square feet of surface to
be drained into the separator with a minimum of 6 cubic .feet.
G. Amendment of Section 1204.3.1 to add the following sentences:
This inspection shall include air, G02 or nitrogen pressure test,
at which time the gas piping shall stand a pressure of not less
than 10 psi for threaded pipe for not less than 15 minutes.
I H. Amendment of Appendix D - (d) - Overflow drains shall be the same
size as the roof drains with the inlet flow line two inches
(50.8mm) above the low point of the roof and shall be installed
independent from the roof drains.
1. Amendment of Section 1249.6 KGas Motor Locations" to add
the following sentence:
Gas meters shall not be located in an area subject to
physical damage, i.e. areas subject to snow and /or ice
falling from roofs or vehicle damage.
J. Amendment of Section 1214.1 to add the following sentences:
TItef1we piping shall be app oved'.mate ial for the installation,
e*tenslon, alteration, or repair of,any,gas piping provided the
installer has been 'certified by ,Titeflex" .
3.05.07 The Uniform Mechanical Code, 1991 Edition is specifically amended
as follows:
B A. Amendment of Section 304(b) Table 3 -A has been amended see Table
4 of the Eagle County Building Resolution.
e B. Amendment of Section 504 ( f) 'To add , the following , sentences :
Aut Approved means for removal of ,unburned gas, shall be a minimum
3# drain pipe to the exterior of the_,buildingl:' The drain shall
nbt' be trapped and shall be protecf�a"frbu� snow closure and
rodents. When the above listed means cannot =be achieved, an
e' sneered mechanical. , exhaust syst+64,:6hall be "Installed. in'
addition to the approved means of removing unburned gas, a
propane sensor, with 100% safety shut -off, shall be required.
C. Amendment of , Section 506 °Auto3iatie Control Devices"-
The exception allowing log lighters to be exempt from having an
automatic control device is hereby deleted.
A D. Section 1104: Domestic kitchen range exhaust ducts which
discharge from the bottom of the range through the base cabinet
and into a space below the floor, shall be made of at least 26
gauge metal and shall have smooth surfaces. This requirement
shall include those listed ranges which permit the use of
flexible metal exhaust ducts.
E. Amendment of Section 2004 (b) 6 "Detailed Require w ts" to add
the following paragraph:
A ,'new subsection has been added; "Protection of Commercial
Cooking Operations and Maintenance". Activation of the fire
extinguishing equipment shall sound an alarm and shall send a.
monitored signal to a remote station monitor.
29
3.05.08 The Uniform Fire'Code, 1991 Edition is specifically amended as
follows:
A. Section 9.105 thief of the; Fire Pep shall mean the head of
the fire prntectidn:-district� having- jirisdi6tion, or his
regularly authorized ,deputie .
B. Section 9'-.13 +central 'Statiai"Sire A1ii-it,Station is a system or
group of systems in which the operations of circuits and devices
are transmitted automatically to,'recorded in, maintained by, and
supervised from a, central station, having competent and
experienced servers and operators who, upon,receipt of a signal,
take such action as required by this code. Such service is to be
controlled.and. operated by a person, firm, yr- corporation whose
business is'the furnishing, maintaining, or monitoring of
supervised .fire alarm systems.
C. Section 9.114 Zvocal Oupervisory System Is a local system arranged
to supervise the performance of guard's tour's, or the operative
condition of automatic sprinkler systems or other systems for the
protection of life: and property against a fire hazard.
D. Section 9.115 Monitored is the mending of fire alarm signals
using circuits installed in accordance with the 1993 edition of
the National Fire Protection Association Standard 72 to transmit
alarm, supervisory and trouble signals from one or more protected
premises to an approved remote station monitoring center at which
appropriate action is taken.
E. Section 9.118 Proprietary Fire Alarm Station is an installation
of fire alarm systems that serve contiguous and noncontiguous
properties under one ownership from a proprietary supervising
station located at the protected property, where trained,
competent personnel are in constant attendance. This includes the
proprietary station; power supplies; signal initiating devices;
initiating device circuits, signal notification appliances;
equipment for the automatic, permanent visual recording of
signals; and equipment for initiating the operation of emergency
building control services.
F. Section 9.120 Remote Station mire Alarm System is a system
installed in accordance with this cede to transmit alarm,
supervisory, and trouble signals from one or more protected
premises to a remote location at which appropriate action is
30
taken.
G. Section 9.120 Remote,Station Mcmiltoring,Center is a place to
w1iich remote alarm and su&rvisor'y`,, pignaling devices are
c4nnect,id,, and .where personneI, are-, 1*,attenda6ce at all times to
s4pervise', the, circuits, investigatte"si4.als'and transmit
e4ergency signals, to", the 'Fire Department,. A remote monitoring
canter may include Centiil,'Staii on
, Service'
H. s*ction,9:110 sixiervisizo Stat�.oi2 is alacility that receives
s$gnails and where personnelj'L`r'e in,,attendance at "'all times to
r4spond io these signals.
1. SO'ction 10.507 (d) Group B, Division 2,10ccupancies is amended .to
riad:
AA automatic sprinkler system shah. -be ,installed in all Group
BI Division'"l and bivision 2 Occupancies where the floor area
exceeds 12,000 square feet on any floor or 24,000 square feet on
all floors. The area of mezzanines shall be included in
determining the areas where sprinklers are required.
J. Section 10.508 Sprinkler System Supervision Alarms is amended to
read:
All valves controlling the water supply for automatic
sprinkler systems and water-flow switches on all systems shall be
electrically supervised. Valve supervision and water-flow alarm
axid trouble signals shall be distinctly different and shall be
automatically transmitted to an approved remote station
monitoring center.
XXCRPTXONS
1. Underground key or hub valves in roadway boxes provided
by the Town, district, or public utility need not be
supervised.
21. Single family homes.
K. Section 10.513 (a) Fire-extinguishing.Equipment for Protection of
Kitchen Grease Hoods and Ducts Section (a) is amended to include
the following
31
L.
M.
Activation of the fire extinguishing equipment shall sound an
alarm and shall serid,a monitored sigzAl t6"a,remote station
monitoring center.,,The remote station Monitoring center shall
notify the fire department, ' in an, approved; mafhod.
Section 14.101 Fire Alarm Systems, Scope is amended as follows:
(a) Installation of .fare alarm systems shall be in accordance
with this :article: The regul4tions contained in this article
require the 'installation of electrically supervised fire alarm
systems.'All fire alarm syst4ks required by .the Fire Code or the
Building-Code shall be moatored,
(b) For the purposes of this article, area separation walls
shall not define separate buildings,, and the number of stories in
occupancies other than R--3, sball,mean all habitable levels of a
structure irxcluding_,bqt not, limited to, basements, garden levels,,
mezzanines, lofts and floors.
(c) Alarm signals sball,be an audible'or visual signal, or both
audible and visual signals indicating the existence of an
emergency fire condition. Alarm,,signals shall be as required by
the Americans With Disability Act,. Audible devices may be horns,
chimes, speakers or similar devices. Voice alarms and pre-
recorded messages shall be approved by the Building Official.
