HomeMy WebLinkAbout901 Red Canyon Cr Rd - 194125102007 - 1785-98ISINDIVIDUAL SEWAGE DISPOSAL SYSTEM PERMIT EAGLE COUNTY ENVIRONMENTAL HEALTH DIVISION P.O. Box 179 - 500 Broadway • Eagle, CO 81631 Telephone: (970) 328-8755 COPY OF PERMIT MUST BE POSTED AT INSTALLATION SITE. PERMIT NO. 1785-98 BP NO. 11962 OWNER: MACK AND NANCY NICHOLS PHONE: 314-878-7668 MAILING ADDRESS: 12300 HALSGAME CREVE COLUR MO 83141 APPLICANT: GEORGE SISNEROS PHONE: 970-827-5231 SYSTEM LOCATION: LOT 7 RED CANTON ESTATES TAX PARCEL NO. 1941-251-02-007 LICENSED INSTALLER: EDWARDS EXCAVATING DON JOHNSON LICENSE NO. 35-98 PHONE: 970-926-3395 DESIGN ENGINEER: LKP ENGINEERING LUIZA PETROVSKA PHONE NO. 970-827-9088 INSTALLATION HEREBY GRANTED FOR THE FOLLOWING: 1500 GALLON SEPTIC TANK 1500 SQUARE FEET OF ABSORPTION AREA VIA 48 INFILTRATOR UNITS AS PER ENGINEER'S DESIGN. SPECIAL REQUIREMENTS: INSTALL AS PER ENGINEER'S DESIGN DATED 5/29/98. BE SURE TO MAINTAIN 50 FOOT SETBACK FROM THE POND. DOUBLE ENCASE AND INSULATE EFFLUENT LINE UNDER STREAM CROSSING. ENGINEER IS RESPONSIBLE FOR FINAL INSPEC- TION. BUILDING CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED WITHOUT SEPTIC SYSTEM APPROVAL. ENVIRONMENTAL HEALTH APPROVAL: L DATE: JUNE 4 1998 CONDITIONS: 1. ALL INSTALLATIONS MUST COMPLY WITH ALL REQUIREMENTS OF THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM REGULATIONS, ADOPTED PURSUANT TO AUTHORITY GRANTED IN 25-10-104, 1973, AS AMENDED. 2. THIS PERMIT IS VALID ONLY FOR CONNECTION TO STRUCTURES WHICH HAVE FULLY COMPLIED WITH COUNTY ZONING AND BUILDING REQUIREMENTS, CONNECTION TO OR USE WITH ANY DWELLING OR STRUCTURE NOT APPROVED BY THE ZONING AND BUILDING DEPARTMENTS SHALL AUTOMATICALLY BE A VIOLATION OF A REQUIREMENT OF THE PERMIT BOTH LEGAL ACTION AND REVOCATION OF THE PERMIT. 3. CHAPTER IV, SECTION 4.03.29 REQUIRES ANY PERSON WHO CONSTRUCTS, ALTERS OR INSTALLS AN INDIVIDUAL SEWAGE DISPOSAL SYSTEM TO BE LICENSED. FINAL APPROVAL OF SYSTEM (TO BE COMPLETED BY INSPECTOR): NO SYSTEM SHALL BE DEEMED TO BE IN COMPLIANCE WITH THE EAGLE COUNTY INDIVIDUAL SEWAGE DISPOSAL SYSTEM REGULATIONS UNTIL THE SYSTEM IS APPROVED PRIOR TO COVERING ANY PORTION OF THE SYSTEM. INSTALLED ABSORPTION OR DISPERSAL AREA: 1500 SQUARE FEET (VIA 48 INFILTRATOR UNITS ) INSTALLED CONCRETE TANK: 1500 GALLONS IS LOCATED DEGREES AND 34 FEET FROM THE MAIN RESIDENCE. COMMENTS: FINAL ENGINEER CERTIFICATION RECEIVED 9-24-9$ SEE SITE TAN AND ENGINEER FINAL LETTER FOR SYSTEM COMPONENTS AND LOCATIONS. ANY ITEM NOT MEETING REQUIREMENTS WILL BE CORRECTED BEFORE FINAL APPROVAL OF SYSTEM IS MADE. ARRANGE A RE -INSPECTION WHEN WORK IS COMPLETED. / ENVIRONMENTAL HEALTH APPROVAL JC/- DATE: SEPT. 24, 1998 I iete Applications Will NOT Be Accepted Flan MUST be attached) ISDS Permit # Building Permit APPLICATION FOR INDIVIDUAL SEWAGE DISPOSAL SYSTEM PERMIT ENVIRONMENTAL HEALTH OFFICE - EAGLE COUNTY P. 0. BOX 179 EAGLE, CO 81631 328-8755/927-3823 (El Jebel) PERMIT APPLICATION FEE $150.00 PERCOLATION TEST FEE $200.00 MAKE ALL REMITTANCE PAYABLE TO: "EAGLE COUNTY TREASURER" IMMOMM-M wM MAILING ADDRESS - PHONE: 5�70 Y C—f E-vo� U(D)L4(,--1 �L6 9 APPLICANT/ CONTACT PERSON: (1501�GC� )6/VZp265 PHONE: LICENSED SYSTEMS CONTRACTOR: PHONE: COMPANY/DBA: ADDRESS: PERMIT APPLICATION IS FOR: NEW INSTALLATION ( ) ALTERATION ( ) REPAIR LOCATION OF PROPOSED INDIVIDUAL SEWAGE DISPOSAL SYSTEM: Legal Description: t 0 7' V Pe, Tax Parcel Number: lqqj- Physical Address �/ 0111w BUILDING TYPE: (Check applicable category) &.4 Residential/Single Family Residential/Multi-Family* Commercial/Industrial* TYPE OF WATER SUPPLY: (Check applicable category) Well ( ) Spring ( ) Surface Public Name of Supplier: Lot Size: 5- acxE,�5 Number of Bedrooms Number