(d) When automatic fire-extinguishing systems are required under
this code, or the building code, such systems shall be connected
to the building fire alarm system, and shall annunciate upon
activation of the system.
(e) in buildings containing an atrium, all doors opening into
the atrium from any A, B, E, or M occupancy shall be equipped
with an electrically operated 'closer' or **'hold open" so that
activation of automatic fire detectors within the occupancy shall
cause such doors into the atrium to close.
Section 14.104 Required Installations is specifically amended as
follows:
(b) Group A, Divisions 1, 2, 2.1, and 3 Occupancies. 1. General.
Group A Divisions 1, 2, 2.1, and 3 Occupancies shall be provided
with a manual and automatic fire alarm system.
(c) Group B Division I and Division 2 Occupancies. 1. General.
Group B Division I and 2 Occupancies where the floor area exceeds
5,000 square feet on any floor or 10,000 square feet on all
floors shall be equipped with an approved manual and automatic
fire alarm system. The area of mezzanines shall be included in
32
de termining the ,aireas"wh a fire alai i:,pyst� s are required.
{ } Group s ,:D ivision l.=.and'Division" '.:t c+cupancies. 1. -Genera..
- 3 ap , Aari, cupant load of G oup , Div�iiion `and Aip
50 or more shall -be ',provided ,,with 4zi Appr4wed Dual and
automatic fire alarm', system.
(,�) 'Group H Occupaxicie .,,,1. Genera... ,Opbup,H Occupancies shall be
pa ovided with a_' jxe alaicm :syste t. •whera: "'the • oor, area ` ceeds
a i 0010 squire feet ',on any:, f ,00i, or Al f aors" ' and in , accordance
with this : subsection._,: The fire, alarzk, system •shall be bath manual
azid automatic.
(f) Group R, Division, 1' Occupancies. 1.7 neral.. .Group'R,
Division 1 Occupancies shall be provided with a, manual and
automatic' fire alarit system In apariii nt, ,h6usas " thhree or mare,
stories in height or, containing 12 ' or 'iW6r� „dwel3:ing,'units, in
hie tell three or more stories in height or,- containing 2'0,6r more
guest rooms, and in congregate residences three of more 11 stories
ii height or having an occupant load of,20,or more. .A fire alarm
aid communication system shall be provicdn Group R, division 1
t cupancies located iri'a high -rise building as set forth in the
B *ilding code.
(4) in any mixed occupancy containing .any' G;oup:,R, Division 1
or Group R, Division 3 Occupancies, and autoinatic. and manual fire
alarm system shall be provided throughout.
N. Section 14.105 Monitoring is deleted.
3.06 RESPONSIBILITY OF OWNER, CONTRACTOR OR AUTHORIZED AGENT
Neither the granting of a permit, nor the approval of the
drawings and specifications, nor inspections made by the Building
Official shall in any way relieve the owner of such building or
structure from full responsibility for carrying out all work in
accordance with the requirements of this Resolution.
3.07 GENERAL RESTRICTIONS
3.07.01 No person shall commence or continue any on site work in respect
to any building, structure, factory -built housing unit, mobile
home equipment, road cut permit, grading permit, construction
parking or storage of materials, without first obtaining the
33
necessary permits from the Community Development Office, Building
Division.
3.07.02 No person shall commence or continue any work in respect to any
private or subsurface sewage disposal system without first
obtaining a permit from the Environmental Health Division.
3.07.03 Written approval of the Environmental Health Division shall be
obtained before the backfilling of any private or subsurface
sewage disposal system.
3.07.04 In respect to any work undertaken in violation of the provisions
of subsection 3.07.03 or 3.07.05 of this Section, the Building
Official or Environmental Health Officer or their duly authorized
representatives, may at any time require that such work, in whole
or in part, be exposed for inspection.
3.07.05 No person shall occupy any new building, factory -built housing
unit or mobile home until sewage disposal facilities, meeting the
minimum standards of the regulations of the State Board of Health
or any of the Eagle County Individual Sewage Disposal
Regulations, have been installed and have been approved, in
writing, by the Environmental Health Division.
3.08 PERMITS AND FEES
3.08.01 The Building Division shall issue a permit where:
A. An application for a permit has been made in accordance with
the provisions of this Resolution.
B. The proposed work set out in the application conforms to
this Resolution and all other laws, regulations,
resolutions, or orders having application in Eagle County.
C. All Construction drawings, applications, and permit fees
have been submitted and approved. A footing and foundation
permit may be awarded to large commercial projects subject
to approval by the Chief Building Official prior to receipt
of other permit information if structural and site plan
information pursuant to Sections 302(b) and 302(d) of the
1991 Building Code and the Eagle County Land Use
Regulations, 1988 as amended, is provided.
34
3.08.02 The Building Department-Division shall not issue a permit where:
A. The proposed work, as set forth in the application, or the
proposed use of the building or structure when completed,
does not comply with the provisions of the Eagle County
Zoning Resolution;
B. The owner or applicant, in relation to the proposed lot or
site, has not complied with the provisions of the Eagle
County Subdivision Regulations controlling the subdivision,
platting, partitioning, or other division of land;
C. The proposed work, as set forth in the application, or the
proposed building or structure when completed, would be in
violation of any official county map, resolution, or the
Eagle County Master Plan;
D. A private or subsurface sewage disposal system is necessary
and the proposed site does not meet the requirements,
conditions, or imposed provisions of State law or regulation
of the State Board of Health, or of any Eagle County sewage
disposal regulation. Where a private or subsurface sewage
disposal system is necessary and the proposed site meets the
requirements or conditions therefore imposed by a provision
of the aforesaid laws, regulations, or resolutions, the
Building Official shall not issue a permit until sewage
disposal permit has first been issued in writing by the
Environmental Health Office;
35
E. The proposed site is located, all or in part, within any
area determined by the Building Official to necessitate
special building requirements as a result of geological
hazards or Flood Plain Hazard Area in any county resolution;
and the special permit required by such resolution has not
been obtained by the applicant. All special building
requirements included in any such special permit shall be
incorporated into the permit issued to the applicant under
this Resolution;
F. In the opinion of the Building Official, the results of the
tests referred to in Section 3.10.02 of this Resolution are
not satisfactory.
G. The proposed work is to be done within a
subdivision (including a resubdivision) for which a final
plat ( including any relevant ametided final plat)
has not been approved and for which a Subdivision
Improvements ,agreement, if required by or for the final plat
approval, has not been entered into.
H. No Building,Permit shall be issued until site plans are
presented that show an on alte area that is and will remain
available for cuff- street parking and storage of construction
materials.
3.08.03 FEES
A. The schedule of fees to be charged
permit under this Resolution shall
3, 4, 5, and 6, as included in the
and inspection fees for the Unifon
the Uniform Swimming Pool, Spa and
with the minimum stated on Table 3
for the issuance of a
be as set forth in Tables
Tables. Minimum permit
u Solar Energy Code and
Hot Tub Code shall comply
of this Resolution.
B. Additional permit fees shall be charged as follows:
1. For moving or demolishing any building or
structure .................... .........................$42.50
(per inspection).
2. For Factory Built, Manufactured Housing /Mobile Home Base Fee
Cost:
Wi
Sinale Wide Unit
2 field inspections and 1 hour plan checking /office
time ......................... ........................$127.50
Double Wide Unit
3 field inspections and 2 hour plan checking /office
time ......................... ........................$212.50
Note: The above includes Plumbing and Mechanical
inspections without separate permitting.
Note: All additional inspections will be $42.50 each.
Examples: Footing, Foundation (other than Block /Pads),
reinspections and any and all inspections performed on a
basement.
3. For site inspection and review of a plot to evaluate
potential locations for an individual subsurface or private
sewage disposal system, per lot or test site (does not
include percolation test) .... .........................$85.00
** See Resolution No. 80 -11, 1980 - Local Board of Health
Eagle county Individual Sewage Disposal Regulations.
4. For site inspection including percolation test and soil
profile observation (per visit ) ......................$200.00
5. For review and completion of a Federal Housing
Administration questionnaire with respect to a dwelling to
be sold, including site inspection of a water supply and
sewage disposal system and water supply evaluation including
water well construction comments .....................$200.00
6. For reinspections of improperly installed septic -
systems ...................... .........................$42.50
C. If the Building Official discovers any person undertaking any
work in violation of this Resolution, he shall notify the
violator to cease such act or acts, and such violator shall pay
for such permit twice the amount of the fee otherwise levied
(U.B.C. Sec 304(e)).
37
D. The estimated value of the work shall be reviewed by the Building
Official and shall be based on the declared cost of materials and
labor for each permit for each building or structure. The
Building Official shall account for all fees paid under this
Resolution for any building, mobile -home placement shall deposit
in the County General Fund. (See 3.05.02 of the ECBR).
E. The General Contractor shall be required to provide adequate
sanitary facilities during construction.
F. The minimum mechanical permit fee for voluntarily replacing an
existing wood burner with a new technology device or a device
which permanently utilizes natural gas, propane or similar clean
burning fuel, shall be waived.
G. A reduced fee for a repetitive, plan check will be allowed when
one or more buildings are to be constructed from a set of plans
previously approved by the.Eagle County Building Division.
The applicant applying for the repetitive plan check will bring
in the original stamped approved plans and an identical plan or
plans to the Building Division. The new identical plans will be
kept as County records. The original approved set of plans will
be re- stamped with the new Building Permit Number and date. This
set will become the approved field copy for the repetitive
permit.
A plan check fee of $42.50 per hour with a minimum of 3 hours to
be charged.
3.08.04 An application for a permit shall:
A. Be made on the form prescribed by the Building
Depar Division;
B. Be signed by the applicant;
C. Be accompanied by the fee prescribed for work to be
undertaken;
D. State the intended use of the building structure;
W:?
E. Include copies in duplicate of a site plan and scale
drawings and specifications of the work to be carried out as
required by Section 302 of the 1991 Uniform Building Code.
Notwithstanding the provisions of Section 302 of the 1991
Uniform Building Code, the site plan shall show and include:
1. Property lines, direction of North and scale of
drawings.
2. outline of proposed and existing building with setbacks
from property lines indicated on all sides.
3. All easement and utility, water and sewer line
locations.
4. Driveway and driveway intersection with public road,
including grades, widths, and necessary culverts and
ditches.
5. Parking spaces dimensioned and numbered, with snow
remov- a±storage area indicated.
6. Proposed method of drainage of water away from
foundation and into drainage way.
7. Proposed soil stabilization, revegetation or landscape
plan with erosion and sediment control.
8. Location of live streams, ponds or lakes, all other dry
washes and irrigation ditches, and 100 year flood plain
limits and 50, setback from high water mark.
9. Proposed and existing wells on subject property and
adjacent property.
10. Location of individual sewage disposal system, if
proposed, with distances indicated from proposed system
to dwellings, wells, and other fixed reference objects.
11. Proposed construction parking and staging area.
3�
12.Whenever a site plan shows a possible
encroachment into a setback, i.0'., within IS
inches, a condition will be placed on the permit that
requires an improvements Location, Certificate be
prepared by a Professional Licensed Surveyor and
submitted with the request for a footing or foundation
inspection. The I.L.G. must include extent of proposed
roof overhangs.
F. The building plans submitted with permit application shall
include:
1. Complete Eagle County Building Permit application,
including the parcel number-This number is available
M
3.09
3.09.01
through the Assessors. office.
±-a,2. Footing and Foundation details are required
to be. submitted before a building permit'can
be -issued.
33- 3. Neat loss calculations for residential dwellings are
required to
be subs fitted be "fare' a: mechanical permit can be
issued.
±4- 4. Floor plans.
3Ei 5. Elevations.
±.& 6. Framing plan gar, crass section..
±--h 7. Roof plan.
±-& S. Framing details.
±-9, 9. Wall,floor and roof framing.
X10. Mechanical details - commercial only.
X11. Plumbing details -- commercial~ only.
X1.2. Electrical drawings -- commercial. only.
X13. Mobile home /Manufactured housing detail
z X14. Any additional information deemed reasonable
and necessary by the Building Official.
DOCUMENTS ON THE SITE
The person to whom the permit is issued shall, during
construction, keep:
A. Posted in a conspicuous place on the property in respect of
which the permit was issued a copy of the building permit or
a poster or place card approved by the Building
Division in lieu thereof, and;
B. A copy of the approved drawings and specifications referred
to in Subsection 3.08.04(E) on the property in respect of
which the permit was issued.
C. It shall be the responsibility of the permittee to display
the building card on the job site throughout the
construction process for inspectors signatures.
For Temporary Certificate of Occupancy or Certificate of
Occupancy approval to occur, the building card must be fully
signed and returned to the Eagle County Building Department.
If this card becomes lost or unreadable, there will be a
$20.00 fee to update or replace the card.
40
3.10 POWERS OF THE BUILDING OFFICIAL
3.10.01 The Building Official is charged with the administration and
enforcement of the Resolution under authority of the Eagle County
Department of Community Development.
3.10.02 The Building Official may , along with
**her r tidies provided in this Ri6p6A7 46n, xd the Uniform
Boilding',_.god.i
A. Enter any premises at any reasonable time for the purpose of
administering this Resolution:
B. Direct that tests of materials, devices, construction
methods, structural assemblies or foundation conditions be
made, or sufficient evidence or proof is necessary to
determine whether the material, devices, construction or
foundation meets the requirements of this Resolution. The
records of such tests shall be kept available for inspection
during the construction of the building or structure and for
such a period thereafter as required by the Building
Official;
C. Direct by written notice, or by attaching a placard to
premises, the correction of any condition where, in the
opinion of the Building Official, such condition violates
the provisions of this Resolution;
D. Revoke a permit or certificate of occupancy where there is a
violation of the provisions of this resolution, including
construction which is not in conformance with approved plans
or conditions of the permit.
3.11 APPEALS
A. A Board of Appeals shall be created as provided in
Section 204 of the 1991 Code.
41
3.11.01 Appeals to the Board of Appeals:
A. Membership of the Board of Appeals.
A Board of Appeals, consisting of five (5) members, shall be
appointed by the Board of Commissioners to hear and decide
appeals as provided hereunder. The Board of Appeals shall
appoint from its membership a Chairman and a Secretary who
shall keep a written record of all proceedings of the Board.