of Bedrooms Type *These systems require design /b ,y a Registered Professional Engineer SIGNATURE: Date: AMOUNT PAID: RECEIPT #: 2-71 DATE: 6-13 / P' CHECK #: 4-,,;2 4-1 -- CASHIER: k� Community Development Department (970) 328-8730 Fax: (970) 328-7185 TDD: (970) 328-8797 EAGLE COUNTY, COLORADO Date: June 4, 1998 TO: Edwards Excavating Eagle County Building P.O. Box 179 500 Broadway Eagle, Colorado 81631-0179 FROM: Environmental Health Division RE: Issuance of Individual Sewage Disposal System Permit No. 1785-98. Tax Parcel # 1941-251-02-007. Property Location: Lot #7, Red Canyon Estates, Edwards, CO., Nichols residence. Enclosed is your ISDS Permit No. 1785-98. It is valid for 120 days. The enclosed copy of the permit must be posted at the installation site. Any changes in plans or specifications invalidates the permit unless otherwise approved. Systems designed by a Registered Professional Engineer must be certified by the Engineer indicating that the system was installed as specified. Eagle County does not perform final inspections on engineer designed systems. Your TCO will not be issued until our office receives this certification. Permit specifications are minimum requirements only, and should be brought to the property owner's attention. This permit does not indicate conformance with other Eagle County requirements. If you have any questions, please feel free to contact the Environmental Health Division at 328- 8755. cc: files LKP Engineering, Luiza Petrovska September 24, 1998 Mack and Nancy Nichols 12300 Halsgame Creve Colur, MO 83151 RE: Final of ISDS Permit #1785-98, Tax Parcel #1941-251-02-007. Property location: 901 Red Canyon Rd., Edwards, CO. Dear Mr & Mrs. Nichols: This letter is to inform you that the above referenced ISDS Permit has been inspected and finalized. Enclosed is a copy to retain for your records. This permit does not indicate compliance with any other Eagle County requirements. Also enclosed is a brochure regarding the care of your septic system. Be aware that later changes to your building may require appropriate alterations of your septic system. If you have any questions regarding this permit, please contact the Eagle County Environmental Health Division at (970) 328-8755. Sincerely, il Janet Kohl Environmental Health Department Eagle County Community Development ENCL:Informational Brochure Final ISDS Permit cc: files 09/23/1998 10:43 970-927-9029 LKP ENGINEERING, INC PAGE 01 WIN MR-ft'l September 23, 1998 Mr. Steve Riden Steve Riden Architects P.O. Box 3238 Vail, CO 81658 Dear Steve: RE: Lupection of Septic System Installation Nichols Residence Lot 7, Red Canyon Estates Eagle County, Colorado Project No. 9810 - Permit No. 1785-98 At the request of Rick from Graystone Construction, on July 22 and September 16, 1998, we visited the construction site on Lot 7, Red Canyon estates, near Eagle, Eagle County, Colorado. The purpose of our site visit was to observe the installation of the septic system. They installed the system in overall compliance with the septic system design, Drawing No. 98 1 OSD.DWG, dated May 29, 1998, The system was connected to the main residence as shown on the above named drawing, From the house to the first cleanout was 4 feet. From there to the septic tank was 30 feet. They installed 1500-gallon, two compartments, a precast, concrete septic tank. The tank had Moot risers on both Inspection covers. From the tank to the stream crossing was 90 feet and from the steam crossing to the cleanout was 30 feet. We recommended installation of an additional cleanout on the west side of the stream crossing. At the stream crossing the 4-inch sewer line was encased in an 8-inch PVC pipe. From the crossing to