B. Qualifications of Board Members:
If any such persons are available in the County, each member
shall be a licensed professional engineer or architect or a
building contractor or superintendent of building
construction, or other person qualified by experience and
training to pass on matters pertaining to building
construction, and at no time shall there be more than two
members from the same profession or business; and at least
one member shall, if possible, be a licensed architect and
one member shall be a licensed structural or civil engineer.
C. Application for Appeal
Any person aggrieved by a decision of the Building Official
denying, issuing, or revoking a permit or in applying the
provisions of the Code or this Resolution to the
construction, alteration or repair of a structure, as herein
defined, may appeal such decision to the Board of Appeals.
D. Time for Appeal
An appeal shall be commenced within 10 days from the date of
the decision appealed from by filing a written Notice of
Appeal with the Secretary of the Board of Appeals setting
forth the decision appealed from.
E. Board Action on Appeal
Upon receipt of a Notice of Appeal, the Secretary shall
schedule said appeal for Hearing in 30 days, or if the Board
has adopted a regular schedule of meetings, not later than
the third regular meeting following receipt of the Notice.
42
The Secretary shall thereupon mail written notice of the
date, time, and place of the Hearing to the Building
Official and to the Appellant.
F. Hearings
Hearings shall be public and shall be conducted as nearly as
possible in conformity with Section 24 -4 -105 C.R.S. 1973, as
amended. The Board shall adopt reasonable rules and
regulations for the conduct of hearings and thereafter such
rules and regulations shall govern the conduct of such
hearings.
G. Rulings
The Board shall issue its findings and rulings thereon in
writing not later than 30 days after the hearing, or not
later than the second regular meeting following the hearing,
if the regular schedule of meetings has been adopted by the
Board. The Secretary shall mail copies of the findings and
rulings to the Building Official and Appellant.
3.11.02 Appeals to the Board of County Commissioners
A. Grievances
Any person aggrieved by a decision of the Board of Appeals
shall have the right of appeal therefrom to the Board of
County Commissioners. Such appeal shall be made within
thirty (30) days from the date of the decision of the Board
of Appeals, and in the case of an appeal by the Building
Official, the original Appellant shall be notified within
five (5) days from the date of the decision that the
Building Official intends to appeal the decision.
B. Procedure
Appeals hereunder shall be commenced by filing a written
Notice of Appeal with the Clerk to the Board of County
Commissioners, who shall schedule the appeal for hearing not
later than the second regular meeting following receipt of
said Notice. The Clerk shall notify the Secretary of the
Board of Appeals, the Building Official and the Appellant in
writing of the date, time and place of the hearing.
43
C. Transmission of Files
Upon receipt of the Notice from the Clerk, the Secretary of
the Board of Appeals shall transmit the File containing all
Exhibits, Testimony and Evidence of whatsoever kind to the
Clerk not later than ten (10) days prior to the scheduled
hearing.
D. Hearing
At the Hearing the Board of County Commissioners shall
examine the file and consider any additional evidence which
it deems appropriate. Strict rules of evidence shall not
apply, but all additional oral evidence shall be reduced to
writing in summary form.
E. Ruling
within ten (10) days from the date of the Hearing the Board
shall issue its written ruling affirming, modifying, or
reversing the Ruling of the Board of
Appeals. Copies of the Ruling shall be mailed to the
Secretary of the Board of Appeals, the Building Official,
and the Appellant.
The Building Official shall then take whatever action is
indicated by the Ruling of the Board.
3.12 PENALTY
3.12.01 No person shall commence or continue any work in respect to
use or occupy any building, structure, or mobile home, or
any sewage disposal system in violation of the provisions of
this Resolution.
3.12.02 Any violation referred to in subsection 1.15.04 of the Lind
Use Regulations shall be deemed a nuisance.
3.12.03 Any person who violates the provisions of this Resolution is
liable upon conviction to a fine of not more than one
hundred dollars, or by imprisonment in the county jail for
not more than ten days, or by both such fine and
imprisonment. Each day during which such illegal erection,
44
construction, reconstruction, alteration, maintenance, or
use continues shall be deemed a separate offense.-
3.12.04 In case any building or structure is or is proposed to
be erected, constructed, reconstructed, altered, remodeled,
used or maintained in violation of the provisions of this
Resolution, the Board, the Building Official, the District
Attorney of the District, or any owner of real estate within
the area, in addition to other remedies provided by law, may
institute an appropriate action for injunction, mandamus or
abatement to prevent, enjoin, abate, or remove such unlawful
erection, construction, reconstruction, alteration,
remodeling, maintenance or use.
3.13 WAIVER
The Building Official may waive any permit requirements
within this Resolution only after a determination that the
effect of such a waiver is minor and will not affect the
health, safety and welfare of the persons occupying
buildings of Eagle County.
3.14 REPEAL
Upon the approval and adoption of this Resolution by the
Board, all existing or previously adopted Building
Resolutions not reflected in this Resolution be and the same
are hereby repealed and superseded by this Resolution.
3.15 SEVERABILITY
The Eagle County Board of Commissioners hereby declares that
if any section, subsection, clause or phrase of this
Resolution or of the 1991 Code adopted by this Resolution,
is for any reason held to be invalid by the decision of any
court of competent jurisdiction, such decision shall not
affect the validity of the remaining portions of this
Resolution and /or 1991 Code.
3.16 EFFECTIVE DATE
This Resolution shall be in force and effect from and after
the date of the Board's execution of this Resolution.
45
(1) BUILDIN, 'LUMBING (3) ELECTRICAL (4) MECHANIC j) GRADING
(6) INDIVIDUAL SEWAGE DISPOSAL (7) SIGN (8) MANUFACTURED HOUSING HOOKUP
(9) FIRE ALARM SYSTEM (10) FIRE SPRINKLER SYSTEM
ROUTING ABBREVIATIONS:
BUILDING DIVISION =BD ENVIRONMENTAL HEALTH =EH
PLANNING DIVISION =PD ENGINEERING =—EG
(This Table is a Permit Requirement Guideline ONLY, and does not take precedence over the Uniform Codes as adopted by Eagle
County)
CLASSIFICATION
SPECIFIC PROJECTS
NO
PERMIT (S)
REVIEW
SITE PLAN
OF PROJECTS
PERMIT
REQUIRED
REQUIRED
REQUIRED
REQUIRED
New Structures
Building of New Residential
1, 2 ,3, 4, 5, 6, 9, 10
BD, EH, PD, EG
X
Structures
Building of New Non-
1, 2, 3, 4, 5, 6, 9, 10
BD, EH, PD, EG
X
&
Residential Commercial
Structure
Factory Built
Structures
Moving of Existing
Structure to New Location
1
BD, EH, PD, EG
X
Moving of Manufactured
Housing into a Mobile
3,8
BD, PD
X
&
Home Park
Manufactured on
Private Land
Moving & Setting of Factory
Built Structure on Building
1, 2, 3, 4, 5, 6
BD, EH, PD, EG
X
Site
May Require a ROM tat
3
EG
X
Permit Through Fatglrteering
Depart
Amended
Building of a Structure Used
X
Agricultural
Solely as an Agricultural
Building (See 3}Pg
9 (See 105,02 0" Pg, 26
One story detached
X
buildings used as tool and
storage sheds playhouses
and similar uses provided
the projected roof area does
not exceed 120 s.f. and the
height of said buildings does
not exceed 10 feet at peak of
roof.
Condemned
Demolition of the Whole or
1
BD, PD
Buildings
Part of Building, Factory
Built Structures, or
Manufactured Housing
Additions &
Additions & alterations
1, 2, 3, 4, 6, 9, 10
BD, EH, PD, EG
X
Alterations to
involving bedroom,
Exterior
bathroom, kitchen, living
Construction & On
room, or other accessory
Sire Accessory
rooms
Construction
Additions & alterations
1, 2, 3, 4, 5, 6
BD, PD, EG
X
involving an attached or
detached garage or shop
Non - structural
X
sidewalWslabs
.,
CLASSIFICATION
SPECIFIC x — OJECTS
NO
PERMIT (S) REVIEW
SITE PLAN
OF PROJECTS
PERMIT
REQUIRED REQUIRED
REQUIRED
REQUIRED
Additions &
Decks and Patios not over 30
X
Exterior
inches above grade with no
Construction &
permanent construction above
On Site Accessory
the floor line
Construction
Decks, Entry Porches, Etc.
1,3
BD, PD
X
Retaining Walls, over 4 feet
1
BD, EG
X
in height (Engineering
Required)
Fences over 6 feet in height
1
BD, PD
X
Fences used for Agricultural
X
purposes only or those fences
under 6 feet in height
Erection of Exterior Signs
7
BD, PD
X
(Except as Exempt in
Zoning Resolutions)
All Non - Structural
X
Landscaping
Exterior Repair &
Replacement of Roof
1
BD
Replacement &/or
Addition
Repair or Replacement of
X
Exterior Siding
Replacement or Addition of
1
BD
Exterior Window
Repair of Existing Exterior
X
Window
Addition of Exterior Door
1
BD, PD
Repair or Replacement of
X
Existing Exterior Door
Interior Repair &
Repair or Replacement of
X
Replacement &/or
floor covering
Addition
Painting, Papering or Similar
X
Finish Work - Exterior or
Interior
Installation of Woodburning
4
BD
Stove or Fireplace
47
CLASSIFICATION
SPECII OJECTS
NO
PERMIT (S) REVIEW
SITE PLAN
OF PROJECT
PERMIT
REQUIRED REQUIRED
REQUIRED
REQUIRED
Interior Repair &
Replacement of Furnace or
4,2
BD
Replacement &/or
Hot Water Heater (Except
Addition
Electrical Appliances)
(Continued)
Kitchen Remodel, i.e. Cabinet
X
EH
Replacement of Counter
Commercial
Replacement
Repair, alteration,
2
BD
replacement or addition of
plumbing system
Repair, alteration,
3
BD
replacement or addition of
electrical system
Demolition of Interior Wall
I
BD
Addition of Interior Wall
1,6
BD
Repair of up to 144 square
X
feet of drywall except fire
resistive assemblies & other
than residential construction
Addition or replacement of
X
built -in cabinets or shelves
Water &/or Sewer
*Installation of Private Sewer
6
EH
X
Systems
System
*Expansion of Private Sewer
6
EH
X
System
*Repair of Private Sewer
6
EH
X
System involving replacement
of septic tank or
repair /moving of leach field
Disconnection of Private
X
EH
Sewer System and
Connecting to Public Sewer
System (Contact Applicable
Water /Sewer Jurisdiction)
Installation of Private Water
X
System (Contact Colorado
Division of Water Resources)
Installation of Public Water
X
System Serving More than 20
People (Contact Colorado
Division of Water Resources,
Colorado Department of
Health)
Serving 20 People or Less
6
EH
X
May Require Road Cut
5
EG
X
Pcruut Through, Pig
TJep�t
*See Resolution of Local Boards
of Health, County
of Eagle, State of Colorado,
Resolution #80
-1980.
RM
CLASSIFICATION
SPECIFI )JECTS
NO
PERMIT (S) REVIEW
SITE PLAN
OF PROJECTS
PERMIT
REQUIRED REQUIRED
REQUIRED
REQUIRED
Plumbing
Plumbing syftm as did
2
BD
In Swdon 202-0 of the UPC
Mechanical
All Mechanical installations
4
BD
as listed in the fee schedule
Fire Alarm
Fire Alarm Systems
9
BD
Installation or addition; fee
OR
based on valuation of system
Fire Sprinkler System
Installation or addition; fee
10
BD
Fire Sprinkler
based on valuation of system
Addition of interior walls
9,10
BD
Road Cut and
Excavation, Grading and
5
EG, BD, PD
X
Grading and Parking
Graveling or Paving of a
Road to be Dedicated to the
County for Maintenance
Excavation, Grading, and
5
EG, BD, PD
X
Graveling or Paving of a
Commercial or Residential
Parking Lot
Excavation, Grading and
5
EG, BD, PD
X
Graveling or Paving a New
Private Driveway
Repair or Repaving of an
X
Existing Driveway or Parking
Lot
Paving of an Existing Gravel
X
Driveway or Parking Lot
Installation of New, Repair or
5
EG, BD
Replacement of Culvert (May
require road cut permit
through Road & Bridge Dept.
Engineering)
49
*Local jurisdictions may vary from this table.
Note - UBC Section 2306 "Reduction of Live Loads ": Reduction of snow loads for roofs having a pitch exceeding 20 degrees shall be
allowed when designed and stamped by a licensed Engineer. Most manufactured housing has been designed and constructed with
specific roof load/snow load capacity. While a manufactured home may appear to meet the manufacturer's specifications for roof
load/snow load in Colorado, said specifications may not be sufficient for the particular climatic conditions in Eagle County. It is the
owner's sole responsibility to maintain the necessary roof load/snow load to protect the manufactured housing.
If the elevation of a specific site differs from an elevation in this table, contact the Building Division for the snow load at the site.
50
TABLE 2
GLE COUNTY SNOW LOAD REOUIREMEN
LOCATION
ALTITUDE
SNOW LOAD
- LBS /SO.FI'.
Arrowhead
7500
60
Aspen Junction
7200
54
Aspen Mesa
7200
54
*Avon
7500
59
Bachelors Gulch
8050 -9500
73 -113
*Basalt
6600
43
Beaver Creek Village
8150
77
Ridge
8800
93
_Bellyache
Berry Creek
7350
57
Bond
6752
45
Burns
6463
40
Colorow Subdivision
8200
77
Cordillera
8000 -8600
70 -85
Cordillera Valley Club
7400
59
Cottonwood Pass
8280
79
Coulter Creek
8100
75
Derby Junction
6463
40
Dotsero
6149
35
Dowd Junction
7726
65
*Eagle
6497
40
Eagle -Vail
7600
63
Eby Creek
6850
47
Edwards
7260
55
El Jebel
6500
40
Frying Pan River Area
7000 -8000
50 -72
Fulford
9900
121
Gilman
8800
93
*Gypsum
6320
40
Homestead
7250 -7800
55 -62
Lake Creek
7500 -8000
59 -72
McCoy
6742
44
*Mintum
8000
72
Missouri Heights
7250
55
Meredith
8000
72
Radium
6800
50
Redcliff
8700
90
Red Table Acres
7200
54
Reudi Shores
7800 -8400
67 -82
Seven Castles
7200
54
Squaw Creek
7500 -8500
60 -85
State Bridge
6886
48
Strawberry Park
8750 -9000
90 -98
Sweetwater
7500
46
Tennessee Pass
10400
98
*Vail
8150
77
Vail Pass Area
10400
98
West Vail
8000
72
Wolcott
6984
50
*Local jurisdictions may vary from this table.