the edge of the pond was 105 feet. From the cast cleanout the line turned at 45 degrees for 52 feet and 22 degrees for 8 feet to the next elmout. From the cleanout to the first Infiltrator trench was 62 feet, Also, from the first infiltrator trench to the edge of the pond was 75 feet. Forty-eight Standard Infiltrator Chambers were installed in four trenches with 12 Infiltrators each. The infiltrators were connected with serial distribution. In the first and last infiltrator of each trench, inspection ports were installed, Horizontal distance from center to center of the trenches, was 9 feet or snore. All piping was SDR-35, 4-inch PVC, The depth of the trenches was two to three feet. The soil profile in the trenches was consistent with the soil exposed in the profile hole. If you have any questions, please do not hesitate to call. Sincerely, L" Engineer r�zll 1 Z-117 Luiza Petrovsk President cc: Ms. Heather Savalox, Eagle County Environmental Health Division, fax: 328-7185 P.O, Box 2837, Edwuds, Colorado 91632 - (970) 926.9088 Tel * (970) 926-9089 Fax OF ROAD OF<R=s Design percolation rate 7• - 25 mmufes per inch Number of bMraoms = 4 am eany craw = wnox peon / mrn x rs 9onpn /p<rsan/der x rsos j / 33 gol[pn — — g, Zee') \. / � L_— I I \ aD g lral two a p rmenr P case aonarere ran y aPl d conarere or eaprwienr Dee Am 900 _ _ _ — Bo d A P ! Rate: l00 — — — ODPe/B69Pd/z/ / Chamber sire m m OnRgare+ion wen Po onowee so Percent ,x .ecomme�dee.` / carrecte = ]50 xf ln(r/tr— Chamber 1S5 s.f >2 /nfi/+rotors Gi FI RP U 8 r ear Chambers m lour (rencnas with in eacM1. W l I I — — l l l I / I l 0 N / / 1. The building sewer line /tom the hwse ro the sepf/c tank shell here 0 1/4 inch per W O m the building sewer shall be limited fa 45 tlegrees. W R O \ / Q / / / / / / / 1 \ \ \ \ / / \ / / / 2 The septc took shall be Installed level ]he took shall how remowble covers or monho/es to wehin 8 n es or the /'mshad rode. /or inspection and cleanin9'I Q ~ U O / \ \ \ \ 3ch Excpwfe three ()9/eer wbe trenches. Th ha-�zan o is once rem s ew sidewoll between fh d f / tl all Yo e O O U W J Ftn z fqy and the sidewalls o/ the rr '- moll tie raked tv —rnvta sme ring i; Assemble and instal/ Me In ultra Chambers in fhe trenches according to the manufacturers tn � - \ \ \ reaammendationx 6. Back tll the sidewoll area with native on -site sell !ar proper suPPorf. \ \ \ \ \ � \ \ \ O w I _ Irwr � \ a Bopknr the trenmee Wien o minimam of Ia inenes Pr tamp<d sal oo trPlRc me 0. ` \ \ \ A— wnrare pwr \ 8. All installations moll the regulations o/ the Eagle Cvvnry Environmental Health Division, \ I— A A \ \ \ meet rules antl Chapter 4, Individual Sewage DRpasol Sysfeme. 11 fie septic System lnsrallvtron xnall be lnspectetl by the Design Engineer pr to bockllling. 1500 GALLON TWO COMPARTMENT CONCRETE SEPTIC TANK \Q \\\\\ \\\\ \ \\ CO \ \ \L�\\ \ \ \ \ \\\ \ \ GRAPHIC SCALE P \ f O.� S' a : / _ — — — — — _ \ g so' ELBOW 22-1/2 ELBOW \ \ \ \. \ \ \ \ \ \ \ \ _ = ` _ \ i DIjGN — — — — — — _\ \ so• ELeowe�:°•A"ERB•ti'ff 6' MINIMUM =S,szenc?= �'—_ =��_ =\ _ — — _ _ bash `\ ` _ — £ RECEIVED CHAMBER � � _ _� \\ _ _ _ _ � � , _ _ — — — — — , \ \ \ _ RECEIVED DETAIL A — A RB. 23 mrerop er rnrh J2 mine m 9 P' `fes Per mcn \ \ FE�dGE` N. T..S ��N 3 1998 lotion rote r cammendae lw d sl n r �s maeed an \ WZRR LE couNrc LP - \ S —� \ �/ — — _ P h�Vt<sr done MYe16 1998 8 P. \,(//\ — — - ATV DEVELOPMEM Bh L.P. — 1O \ / — O-8 OLO FILL CONSISBNC DF D 6 OLD FILL CON.bSPNC D< oO — — _ — — \\\ ,0 1Q2a — REDOrsH-eaolm curEr sANo REoorsH-eaC-ILA 11 IA. . STANDARD INFILTRATOR B, serosD.oxc B-8' REDDISH-BROKN SANDY GRAVEL• 6-8' REDDISH-BRONN EANOr CRA VEL. ANGULAR.. a—Y. ANGULAR.. Br Srz}[N xlv[N ARouRCrs I OF i