Note - UBC Section 2306 "Reduction of Live Loads ": Reduction of snow loads for roofs having a pitch exceeding 20 degrees shall be
allowed when designed and stamped by a licensed Engineer. Most manufactured housing has been designed and constructed with
specific roof load/snow load capacity. While a manufactured home may appear to meet the manufacturer's specifications for roof
load/snow load in Colorado, said specifications may not be sufficient for the particular climatic conditions in Eagle County. It is the
owner's sole responsibility to maintain the necessary roof load/snow load to protect the manufactured housing.
If the elevation of a specific site differs from an elevation in this table, contact the Building Division for the snow load at the site.
50
TABLE *3
BUILDING PERMIT FEES
EAGLE COUNTY, COLORADO
Amendment of Section 304(b)- Valuation
BUILDING PERMIT FEES
TOTAL VALUATION FEES
$1.00 TO $500.00 $20.00 (MINIMUM)
$501.00 TO $2,000.00 $20.00 FOR THE FIRST $500.00 PLUS $3.00 FOR EACH
ADDITIONAL $100.00 OR FRACTION THEREOF, TO AND
INCLUDING $2,000.00. IN NO CASE SHALL FEES BE
LESS THAN $20.00. EXCEPTION, REFER TO OTHER
INSPECTIONS AND FEES.
$2,001.00 TO $25,000.00 ,$65.00 FOR THE FIRST $2,000.00 PLUS $10.00 FOR
EACH ADDITIONAL $1,000.00 OR FRACTION THEREOF, TO
AND INCLUDING $25,000.00
$25,001.00 TO $50,000.00 $315.00 FOR THE FIRST $25,000.00 PLUS $7.00 FOR
EACH ADDITIONAL $1,000.00 OR FRACTION THEREOF, TO
AND INCLUDING $50,000.00
$50,001.00 TO $100,000.00 $490.00 FOR THE FIRST $50,000.00 PLUS $5.00 FOR
EACH ADDITIONAL $1,000.00 OR FRACTION THEREOF, TO
AND INCLUDING $100,000.00
$100,001.00 TO $500,000.00 $740.00 FOR THE FIRST $100,000.00 PLUS $4.00 FOR
EACH ADDITIONAL $1,000.00 OR FRACTION THEREOF TO
AND INCLUDING $500,000.00
$500,001.00 TO $1,000,000.00 $2,340.00 FOR THE FIRST $500,000.00 PLUS $4.00 FOR
EACH ADDITIONAL $1,000.00 OR FRACTION THEREOF, TO
AND INCLUDING $1,000,000.00
$1,000,001.00 AND UP $4,340.00 FOR THE FIRST $1,000,000.00 PLUS $3.00
FOR EACH ADDITIONAL $1,000.00 OR FRACTION THEREOF.
PLAN CHECK FEES RESIDENTIAL & COMMERCIAL ARE 65% OF AMOUNT OF
BUILDING PERMIT FEE.
aasxsxaa asa sxxssxxsaxaa aax:: aasssxxxas :ss : :sassasaaxsaaaa :aa :asaaa
OTHER INSPECTIONS AND FEES:
1. Inspections outside of normal business hours ..............$63.75 per hour.
2. Reinspection fee assessed under provisions of
Section 305(8) ................... .........................$42.50 per hour.
51
3. Inspections for which no fee is specifically indicated... $42.50 per hour.
4. Additional plan review required by changes, additions
or revisions to approved plans (minimum charge 3 hour) at $42.50 per hour.
5. Additional inspections for which collected fees are
not adequate .............. ............................... $42.50 per hour.
6. For Factory Built, Manufactured Housing /Mobile Home Base Fee Cost:
Single Wide Unit
2 field inspections and 1 hour plan checking /office
time......................... ............................... $127.50
Double Wide Unit
3 field inspections and 2 hour plan checking /office
time ........................ ............................... $212.50
Note: The above includes Plumbing and Mechanical inspections without
separate permitting.
Note: All additional inspections will be $42.50 each. Examples:
Footing, Foundation (other than Block /Pads), reinspections and any
and all inspections performed on a basement.
7. Requests for specialized reports will be charged $42.50 hourly with a 1/2
hour minimum.
8. Per Eagle County Building Resolution Section 3.05.02(F), if the building
card becomes lost or unreadable, there will be a $20.00 fee to update or
replace the card.
9. Fire Sprinkler systems and Fire Alarm Systems. Permit fees shall be based
on the valuation of the systems equipment and installation. Plus an
additional 65% for plan review.
10, Elevator Permit fees shah be paid to the Northwest Colorado Council of
Governments.
See table 7 for fee requirements by Northwest Colorado Council of
Governments.
For permit applications and to schedule inspections, contact Elevator
Inspection Program at 1970} 468 -0295 Ext. 108,
-1-6 11. Replacement of roof for single - family structure v:rlyis $27.00.
52
3± 12. Grading permit fees and plan review fees.
PLAN REVIEW(2 hour min) ................. .................$42.5@ /hour$85.00
50 cubic yards or less .............. ............................... $42.50
51 to 100 cubic yards ............. ............................... $42.50
101 to 1000 cubic yards - $42.50 for the first 100 cubic yards plus $10.50
for each additional 100 cubic yards or fraction thereof.
1001 to 10,000 cubic yards - $117.00 for the first 1,000 cubic yards, plus
$9.00 for each additional 1,000 cubic yards or fraction thereof.
10,001 to 100,000 cubic yards - $198.00 for the first 10,000 cubic yards,
plus $40.50 for each additional 10,000 cubic yards or fraction thereof.
100,001 cubic yards or more - $562.50 for the first 100,000 cubic yards,
plus $22.50 for each additional 10,000 cubic yards or fraction thereof.
Other Inspections and Fees:
1. Inspections outside of normal business hours........ $63.75 per hour
2. Reinspection fees assessed under provisions of
Section 305( g) ....... ............................... $42.50 per hour
3. Inspections for which no fee is specifically
indicated (minimum charge -on hour) .................. $42.50 per hour
53
TABLE 4
MECHANICAL PERMIT FEES
The minimum mechanical permit fee for voluntarily replacing an existing wood
burner with a new technology device or a device which permanently utilizes
natural gas, propane or similar clean burning fuel, shall be waived.
Permit Issuance
1. For the issuance of each permit ..... ............................... $20.00
2. For issuing a transfer permit ....... ............................... $20.00
3. Total Permit Fee shall not be less than ............................ $42.50
Unit Fee Schedule
1. For the installation or relocation of each forced -air or
54
gravity type furnace or burner, including ducts and vents
attached to such appliance, up to and
including 100,000 Btu /h ............. ...............................
$9.00
2.
For the installation or relocation of each forced air or
gravity type furnace or burner, including ducts and vents
attached to such appliance over 100,000 Btu /h .......... ...........
$11.00
3.
For the installation or relocation of each floor furnace,
includingvent ....................... ...............................
$9.00
4.
For the installation or relocation of each suspended heater,
recessed wall- heater or floor- mounted unit heater ...................
$9.00
5.
For the installation, relocation or replacement of each
appliance vent installed and not included in an appliance
permit............................... ...............................
$4.50
6.
For the repair of, alteration of, or addition to each heating
appliance, refrigeration unit, cooling unit, absorption unit,
or each heating, cooling, absorption, or evaporative
coolant system, including installation of controls regulated
by this code ......................... ...............................
$9.00
7.
For the installation or relocation of each boiler or
compressor to and including three horsepower, or each
absorption system to and including 100,000 Btu /h ....................
$9.00
8.
For the installation or relocation of each boiler or
compressor to and including three horsepower, or each
absorption system over 100,000 Btu /h and including 500,000
Btu/ h ............................... ...............................
$16.50
9.
For the installation or relocation of each boiler or
compressor over 15 horsepower, to and including 30
horsepower, or each absorption system over 500,000 Btu /h
and including 1,000,000 Btu/ h ....... ...............................
$22.50
10.
For the installation or relocation of each boiler or
compressor over 30 horsepower to and including 50 horsepower,
or for each absorption system over 1,000,000 Btu /h to
and including 1,750,000 Btu/ h ....... ...............................
$33.50
54
11. For the installation or relocation of each boiler or refrigeration
For each gas - piping system of one to four outlets 1 to 4........ $5.00
For each gas - piping system of over four (4) outlets, per outlet..... $1.00
Other InsDection Fees
1.
compressor over 50 horsepower, or each absorption system -over 1,750,000
hour)
Btu/ h ............................... ...............................
$56.00
12.
For each air - handling unit to and including 10,000 cubic feet
305( g) .............. ............................... $42.50(per
per minute including ducts attached thereto .........................
$6.50
13.
For each air - handling unit over 10,000 cfm .........................
$11.00
14.
For each evaporative cooler other than portable type ................
$6.50
15.
For each ventilation fan connected to a single duct .................
$4.50
16.
For each ventilation system which is not a portion of any
Additional plan review required
by changes, additions or revisions
heating or air - conditioning system authorized by a permit...........
$6.50
17.
For the installation of each hood which is served by
(minimum charge - one hour)
mechanical exhaust, including the ducts for such hood ...............
$6.50
18.
For the installation or relocation of each domestic -type
$27.00
incinerator ......................... ...............................
$11.00
19.
For the installation or relocation of each commercial
or industrial type incinerator ...... ...............................
$45.00
20.
For each appliance or piece of equipment regulated by this
code but not classed in other appliance categories, or
for which no other fee is listed in this code .......................
$6.50
21.
When Chapter 22 of the Uniform Mechanical Code is applicable
(see Section 103), permit fees for fuel -gas piping
shall be as follows:
For each gas - piping system of one to four outlets 1 to 4........ $5.00
For each gas - piping system of over four (4) outlets, per outlet..... $1.00
Other InsDection Fees
1.
Inspections outside of normal business hours....... $63.75(per
hour)
2.
Reinspection fee assessed under
provisions of Section
305( g) .............. ............................... $42.50(per
hour)
3.
Inspections for which no fee is
specifically indicated
.................... ............................... $42.50(per
hour)
(minimum charge - one hour)
4.
Additional plan review required
by changes, additions or revisions
to approved plans ... ............................... $42.50(per
hour)
(minimum charge - one hour)
5.
Replacement of existing boiler or furnace ....................
$27.00
55
TABLE 5
PLUMBING PERMIT FEES
Permit Issuance
1. For issuing each permit ......................... $20.00
2. For issuing each transfer permit ................ $20.00
3. Total permit fee shall not be less than......... $42.50
Unit Fee Schedule (in addition to Items 1 -3 above
1.
For each plumbing fixture on one trap or
a set of fixtures on one trap (including
water, drainage piping and backflow
protection therefore ) ...........................
$
7.00
2.
For each building sewer and each trailer
park sewer ....... ...............................
$15.00
3.
Rain water systems -per drain (inside building)..
$
7.00
4.
For each cesspool (where permitted) ........... $25.00
**
5.
For each private sewage disposal system....... $40.00
**
6.
For each water heater and /or vent ...............
$
7.00
7.
For each gas - piping system of one to five outlets$
5.00
8.
For each additional gas piping system outlet,
per outlet....' ... ...............................
$
1.00
9.
For each industrial waste pretreatment interceptor
including its trap and vent, excepting kitchen -type
grease interceptors functioning as fixture
traps............ ...............................
$
7.00
10.
For each installation, alteration or repair of water
piping and /or water treating equipment, each....
$
7.00
11.
For each repair or alteration of drainage or vent
piping, each fixture ............................
$
7.00
12.
For each lawn sprinkler system on any one meter
including backflow protection devices therefor..
$
7.00
13.
For atmospheric -type vacuum breakers not
included in item 12:
1 to 5 ........... ...............................
$
5.00
over 5, each ..... ...............................
$
1.00
14.
For each backflow protective device other than
atmospheric type vacuum breakers:
2 inch diameter and smaller .....................
$
7.00
over 2 inch diameter ............................
$15.00
Other Inspections and Fees
1. Inspections outside of normal business
hours ............ ............................... $63.75
2. Reinspection fee . ............................... $42.50
3. Inspections for which no fee is specifically
indicated ........ ............................... $42.50
4. Additional plan review required by changes,
additions or revisions to approved plans
(minimum charge; one -half hour) ................. $42.50
5. Replacement of existing hot water heater........ $27.00
* *See Eagle County Land Use Regulations, Chapter 4
56
TABLE 6
ELECTRICAL PERMIT FEES
Residential: (Single ownership Residence)
This includes modular homes, manufactured homes, travel trailers, also duplexes,
tri- plexes and four - plexes. Construction and extensive remodeling and additions
to, (based on enclosed living area)
Not more than 1,000 Sq. Ft ......... ............................... $35.00
Over 1,000 Sq. Ft. and not more than 1,500 Sq. Ft . ............... $55.00
Over 1,500 Sq. Ft. and not more than 2,000 Sq. Ft . ............... $70.00
Per 100 Sq. Ft. in excess of 2,000 Sq. Ft ......................... $ 3.00
All Other Fees:
Except for inspection in mobile homes and travel trailer parks shall be
computed on the dollar value of the electrical installation, including
fixtures and installation costs thereof, and such fees shall be as
follows:
Valuation of Work: (Actual cost to customer)
Not more than $ 300. 00 .............. ............................... $30.00
More than $300.00 but not more than $2,000.00 ..................... $35.00
More than $2,000.00 but not more than $50,000.00 .................. $15.00
per thousand or fraction thereof total valuation
More than $50,000.00 but not more than $500,000.00 ................ $14.00
per thousand or fraction thereof of total valuation PLUS $50.00
More than $ 500, 000. 00 .............. ............................... $13.00
per total valuation PLUS $550.00
Mobile homes and travel parks per space ........................... $30.00
Reinspection on all the above ...... ............................... $35.00
Temporary Power Permits:
Temporary power .......................... ............................... $42.50
For issuing each transfer permit ......... ............................... $20.00
Other Inspection Fees
1.
Inspections outside of normal business
hours .............................................
$63.75(per
hour)
2.
Reinspection fee assessed under provisions
of Section 305( g) .. ...............................
$42.50(per
hour)
3.
Inspections for which no fee is specifically
indicated .......... ...............................
$42.50(per
hour)
(minimum charge - one hour)
4.
Additional plan review required by changes, additions
or revisions to approved plans ...................
$42.50(per
hour)
(minimum charge -one hour)
57
TABLE 7
ELEVATOR PERMIT FEES
TABLE 3- F- ELEVATOR PERMIT FEES, is amended to read as follows:
New Installations
1. Passenger or freight elevator, escalator, moving walk
Up to and including $50,000.00 of valuation . ........................$350.00
Over $50,000.00 of valuation .......... $350.00 plus $6.00 for each $1,000.00
or fraction thereof over $50,000.00
2. Dumbwaiter or private residence elevator
Up to and including $20,000.00 of valuation . ........................$250.00
Over $20,000.00 of valuation .......... $250.00 plus $3.00 for each $1,000.00
or fraction thereof over $20,000.00
Major Alterations
Fees for major alterations shall be as set forth in table 3 -A. Installation
fees include charges for equipment on the conveyance side of the disconnect
switch.
Other Inspections and Fees:
1. Inspections outside of normal business hours, per hour ..............$50.00*
each
(Minimum charge -two hours)
For
each
2. Reinspection fees assessed under
provisions of Section 305.8,
For
each
Per inspection ..............................
........................$50.00*
For
3. Inspections for which no fee is
specifically indicated, per hour .... $50.00*
(Minimum charge -one half hour)
4. Additional plan review required
by changes, additions or revisions
to plans
for which an initial review has
been completed ......................$50.00*
(Minimum charge -one half hour)
*Or the total hourly cost to the jurisdiction, whichever is greatest. This
cost shall include supervision, overhead, equipment, hourly wages and fringe
benefits of the employees involved.
TABLE 3- F- ELEVATOR ANNUAL CERTIFICATES OF INSPECTION FEES, is amended to read
as follows:
For
each
elevator ............................... ........................$150.00
For
each
escalator or moving walk ............... ........................$150.00
For
each
commercial dumbwaiter .................. .........................$75.00
For
each
platform lift .......................... .........................$75.00
(Notes: 1. Each escalator or moving walk unit powered by one motor shall be
considered as separate escalator or moving walk. 2. Residential elevators do
not require certificates of inspection.)
58
TABLE 8
FACTORY BUILT CffIHNEY ENC] RE
ENCLOSURE AND GYPSUM BOARD
EXTENDED TO THE FLOOR.
59
LL TO THE UPPER EDGE
E TOP PLATE
LINE
ES ON THE INTERIOR 0
BE COVERED WITH 5/8"
OARD AND FIRE TAPED.
S MAY BE APPROVED
OFFICIAL.
As of January 1, 1982, an address sing board will be required at all building
sites for construction permitted through the Eagle County Building
See UBC 1979, Section 305(c). A County Sign Permit is not
required in this case.
This requirement will help County Building Inspectors as well as sub-
contractors and suppliers to find the job site. The sign board will also
provide a place to mount the permit card where it can be signed during various
inspections.
The dimensions shown are guidelines only. Your sign must be legible from the
road that serves your driveway and must provide weatherproof cover for the
building permit.
Address on Outer Surface
(Lot &'Block Numbers Optional)
B. P.* 0000' Haut the
Permit Card
ADDRESSon the Inner
1234 Your Street Surface \
Lot * Block
CONTRACTORS NAME
FRONT VIEW
1/2" ply
FOR INFORMATION CALL: Eagle 328 -8735
El Jebel 963 -0285
:I
SIDE VIEW
Engineering Department
(970) 328 -8760
Fax: (970) 328 -7185
TDD: (970) 328 -8797
EAGLE COUNTY, COLORADO
M E M O R A N D U M
TO: Community Development
FROM: Engineering Department
DATE: September 12, 1995
Eagle Countv Building
V P.O Box 850 y
500 Broadwav
Eagle, Colorado 81631 -0850
SUBJECT: Construction Within the Public Way of Eagle County
It shall be unlawful for any person to construct in the public way unless such
person shall first have obtained a permit for the performance of such
construction. Construction Within the Public Way shall mean to construct, re-
construct, build, re- build, make pipeline, cable, sidewalk, curb, gutter,
driveway, or street, or to perform other work of any kind within the public way
which will result in the physical alteration therof. Public way shall mean
under the control and jurisdiction to the County of Eagle, State of Colorado.
A public way shall include, by way of example only, drainage easements, rights -
of -way, and roads over private lands dedicated to public uses by deed,
subdivision plat or other legal document to that effect.
Each and every person desiring to perform construction of any kind, in a public
way within the County, shall make application for a permit to construct within
the public way. Such application shall be filed with the Eagle County
Engineering Department on forms to be furnished by them.
For further information and a copy of the Regulations for Construction Within
the Public Way of Eagle County, please contact the Engineering Department at
328 -8760.
61
PERMIT TO CONSTRUCT WITHIN THE PUBLIC WAY
A PERMIT M CMGT UCi' SM TIE RAW WAY
IS REOU1iED FOR ALL CMSiRUCU 0 CUJ0M G
DRIVEWAYS AND URM EICAVA110N) WIM 11E CMW RIGHT -OF WAY.
THESE PERMITS MAY BE OBTAIED AT-
EAGLE CM11M DOESMIG DEPARIIENT
POB Rio
EAGLE; 00 81631
FOR RRM WMMATIOK PHONE (970) 326 -8760
0 0 EDGE OF DRIVE
z
01 1 So MIN. DIA.
c CULVERT
U W
CENTERUNE OF IVEW _ 16' (MIN.) DIA. CULVERT
0
Z 60, -90,
I N I �
z I EDGE OF DRIVE
1 s•
ANY WORK IN THIS AREA IS WORK WITHIN THE PUBUC WAY AND WILL REQUIRE
A PERMIT SEPARATE FROM THE BUILDING PERMIT. EXCEPT FOR THE DRIVEWAY AND
CULVERT, WHICH ARE INCLUDED IN THE BUILDING PERMIT FOR NEW CONSTRUCTION.
LOW POINT
RECOMMENDED MAX. GRADE
2% OF 10%
PAVEMENTS 3I
GRAVEL BASE
NPROVE DITCH THROUGH
PROPERTY AS NECESSARY
TO MATCH CULVERT
DEPTH